{"title":"地面条件对塔内150KV kramadan - mariana脚踝的影响","authors":"Nita Nurdiana, Rieski Radeli","doi":"10.32502/jse.v6i2.3774","DOIUrl":null,"url":null,"abstract":"The grounding system is intended to ensure that both electrical equipment and the people around it are in a safe condition from overcurrent faults by transferring the fault current to earth. Electrode implantation is one of the factors to get a small grounding resistance value. This study aims to determine the effect of soil conditions on the value of grounding resistance at the foot of the Menara. By using the three-point method on three types of soil conditions at 6 feet Menara, the lowest grounding value is 5.12 ohms in the swamp area at Menara 10 location. The highest grounding resistance in the garden area is 8.32 ohm at Menara 66 location. All values the grounding resistance is in good condition and does not exceed the 150 Kilo Volt high voltage overhead line grounding standard, which is 10 ohms. From the results of the analysis, it is concluded that the soil conditions where the electrodes are implanted affect the grounding value ABSTRAKSistem pentanahan dimaksudkan untuk memastikan bahwa baik peralatan listrik maupun orang-orang disekitarnya dalam kondisi yang aman dari gangguan arus lebih dengan cara mentransfer arus gangguan ke bumi. Penanaman elektroda merupakan salah satu faktor untuk mendapatkan nilai hambatan pentanahan yang kecil. Penelitian ini bertujuan untuk mengetahui pengaruh kondisi tanah terhadap nilai tahanan pentanahan pada kaki Menara SUTT. Dengan menggunakan metode tiga titik pada tiga jenis kondisi tanah pada 6 kaki Menara, didapatkan nilai pentanahan terendah sebesar 5,12 ohm di daerah rawa pada lokasi Menara 10. Hambatan pembumpentanahan tertinggi di daerah kebun yaitu 8,32 ohm pada lokasi Menara 66. Semua nilai tahanan pentanahan dalam keadaan baik dan tidak melebihi standar pentanahan saluran udara tegangan tinggi 150 Kilo Volt yaitu sebesar 10 ohm. Dari hasil analisa diperoleh kesimpulan bahwa kondisi tanah dimana elektroda ditanamkan mempengaruhi nilai pentanahan.","PeriodicalId":307311,"journal":{"name":"JURNAL SURYA ENERGY","volume":"75 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2022-08-05","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"PENGARUH KONDISI TANAH TERHADAP TAHANAN PENTANAHAN KAKI MENARA 150KV KRAMASAN-MARIANA\",\"authors\":\"Nita Nurdiana, Rieski Radeli\",\"doi\":\"10.32502/jse.v6i2.3774\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The grounding system is intended to ensure that both electrical equipment and the people around it are in a safe condition from overcurrent faults by transferring the fault current to earth. Electrode implantation is one of the factors to get a small grounding resistance value. This study aims to determine the effect of soil conditions on the value of grounding resistance at the foot of the Menara. By using the three-point method on three types of soil conditions at 6 feet Menara, the lowest grounding value is 5.12 ohms in the swamp area at Menara 10 location. The highest grounding resistance in the garden area is 8.32 ohm at Menara 66 location. All values the grounding resistance is in good condition and does not exceed the 150 Kilo Volt high voltage overhead line grounding standard, which is 10 ohms. From the results of the analysis, it is concluded that the soil conditions where the electrodes are implanted affect the grounding value ABSTRAKSistem pentanahan dimaksudkan untuk memastikan bahwa baik peralatan listrik maupun orang-orang disekitarnya dalam kondisi yang aman dari gangguan arus lebih dengan cara mentransfer arus gangguan ke bumi. Penanaman elektroda merupakan salah satu faktor untuk mendapatkan nilai hambatan pentanahan yang kecil. Penelitian ini bertujuan untuk mengetahui pengaruh kondisi tanah terhadap nilai tahanan pentanahan pada kaki Menara SUTT. Dengan menggunakan metode tiga titik pada tiga jenis kondisi tanah pada 6 kaki Menara, didapatkan nilai pentanahan terendah sebesar 5,12 ohm di daerah rawa pada lokasi Menara 10. Hambatan pembumpentanahan tertinggi di daerah kebun yaitu 8,32 ohm pada lokasi Menara 66. Semua nilai tahanan pentanahan dalam keadaan baik dan tidak melebihi standar pentanahan saluran udara tegangan tinggi 150 Kilo Volt yaitu sebesar 10 ohm. Dari hasil analisa diperoleh kesimpulan bahwa kondisi tanah dimana elektroda ditanamkan mempengaruhi nilai pentanahan.