1000kV半波长交流输电线路的电磁瞬变特性

Xinyu Xiang, Lei Qi, X. Cui
{"title":"1000kV半波长交流输电线路的电磁瞬变特性","authors":"Xinyu Xiang, Lei Qi, X. Cui","doi":"10.1109/CRIS.2010.5617497","DOIUrl":null,"url":null,"abstract":"in China, the energy resources is against the productive forces development, the base of energy in the west is about 3000km away from the load centers in the east, so the transmission systems with long distance and large capacity should be established. In this paper, based on the design example of UHV (1000kV) AC transmission system, the Half Wavelength AC Transmission (HWACT) is introduced, and the study of Some electromagnetic transient characteristic of HWACT lines without the presence of intermediate switching stations by two types of 3 phase conductors arrangements are carried out, such as capacitance effect of unloaded line, single-phase-to-ground fault and switching over voltages; the results shows that 1000kV half wavelength AC Transmission is in well condition : The maximum power frequency voltages rising caused by capacitance effect in unloaded line is 1.04 per unit, by single-phase-to-ground fault is 2.19 per unit, the maximum switching over voltage such as closing unloaded line, 3 phases load shedding and single-phase auto-recloser are 1.6 per unit, 2.0 per unit, 1.7 per unit respectively; and these over voltages are under the concerned regulations of our country owing, except for the amplitude of the secondary arc current, which HSGS can reduce but not ideal.","PeriodicalId":206094,"journal":{"name":"2010 5th International Conference on Critical Infrastructure (CRIS)","volume":"67 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2010-11-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"13","resultStr":"{\"title\":\"Electromagnetic transient characteristic of 1000kV half-wavelength AC transmission lines\",\"authors\":\"Xinyu Xiang, Lei Qi, X. Cui\",\"doi\":\"10.1109/CRIS.2010.5617497\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"in China, the energy resources is against the productive forces development, the base of energy in the west is about 3000km away from the load centers in the east, so the transmission systems with long distance and large capacity should be established. In this paper, based on the design example of UHV (1000kV) AC transmission system, the Half Wavelength AC Transmission (HWACT) is introduced, and the study of Some electromagnetic transient characteristic of HWACT lines without the presence of intermediate switching stations by two types of 3 phase conductors arrangements are carried out, such as capacitance effect of unloaded line, single-phase-to-ground fault and switching over voltages; the results shows that 1000kV half wavelength AC Transmission is in well condition : The maximum power frequency voltages rising caused by capacitance effect in unloaded line is 1.04 per unit, by single-phase-to-ground fault is 2.19 per unit, the maximum switching over voltage such as closing unloaded line, 3 phases load shedding and single-phase auto-recloser are 1.6 per unit, 2.0 per unit, 1.7 per unit respectively; and these over voltages are under the concerned regulations of our country owing, except for the amplitude of the secondary arc current, which HSGS can reduce but not ideal.\",\"PeriodicalId\":206094,\"journal\":{\"name\":\"2010 5th International Conference on Critical Infrastructure (CRIS)\",\"volume\":\"67 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2010-11-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"13\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2010 5th International Conference on Critical Infrastructure (CRIS)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/CRIS.2010.5617497\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2010 5th International Conference on Critical Infrastructure (CRIS)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CRIS.2010.5617497","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 13

摘要

在中国,能源资源与生产力发展相矛盾,西部的能源基地与东部的负荷中心相距约3000公里,因此应建立远距离、大容量的输电系统。本文以特高压(1000kV)交流输电系统的设计实例为基础,介绍了半波长交流输电系统(HWACT),并对无中间开关站时半波长交流输电线路在两种三相导线布置下的一些电磁暂态特性进行了研究,如空载线路的电容效应、单相接地故障和切换电压;结果表明,1000kV半波长交流输电处于良好状态:空载线路电容效应引起的工频电压最大上升为1.04 /台,单相接地故障引起的工频电压最大上升为2.19 /台,空载线路合闸、三相减载、单相自动重合闸引起的最大切换过电压分别为1.6、2.0、1.7 /台;这些过电压都在我国有关规定之内,除了二次电弧电流的幅值,HSGS可以降低,但并不理想。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Electromagnetic transient characteristic of 1000kV half-wavelength AC transmission lines
in China, the energy resources is against the productive forces development, the base of energy in the west is about 3000km away from the load centers in the east, so the transmission systems with long distance and large capacity should be established. In this paper, based on the design example of UHV (1000kV) AC transmission system, the Half Wavelength AC Transmission (HWACT) is introduced, and the study of Some electromagnetic transient characteristic of HWACT lines without the presence of intermediate switching stations by two types of 3 phase conductors arrangements are carried out, such as capacitance effect of unloaded line, single-phase-to-ground fault and switching over voltages; the results shows that 1000kV half wavelength AC Transmission is in well condition : The maximum power frequency voltages rising caused by capacitance effect in unloaded line is 1.04 per unit, by single-phase-to-ground fault is 2.19 per unit, the maximum switching over voltage such as closing unloaded line, 3 phases load shedding and single-phase auto-recloser are 1.6 per unit, 2.0 per unit, 1.7 per unit respectively; and these over voltages are under the concerned regulations of our country owing, except for the amplitude of the secondary arc current, which HSGS can reduce but not ideal.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信