Cheng-Min Yang , M. Muneeshwaran , Yifeng Hu , Gustavo Pottker , Samuel F. Yana Motta
{"title":"新一代介质流体的池沸腾传热评估:Opteon™2P50","authors":"Cheng-Min Yang ,&nbsp;M. Muneeshwaran ,&nbsp;Yifeng Hu ,&nbsp;Gustavo Pottker ,&nbsp;Samuel F. Yana Motta","doi":"10.1016/j.ijft.2025.101379","DOIUrl":null,"url":null,"abstract":"<div><div>The growing use of artificial intelligence has led to heavy thermal loads and high heat dissipation rates in data centers. Conventional air-cooled technologies are not able to fulfill these requirements. To overcome these challenges, two-phase immersion cooling (2PIC) has emerged as one of the leading technologies for high power-density chips. 2PIC increases the heat dissipation rate and efficiency of the system while reducing the footprint of the cooling equipment. A fluid with adequate dielectric properties, a suitable normal boiling temperature to maintain chip temperatures, and good material compatibility, is desired for 2PIC system. In this study, the pool boiling heat transfer of a new developmental dielectric fluid, Opteon™ 2P50, was experimentally investigated. The heat transfer coefficients at various heat fluxes (20–150 kW/m<sup>2</sup>) and the critical heat flux were measured using a smooth aluminum surface. Compared with HFE-7100, Opteon™ 2P50 shows higher heat transfer coefficient (up to 59% higher) and a slightly lower value of critical heat flux (around 5.9% lower). The modified Cooper correlation with the optimized leading constant resulted in reliable prediction accuracy with a 5.3% mean absolute error percentage. Overall, these results indicate that the new dielectric fluid provides similar thermal performance to some legacy fluids.</div></div>","PeriodicalId":36341,"journal":{"name":"International Journal of Thermofluids","volume":"29 ","pages":"Article 101379"},"PeriodicalIF":0.0000,"publicationDate":"2025-08-15","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Pool boiling heat transfer evaluation of next-generation dielectric fluid: Opteon™ 2P50\",\"authors\":\"Cheng-Min Yang ,&nbsp;M. Muneeshwaran ,&nbsp;Yifeng Hu ,&nbsp;Gustavo Pottker ,&nbsp;Samuel F. Yana Motta\",\"doi\":\"10.1016/j.ijft.2025.101379\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"<div><div>The growing use of artificial intelligence has led to heavy thermal loads and high heat dissipation rates in data centers. Conventional air-cooled technologies are not able to fulfill these requirements. To overcome these challenges, two-phase immersion cooling (2PIC) has emerged as one of the leading technologies for high power-density chips. 2PIC increases the heat dissipation rate and efficiency of the system while reducing the footprint of the cooling equipment. A fluid with adequate dielectric properties, a suitable normal boiling temperature to maintain chip temperatures, and good material compatibility, is desired for 2PIC system. In this study, the pool boiling heat transfer of a new developmental dielectric fluid, Opteon™ 2P50, was experimentally investigated. The heat transfer coefficients at various heat fluxes (20–150 kW/m<sup>2</sup>) and the critical heat flux were measured using a smooth aluminum surface. Compared with HFE-7100, Opteon™ 2P50 shows higher heat transfer coefficient (up to 59% higher) and a slightly lower value of critical heat flux (around 5.9% lower). The modified Cooper correlation with the optimized leading constant resulted in reliable prediction accuracy with a 5.3% mean absolute error percentage. Overall, these results indicate that the new dielectric fluid provides similar thermal performance to some legacy fluids.</div></div>\",\"PeriodicalId\":36341,\"journal\":{\"name\":\"International Journal of Thermofluids\",\"volume\":\"29 \",\"pages\":\"Article 101379\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2025-08-15\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"International Journal of Thermofluids\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://www.sciencedirect.com/science/article/pii/S2666202725003258\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"Q1\",\"JCRName\":\"Chemical Engineering\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"International Journal of Thermofluids","FirstCategoryId":"1085","ListUrlMain":"https://www.sciencedirect.com/science/article/pii/S2666202725003258","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q1","JCRName":"Chemical Engineering","Score":null,"Total":0}
引用次数: 0

摘要

越来越多的人工智能应用导致数据中心的热负荷和高散热率。传统的风冷技术无法满足这些要求。为了克服这些挑战,两相浸入式冷却(2PIC)已经成为高功率密度芯片的领先技术之一。2PIC提高了系统的散热速率和散热效率,同时减少了制冷设备的占地面积。2PIC系统需要具有适当介电性能、适当的正常沸点温度以维持芯片温度和良好的材料相容性的流体。在本研究中,实验研究了新型介质流体Opteon™2P50的池沸腾传热。采用光滑铝表面测量了不同热流密度(20 ~ 150kw /m2)下的换热系数和临界热流密度。与HFE-7100相比,Opteon™2P50具有更高的传热系数(高达59%)和略低的临界热流密度值(约5.9%)。修正后的库珀相关系数与优化后的先导常数的预测精度可靠,平均绝对误差百分比为5.3%。总的来说,这些结果表明,新的介电流体与一些传统流体具有相似的热性能。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Pool boiling heat transfer evaluation of next-generation dielectric fluid: Opteon™ 2P50
The growing use of artificial intelligence has led to heavy thermal loads and high heat dissipation rates in data centers. Conventional air-cooled technologies are not able to fulfill these requirements. To overcome these challenges, two-phase immersion cooling (2PIC) has emerged as one of the leading technologies for high power-density chips. 2PIC increases the heat dissipation rate and efficiency of the system while reducing the footprint of the cooling equipment. A fluid with adequate dielectric properties, a suitable normal boiling temperature to maintain chip temperatures, and good material compatibility, is desired for 2PIC system. In this study, the pool boiling heat transfer of a new developmental dielectric fluid, Opteon™ 2P50, was experimentally investigated. The heat transfer coefficients at various heat fluxes (20–150 kW/m2) and the critical heat flux were measured using a smooth aluminum surface. Compared with HFE-7100, Opteon™ 2P50 shows higher heat transfer coefficient (up to 59% higher) and a slightly lower value of critical heat flux (around 5.9% lower). The modified Cooper correlation with the optimized leading constant resulted in reliable prediction accuracy with a 5.3% mean absolute error percentage. Overall, these results indicate that the new dielectric fluid provides similar thermal performance to some legacy fluids.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
International Journal of Thermofluids
International Journal of Thermofluids Engineering-Mechanical Engineering
CiteScore
10.10
自引率
0.00%
发文量
111
审稿时长
66 days
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信