利用基于有限元法的参数分析确定变压器槽壁水平磁分流器的位置和尺寸

Mehmet Çeçen, Bilal Gümüş, İrem Hazar
{"title":"利用基于有限元法的参数分析确定变压器槽壁水平磁分流器的位置和尺寸","authors":"Mehmet Çeçen, Bilal Gümüş, İrem Hazar","doi":"10.3390/app14166930","DOIUrl":null,"url":null,"abstract":"Magnetic shunts efficiently mitigate losses caused by leakage currents in the tank walls of power transformers. Transformer manufacturers frequently utilize vertical magnetic shunts positioned on the inside surfaces of the transformer tank walls. This study investigated the optimum use of horizontal shunts in a power transformer. A 50 MVA power transformer, manufactured on a commercial scale and featuring optimized vertical magnetic shunts integrated into the wall structure, was analyzed using the 3D finite element method for 100 ms at full load. Simulations for analyses were performed using a commercial ANSYS Electronics Desktop 2021 R1 FEM software program. The model’s validity was demonstrated by verifying the analysis results with experimental tank loss values. Tank loss samples were obtained by analyzing the transformer tank for two milliseconds with vertical magnetic shunts only on the long front wall and the short side wall. Using these loss samples as a reference, parametric analyses were performed for two milliseconds with horizontal magnetic shunts only on the short side wall and only on the long front wall of the tank. A tank model with horizontal magnetic shunts of an appropriate location and size was obtained via the parametric analyses. This model was analyzed for 100 milliseconds at full load and compared with the experimental results of the transformer manufacturer’s vertical magnetic shunt transformer. According to the results, a saving of 25.83% was achieved in the horizontal magnetic shunt volume compared with the vertical magnetic shunt volume. The maximum magnetic flux density was lower in the horizontal magnetic shunts, and the maximum current density was lower in the transformer tank with horizontal magnetic shunts.","PeriodicalId":502388,"journal":{"name":"Applied Sciences","volume":"44 17","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2024-08-08","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Determining the Positions and Dimensions of Horizontal Magnetic Shunts in Transformer Tank Walls Using Parametric Analyses Based on the Finite Element Method\",\"authors\":\"Mehmet Çeçen, Bilal Gümüş, İrem Hazar\",\"doi\":\"10.3390/app14166930\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Magnetic shunts efficiently mitigate losses caused by leakage currents in the tank walls of power transformers. Transformer manufacturers frequently utilize vertical magnetic shunts positioned on the inside surfaces of the transformer tank walls. This study investigated the optimum use of horizontal shunts in a power transformer. A 50 MVA power transformer, manufactured on a commercial scale and featuring optimized vertical magnetic shunts integrated into the wall structure, was analyzed using the 3D finite element method for 100 ms at full load. Simulations for analyses were performed using a commercial ANSYS Electronics Desktop 2021 R1 FEM software program. The model’s validity was demonstrated by verifying the analysis results with experimental tank loss values. Tank loss samples were obtained by analyzing the transformer tank for two milliseconds with vertical magnetic shunts only on the long front wall and the short side wall. Using these loss samples as a reference, parametric analyses were performed for two milliseconds with horizontal magnetic shunts only on the short side wall and only on the long front wall of the tank. A tank model with horizontal magnetic shunts of an appropriate location and size was obtained via the parametric analyses. This model was analyzed for 100 milliseconds at full load and compared with the experimental results of the transformer manufacturer’s vertical magnetic shunt transformer. According to the results, a saving of 25.83% was achieved in the horizontal magnetic shunt volume compared with the vertical magnetic shunt volume. The maximum magnetic flux density was lower in the horizontal magnetic shunts, and the maximum current density was lower in the transformer tank with horizontal magnetic shunts.\",\"PeriodicalId\":502388,\"journal\":{\"name\":\"Applied Sciences\",\"volume\":\"44 17\",\"pages\":\"\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2024-08-08\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Applied Sciences\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.3390/app14166930\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Applied Sciences","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.3390/app14166930","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

磁分流器可有效降低电力变压器油箱壁漏电电流造成的损耗。变压器制造商通常使用安装在变压器油箱壁内侧表面的垂直磁分流器。本研究调查了电力变压器中水平分流器的最佳使用情况。我们使用三维有限元法对商业规模制造的 50 MVA 电力变压器进行了分析,该变压器在满负荷情况下运行了 100 毫秒,变压器壁结构中集成了经过优化的垂直磁分流器。分析仿真使用的是商用 ANSYS Electronics Desktop 2021 R1 FEM 软件程序。通过将分析结果与试验水箱损耗值进行验证,证明了模型的有效性。油箱损耗样本是通过对变压器油箱进行两毫秒的分析获得的,分析时仅在长前壁和短侧壁上进行了垂直磁分流。以这些损耗样本为参考,只在短侧壁和油箱长前壁上安装水平磁分流器的情况下,进行了两毫秒的参数分析。通过参数分析获得了一个具有适当位置和尺寸的水平磁分流器的水箱模型。对该模型进行了 100 毫秒满负荷分析,并与变压器制造商生产的垂直磁分路变压器的实验结果进行了比较。结果显示,水平磁分流体积比垂直磁分流体积节省了 25.83%。水平磁分流变压器的最大磁通密度较低,水平磁分流变压器油箱的最大电流密度也较低。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Determining the Positions and Dimensions of Horizontal Magnetic Shunts in Transformer Tank Walls Using Parametric Analyses Based on the Finite Element Method
Magnetic shunts efficiently mitigate losses caused by leakage currents in the tank walls of power transformers. Transformer manufacturers frequently utilize vertical magnetic shunts positioned on the inside surfaces of the transformer tank walls. This study investigated the optimum use of horizontal shunts in a power transformer. A 50 MVA power transformer, manufactured on a commercial scale and featuring optimized vertical magnetic shunts integrated into the wall structure, was analyzed using the 3D finite element method for 100 ms at full load. Simulations for analyses were performed using a commercial ANSYS Electronics Desktop 2021 R1 FEM software program. The model’s validity was demonstrated by verifying the analysis results with experimental tank loss values. Tank loss samples were obtained by analyzing the transformer tank for two milliseconds with vertical magnetic shunts only on the long front wall and the short side wall. Using these loss samples as a reference, parametric analyses were performed for two milliseconds with horizontal magnetic shunts only on the short side wall and only on the long front wall of the tank. A tank model with horizontal magnetic shunts of an appropriate location and size was obtained via the parametric analyses. This model was analyzed for 100 milliseconds at full load and compared with the experimental results of the transformer manufacturer’s vertical magnetic shunt transformer. According to the results, a saving of 25.83% was achieved in the horizontal magnetic shunt volume compared with the vertical magnetic shunt volume. The maximum magnetic flux density was lower in the horizontal magnetic shunts, and the maximum current density was lower in the transformer tank with horizontal magnetic shunts.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信