{"title":"LCL-type Grid-connected Inverters with PI and IMC in Weak Grid","authors":"Wang Kai, L. Juan, Zhang Shengguo","doi":"10.1145/3372047.3372082","DOIUrl":"https://doi.org/10.1145/3372047.3372082","url":null,"abstract":"Under the high penetration of renewable energy, the power grid may features as the weak grid, which contains a large set of grid impedance values and varies of harmonics. The stability problem may be aroused by the grid impedance and the injected grid current can be greatly distorted by the grid voltage harmonics. For grid connected inverters (GCI) with voltage feed-forward and time delay, PI control can decrease the phase of open loop transfer function and cause the left shift and disappearance of negative crossing points, the left shift may cause reduce of phase margin and the disappearance may cause instability of the grid connected inverter system. Hence internal model controller (IMC) is used to replace PI controller for improvement of low frequency phase, so the negative crossing point is kept and the adaptability to the grid impedance is improved. Simulation results verify IMC has better robustness of grid, transient performance and suppression capability of background harmonic.","PeriodicalId":335408,"journal":{"name":"Proceedings of the 2019 The 2nd International Conference on Robotics, Control and Automation Engineering","volume":"54 1","pages":"0"},"PeriodicalIF":0.0,"publicationDate":"2019-11-16","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"134139143","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":0,"RegionCategory":"","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}