Karolina Kasaš-Lažetić, Gorana Mijatović, Dejana Herceg, Miroslav Prša
{"title":"Analiza zagrevanja bakarnih provodnika sa strujom","authors":"Karolina Kasaš-Lažetić, Gorana Mijatović, Dejana Herceg, Miroslav Prša","doi":"10.46793/eee21-1.16kl","DOIUrl":null,"url":null,"abstract":"The method for the temperature measurement on the surface of three copper conductors, with cross-sections of 4 mm2 , 6 mm2 i 10 mm2 , are presented in this paper. After the determination of temperature probe, the series of temperature measurements are performed on chosen wire conductors. The first two series are performed applying DC generator, in two different cases: when, during the measurement the voltage on the conductor’s end was held constant and the current inside the conductor was held constant. After that, the temperature measurements on the conductor’s surface were performed supplying conductors with AC, time harmonic currents, again in two particular cases: constant RMS voltage value on the conductor’s ends and constant RMS value of current inside the conductor. The measuring results were expected for all four cases and for all thee conductors. Due to presence of skin effect, the Joule’s losses were higher in the AC cases, meaning that the temperature increase was faster and that the final reached temperature, for the same values of voltage or currents, was higher. It was also demonstrated that the higher Joule’s losses appeared when the current was kept constant during the measurements, in both DC and AC supplying. The measurements were performed with the instrument which enabled the results recording on USB stick; hence the measurements duration was 30 minutes, recording result every two seconds. The measuring results were presented graphically, together with graphical presentation of the comparison between methods and the results for all investigated conductors.","PeriodicalId":236996,"journal":{"name":"Energija, ekonomija, ekologija","volume":"2 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1900-01-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Energija, ekonomija, ekologija","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.46793/eee21-1.16kl","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

本文介绍了三种截面分别为4mm2、6mm2和10mm2的铜导体表面温度的测量方法。在确定温度探头后,对所选导线进行一系列温度测量。在两种不同的情况下,前两个系列是应用直流发电机进行的:在测量期间,导体一端的电压保持恒定,导体内部的电流保持恒定。之后,导体表面的温度测量是在两种特殊情况下进行的,即给导体提供交流、时间谐波电流:导体两端的均方根电压值恒定,导体内部的电流均方根值恒定。所有四种情况和所有三种导体的测量结果都是预期的。由于集肤效应的存在,焦耳损耗在交流情况下更高,这意味着温度上升更快,并且在相同的电压或电流值下,最终达到的温度更高。结果还表明,在直流和交流供电的测量过程中,当电流保持恒定时,焦耳损耗会增加。测量用仪器进行,仪器可将测量结果记录在u盘上;因此,测量时间为30分钟,每2秒记录一次结果。测量结果用图形表示,同时用图形表示所有被测导体的方法和结果之间的比较。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Analiza zagrevanja bakarnih provodnika sa strujom
The method for the temperature measurement on the surface of three copper conductors, with cross-sections of 4 mm2 , 6 mm2 i 10 mm2 , are presented in this paper. After the determination of temperature probe, the series of temperature measurements are performed on chosen wire conductors. The first two series are performed applying DC generator, in two different cases: when, during the measurement the voltage on the conductor’s end was held constant and the current inside the conductor was held constant. After that, the temperature measurements on the conductor’s surface were performed supplying conductors with AC, time harmonic currents, again in two particular cases: constant RMS voltage value on the conductor’s ends and constant RMS value of current inside the conductor. The measuring results were expected for all four cases and for all thee conductors. Due to presence of skin effect, the Joule’s losses were higher in the AC cases, meaning that the temperature increase was faster and that the final reached temperature, for the same values of voltage or currents, was higher. It was also demonstrated that the higher Joule’s losses appeared when the current was kept constant during the measurements, in both DC and AC supplying. The measurements were performed with the instrument which enabled the results recording on USB stick; hence the measurements duration was 30 minutes, recording result every two seconds. The measuring results were presented graphically, together with graphical presentation of the comparison between methods and the results for all investigated conductors.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信