{"title":"配电网单相脱扣评价","authors":"R. Toledo, Tiago da Rocha Honorato, K. M. e Silva, Felipe Vigolvino Lopes","doi":"10.1109/TDLA47668.2020.9326153","DOIUrl":null,"url":null,"abstract":"Reliability and continuity improvement in distribution system protection and operation has led to the reevaluation of traditional practices in the field. Although these systems employ single-phase protection devices such as fuses, most utilities have avoided the use of single-phase tripping (SPT) schemes in their reclosers. In order to evaluate SPT implementation feasibility on reliability indices and regulatory report perspectives, this paper presents a detailed distribution feeder secondary voltage analysis when the SPT with three-phase transformers over a radial distribution feeder is implemented. Aiming on a practical application, a real overhead distribution feeder was modeled in Alternative Transients Program, allowing protection algorithm implementation and transient simulation. In this paper, three different types of independent phase-interrupting equipment are evaluated: recloser, lateral fuse and transformer fuse. The obtained results are divided into two approaches: the transient analysis, evaluating the voltage behavior on time domain, and the steady-state sensitivity analysis, evaluating the load level impact on secondary voltage level after the single-pole opening as a response to single-phase-to-ground faults.","PeriodicalId":448644,"journal":{"name":"2020 IEEE PES Transmission & Distribution Conference and Exhibition - Latin America (T&D LA)","volume":"21 5 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2020-09-28","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"On Evaluating Single-Phase Tripping on Distribution Networks\",\"authors\":\"R. Toledo, Tiago da Rocha Honorato, K. M. e Silva, Felipe Vigolvino Lopes\",\"doi\":\"10.1109/TDLA47668.2020.9326153\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Reliability and continuity improvement in distribution system protection and operation has led to the reevaluation of traditional practices in the field. Although these systems employ single-phase protection devices such as fuses, most utilities have avoided the use of single-phase tripping (SPT) schemes in their reclosers. In order to evaluate SPT implementation feasibility on reliability indices and regulatory report perspectives, this paper presents a detailed distribution feeder secondary voltage analysis when the SPT with three-phase transformers over a radial distribution feeder is implemented. Aiming on a practical application, a real overhead distribution feeder was modeled in Alternative Transients Program, allowing protection algorithm implementation and transient simulation. In this paper, three different types of independent phase-interrupting equipment are evaluated: recloser, lateral fuse and transformer fuse. The obtained results are divided into two approaches: the transient analysis, evaluating the voltage behavior on time domain, and the steady-state sensitivity analysis, evaluating the load level impact on secondary voltage level after the single-pole opening as a response to single-phase-to-ground faults.\",\"PeriodicalId\":448644,\"journal\":{\"name\":\"2020 IEEE PES Transmission & Distribution Conference and Exhibition - Latin America (T&D LA)\",\"volume\":\"21 5 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2020-09-28\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2020 IEEE PES Transmission & Distribution Conference and Exhibition - Latin America (T&D LA)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/TDLA47668.2020.9326153\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2020 IEEE PES Transmission & Distribution Conference and Exhibition - Latin America (T&D LA)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/TDLA47668.2020.9326153","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

配电系统保护和运行的可靠性和连续性的改进导致了对该领域传统做法的重新评估。尽管这些系统采用了熔断器等单相保护装置,但大多数公用事业公司都避免在其重合器中使用单相跳闸(SPT)方案。为了从可靠性指标和监管报告的角度评估SPT实施的可行性,本文详细分析了带三相变压器的SPT在径向配电馈线上实施时的配电馈线二次电压。针对实际应用,在备用暂态程序中对实际架空配电馈线进行建模,实现了保护算法的实现和暂态仿真。本文对三种不同类型的独立断相装置:重合闸、侧熔断器和变压器熔断器进行了评价。得到的结果分为两种方法:暂态分析,评估电压在时域上的行为;稳态灵敏度分析,评估单相接地故障对单极开断后负载水平对二次电压水平的影响。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
On Evaluating Single-Phase Tripping on Distribution Networks
Reliability and continuity improvement in distribution system protection and operation has led to the reevaluation of traditional practices in the field. Although these systems employ single-phase protection devices such as fuses, most utilities have avoided the use of single-phase tripping (SPT) schemes in their reclosers. In order to evaluate SPT implementation feasibility on reliability indices and regulatory report perspectives, this paper presents a detailed distribution feeder secondary voltage analysis when the SPT with three-phase transformers over a radial distribution feeder is implemented. Aiming on a practical application, a real overhead distribution feeder was modeled in Alternative Transients Program, allowing protection algorithm implementation and transient simulation. In this paper, three different types of independent phase-interrupting equipment are evaluated: recloser, lateral fuse and transformer fuse. The obtained results are divided into two approaches: the transient analysis, evaluating the voltage behavior on time domain, and the steady-state sensitivity analysis, evaluating the load level impact on secondary voltage level after the single-pole opening as a response to single-phase-to-ground faults.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信