M. Grebchenko, M. Sopel, Y. Pylypenko, D. Voitov
{"title":"确定单侧电力线路到接地故障距离的准双边方法","authors":"M. Grebchenko, M. Sopel, Y. Pylypenko, D. Voitov","doi":"10.1109/ESS57819.2022.9969330","DOIUrl":null,"url":null,"abstract":"In this paper the method to determine fault location in case of ground fault at power line with isolated neutral has been proposed. Estimation of fault's distance is carried out based on line's operating mode parameters (namely phase currents and voltages to ground) at the start of the line. Fault's distance calculation is implemented using vectors of line's operating mode parameters from both sides of the line. Verification of the method has been conducted experimentally as well as via math modelling. Method's errors were caused mostly by small currents' value alteration in case of fault, existence of resistance at fault's location and power line's load resistance change. Research about impact on method's accuracy due to distance to the fault as well as resistance value at the fault location has been carried out.","PeriodicalId":432063,"journal":{"name":"2022 IEEE 8th International Conference on Energy Smart Systems (ESS)","volume":"8 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2022-10-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Quasi-bilateral method for determining the distance to the ground fault of unilateral power lines\",\"authors\":\"M. Grebchenko, M. Sopel, Y. Pylypenko, D. Voitov\",\"doi\":\"10.1109/ESS57819.2022.9969330\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"In this paper the method to determine fault location in case of ground fault at power line with isolated neutral has been proposed. Estimation of fault's distance is carried out based on line's operating mode parameters (namely phase currents and voltages to ground) at the start of the line. Fault's distance calculation is implemented using vectors of line's operating mode parameters from both sides of the line. Verification of the method has been conducted experimentally as well as via math modelling. Method's errors were caused mostly by small currents' value alteration in case of fault, existence of resistance at fault's location and power line's load resistance change. Research about impact on method's accuracy due to distance to the fault as well as resistance value at the fault location has been carried out.\",\"PeriodicalId\":432063,\"journal\":{\"name\":\"2022 IEEE 8th International Conference on Energy Smart Systems (ESS)\",\"volume\":\"8 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2022-10-12\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2022 IEEE 8th International Conference on Energy Smart Systems (ESS)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ESS57819.2022.9969330\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2022 IEEE 8th International Conference on Energy Smart Systems (ESS)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ESS57819.2022.9969330","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

本文提出了在中性点隔离的电力线路发生接地故障时确定故障位置的方法。故障距离的估计是根据线路起始处的运行模式参数(即相电流和对地电压)进行的。故障距离计算是利用线路两侧运行模式参数的矢量实现的。通过实验和数学建模对该方法进行了验证。该方法的误差主要是由于故障时小电流值的变化、故障位置电阻的存在以及电源线负载电阻的变化造成的。研究了故障点与故障点的距离以及故障点的电阻值对方法精度的影响。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Quasi-bilateral method for determining the distance to the ground fault of unilateral power lines
In this paper the method to determine fault location in case of ground fault at power line with isolated neutral has been proposed. Estimation of fault's distance is carried out based on line's operating mode parameters (namely phase currents and voltages to ground) at the start of the line. Fault's distance calculation is implemented using vectors of line's operating mode parameters from both sides of the line. Verification of the method has been conducted experimentally as well as via math modelling. Method's errors were caused mostly by small currents' value alteration in case of fault, existence of resistance at fault's location and power line's load resistance change. Research about impact on method's accuracy due to distance to the fault as well as resistance value at the fault location has been carried out.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信