\",\"PeriodicalId\":307311,\"journal\":{\"name\":\"JURNAL SURYA ENERGY\",\"volume\":\"75 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2022-08-05\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"JURNAL SURYA ENERGY\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.32502/jse.v6i2.3774\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"JURNAL SURYA ENERGY","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.32502/jse.v6i2.3774","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0
摘要
接地系统的目的是通过将故障电流输送到地球,以确保电气设备及其周围的人员处于安全状态,免受过流故障的影响。电极植入是获得小接地电阻值的因素之一。本研究旨在确定土壤条件对Menara山脚接地电阻值的影响。通过在6英尺Menara三种土壤条件下使用三点法,Menara 10位置沼泽地区的最低接地值为5.12欧姆。Menara 66位置花园区域的最高接地电阻为8.32欧姆。接地电阻值应不超过150千伏高压架空线路接地标准(10 ω)。从分析结果可知,电极埋设地的土壤条件对接地值有影响。我是说,我是说,我是说,我是说,我是说,我是说,我是说,我是说,我是说,我是说。Penelitian ini bertujuan untuk mengetahui pengaruh kondisi tanah terhadap nilai tahanan pentanhanhan pakaki Menara SUTT。登干menggunakan方法tiga titik pada tiga jenis kondisi tanah pada 6 kaki Menara, didapatkan nilai pentanahan terendah sebesar 5,12 ohm ddaerah rawa pada lokasi Menara 10。Hambatan pembumpentanahan tertinggi di daerah kebun yaitu 8,32 ohm pada lokasi Menara 66。Semua nilai tahanan pentanahan dalam keadaan baik dan dalak melebihi标准pentanahan saluran udara tegangan tingi 150千伏yyitu sebesar 10欧姆。Dari hasil analisa diperoleh kespulpan bahwa kondisi tanah dimana elektroda ditanamkan mempengaruhi nilai pentanhan。
PENGARUH KONDISI TANAH TERHADAP TAHANAN PENTANAHAN KAKI MENARA 150KV KRAMASAN-MARIANA
The grounding system is intended to ensure that both electrical equipment and the people around it are in a safe condition from overcurrent faults by transferring the fault current to earth. Electrode implantation is one of the factors to get a small grounding resistance value. This study aims to determine the effect of soil conditions on the value of grounding resistance at the foot of the Menara. By using the three-point method on three types of soil conditions at 6 feet Menara, the lowest grounding value is 5.12 ohms in the swamp area at Menara 10 location. The highest grounding resistance in the garden area is 8.32 ohm at Menara 66 location. All values the grounding resistance is in good condition and does not exceed the 150 Kilo Volt high voltage overhead line grounding standard, which is 10 ohms. From the results of the analysis, it is concluded that the soil conditions where the electrodes are implanted affect the grounding value ABSTRAKSistem pentanahan dimaksudkan untuk memastikan bahwa baik peralatan listrik maupun orang-orang disekitarnya dalam kondisi yang aman dari gangguan arus lebih dengan cara mentransfer arus gangguan ke bumi. Penanaman elektroda merupakan salah satu faktor untuk mendapatkan nilai hambatan pentanahan yang kecil. Penelitian ini bertujuan untuk mengetahui pengaruh kondisi tanah terhadap nilai tahanan pentanahan pada kaki Menara SUTT. Dengan menggunakan metode tiga titik pada tiga jenis kondisi tanah pada 6 kaki Menara, didapatkan nilai pentanahan terendah sebesar 5,12 ohm di daerah rawa pada lokasi Menara 10. Hambatan pembumpentanahan tertinggi di daerah kebun yaitu 8,32 ohm pada lokasi Menara 66. Semua nilai tahanan pentanahan dalam keadaan baik dan tidak melebihi standar pentanahan saluran udara tegangan tinggi 150 Kilo Volt yaitu sebesar 10 ohm. Dari hasil analisa diperoleh kesimpulan bahwa kondisi tanah dimana elektroda ditanamkan mempengaruhi nilai pentanahan.