基于ATP-EMTP的微型水轮机谐波影响研究

P. Kirawanich, R. O’Connell, G. Brownfield
{"title":"基于ATP-EMTP的微型水轮机谐波影响研究","authors":"P. Kirawanich, R. O’Connell, G. Brownfield","doi":"10.1109/ICHQP.2004.1409339","DOIUrl":null,"url":null,"abstract":"ATP-EMTP simulations of a 3-phase commercial power distribution system containing 250 kW, 480 V microturbines running at less than full load and producing harmonic currents that violate recommended current distortion limits are described. The purpose of the simulations was to investigate the extent to which the nonlinear currents generated by the microturbines in this situation might cause line voltage distortion. The results showed that even at the most vulnerable lateral tap points in the system under worst-case conditions the voltage THD did not exceed the IEEE standard 519 limitation for up to 50% saturation of commercial service entrances with microturbines.","PeriodicalId":406398,"journal":{"name":"2004 11th International Conference on Harmonics and Quality of Power (IEEE Cat. No.04EX951)","volume":"15 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2004-09-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Microturbine harmonic impact study using ATP-EMTP\",\"authors\":\"P. Kirawanich, R. O’Connell, G. Brownfield\",\"doi\":\"10.1109/ICHQP.2004.1409339\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"ATP-EMTP simulations of a 3-phase commercial power distribution system containing 250 kW, 480 V microturbines running at less than full load and producing harmonic currents that violate recommended current distortion limits are described. The purpose of the simulations was to investigate the extent to which the nonlinear currents generated by the microturbines in this situation might cause line voltage distortion. The results showed that even at the most vulnerable lateral tap points in the system under worst-case conditions the voltage THD did not exceed the IEEE standard 519 limitation for up to 50% saturation of commercial service entrances with microturbines.\",\"PeriodicalId\":406398,\"journal\":{\"name\":\"2004 11th International Conference on Harmonics and Quality of Power (IEEE Cat. No.04EX951)\",\"volume\":\"15 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2004-09-12\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2004 11th International Conference on Harmonics and Quality of Power (IEEE Cat. No.04EX951)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ICHQP.2004.1409339\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2004 11th International Conference on Harmonics and Quality of Power (IEEE Cat. No.04EX951)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICHQP.2004.1409339","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

本文描述了一个包含250kw, 480 V微型涡轮机的三相商业配电系统的ATP-EMTP模拟,该系统在低于满负荷的情况下运行,并产生违反推荐电流失真限制的谐波电流。模拟的目的是研究在这种情况下微型涡轮机产生的非线性电流对线路电压畸变的影响程度。结果表明,在最坏情况下,即使在系统中最脆弱的侧分接点,电压THD也没有超过IEEE标准519的限制,达到微型涡轮机商业服务入口50%的饱和。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Microturbine harmonic impact study using ATP-EMTP
ATP-EMTP simulations of a 3-phase commercial power distribution system containing 250 kW, 480 V microturbines running at less than full load and producing harmonic currents that violate recommended current distortion limits are described. The purpose of the simulations was to investigate the extent to which the nonlinear currents generated by the microturbines in this situation might cause line voltage distortion. The results showed that even at the most vulnerable lateral tap points in the system under worst-case conditions the voltage THD did not exceed the IEEE standard 519 limitation for up to 50% saturation of commercial service entrances with microturbines.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信