A non-invasive measurement-based modeling for assessing power transformer aging and reliability

IF 6.1 2区 工程技术 Q1 ENGINEERING, MULTIDISCIPLINARY
Measurement Pub Date : 2026-05-05 Epub Date: 2026-02-28 DOI:10.1016/j.measurement.2026.120968
D. Mishra , V. Chopra , D. Mishra , A. Baral
{"title":"A non-invasive measurement-based modeling for assessing power transformer aging and reliability","authors":"D. Mishra ,&nbsp;V. Chopra ,&nbsp;D. Mishra ,&nbsp;A. Baral","doi":"10.1016/j.measurement.2026.120968","DOIUrl":null,"url":null,"abstract":"<div><div>A non-invasive and quantitative methodology for assessing the health of oil–paper insulation in power transformers is presented in this paper. Paper moisture (moisture in cellulosic part of insulation) (<em>pm</em>) and dissipation factor (tan <em>δ</em>) are widely recognized as critical indicators of insulation aging and overall system reliability, yet their accurate determination often requires intrusive or time-consuming procedures. To overcome these limitations, this work introduces an Aging Factor (<em>A<sub>F</sub></em>), computed directly from the complete depolarization current profile by estimating the branch parameters of a Debye-based insulation model and evaluating the ratio of charge contributions associated with the two branches having the largest time constants. This approach utilizes the full dielectric relaxation behaviour of the insulation without relying on extensive curve fitting or lengthy frequency-domain measurements. The method was validated using ten laboratory-prepared oil-impregnated insulation samples and subsequently applied to ten in-service power transformers. The AF showed strong correlation with both %pm and %tan δ, enabling their prediction with accuracies of 2.47% and 5.0%, respectively, with all deviations confined within ± 5%. By providing a robust, non-invasive, and time-efficient means to estimate key insulation-health indicators, the proposed AF-based technique supports condition-based maintenance and enhances diagnostic reliability for power transformer insulation systems.</div></div>","PeriodicalId":18349,"journal":{"name":"Measurement","volume":"272 ","pages":"Article 120968"},"PeriodicalIF":6.1000,"publicationDate":"2026-05-05","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Measurement","FirstCategoryId":"5","ListUrlMain":"https://www.sciencedirect.com/science/article/pii/S0263224126006779","RegionNum":2,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"2026/2/28 0:00:00","PubModel":"Epub","JCR":"Q1","JCRName":"ENGINEERING, MULTIDISCIPLINARY","Score":null,"Total":0}
引用次数: 0

Abstract

A non-invasive and quantitative methodology for assessing the health of oil–paper insulation in power transformers is presented in this paper. Paper moisture (moisture in cellulosic part of insulation) (pm) and dissipation factor (tan δ) are widely recognized as critical indicators of insulation aging and overall system reliability, yet their accurate determination often requires intrusive or time-consuming procedures. To overcome these limitations, this work introduces an Aging Factor (AF), computed directly from the complete depolarization current profile by estimating the branch parameters of a Debye-based insulation model and evaluating the ratio of charge contributions associated with the two branches having the largest time constants. This approach utilizes the full dielectric relaxation behaviour of the insulation without relying on extensive curve fitting or lengthy frequency-domain measurements. The method was validated using ten laboratory-prepared oil-impregnated insulation samples and subsequently applied to ten in-service power transformers. The AF showed strong correlation with both %pm and %tan δ, enabling their prediction with accuracies of 2.47% and 5.0%, respectively, with all deviations confined within ± 5%. By providing a robust, non-invasive, and time-efficient means to estimate key insulation-health indicators, the proposed AF-based technique supports condition-based maintenance and enhances diagnostic reliability for power transformer insulation systems.
基于非侵入性测量的电力变压器老化和可靠性评估模型
本文提出了一种非侵入性的、定量的电力变压器油纸绝缘健康评估方法。纸张水分(绝缘纤维部分的水分)(pm)和耗散系数(tan δ)被广泛认为是绝缘老化和整个系统可靠性的关键指标,但它们的准确测定通常需要侵入性或耗时的过程。为了克服这些限制,本工作引入了老化因子(AF),通过估计基于debye的绝缘模型的支路参数并评估与具有最大时间常数的两个支路相关的电荷贡献比,直接从完整的去极化电流剖面计算。这种方法利用绝缘的完全介电弛豫行为,而不依赖于广泛的曲线拟合或冗长的频域测量。用10个实验室制备的油浸绝缘样品对该方法进行了验证,并应用于10台在役电力变压器。AF与%pm和%tan δ均表现出较强的相关性,预测精度分别为2.47%和5.0%,所有偏差限制在±5%以内。通过提供一种强大的、非侵入性的、省时的方法来估计关键的绝缘健康指标,所提出的基于af的技术支持基于状态的维护,并提高了电力变压器绝缘系统的诊断可靠性。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
Measurement
Measurement 工程技术-工程:综合
CiteScore
10.20
自引率
12.50%
发文量
1589
审稿时长
12.1 months
期刊介绍: Contributions are invited on novel achievements in all fields of measurement and instrumentation science and technology. Authors are encouraged to submit novel material, whose ultimate goal is an advancement in the state of the art of: measurement and metrology fundamentals, sensors, measurement instruments, measurement and estimation techniques, measurement data processing and fusion algorithms, evaluation procedures and methodologies for plants and industrial processes, performance analysis of systems, processes and algorithms, mathematical models for measurement-oriented purposes, distributed measurement systems in a connected world.
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书