{"title":"同步发电机现有不同失磁保护方案的比较研究","authors":"H. Bentarzi, A. Mati, J. Maun","doi":"10.51485/ajss.v6i4.146","DOIUrl":null,"url":null,"abstract":"Synchronous generator is the most important element of a power system and its fast and reliable protection is crucial. One of the most abnormal conditions in a generator is loss of excitation (LOE) which is harmful to both the generator and the power system. This condition should be detected and the generator isolated from the system to avoid generator damage as well as power system instability. \nThis work presents an experimental study and comparison of the two conventional LOE protection schemes, negative-offset and positive-offset mho element under different conditions. The results show that the two schemes can detect LOE fault under total or partial LOE conditions, however in terms of speed (fault detection time) the positive offset scheme is faster than the negative offset scheme under all loading conditions. Besides, the two LOE protection schemes are reliable and do not operate under power swing disturbances caused by any type of external faults.","PeriodicalId":153848,"journal":{"name":"Algerian Journal of Signals and Systems","volume":"166 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2021-12-31","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Comparison study among the different existing loss of excitation protection schemes in synchronous generator\",\"authors\":\"H. Bentarzi, A. Mati, J. Maun\",\"doi\":\"10.51485/ajss.v6i4.146\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Synchronous generator is the most important element of a power system and its fast and reliable protection is crucial. One of the most abnormal conditions in a generator is loss of excitation (LOE) which is harmful to both the generator and the power system. This condition should be detected and the generator isolated from the system to avoid generator damage as well as power system instability. \\nThis work presents an experimental study and comparison of the two conventional LOE protection schemes, negative-offset and positive-offset mho element under different conditions. The results show that the two schemes can detect LOE fault under total or partial LOE conditions, however in terms of speed (fault detection time) the positive offset scheme is faster than the negative offset scheme under all loading conditions. Besides, the two LOE protection schemes are reliable and do not operate under power swing disturbances caused by any type of external faults.\",\"PeriodicalId\":153848,\"journal\":{\"name\":\"Algerian Journal of Signals and Systems\",\"volume\":\"166 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2021-12-31\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Algerian Journal of Signals and Systems\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.51485/ajss.v6i4.146\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Algerian Journal of Signals and Systems","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.51485/ajss.v6i4.146","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

同步发电机是电力系统的重要组成部分,其快速可靠的保护至关重要。发电机中最常见的异常状态之一是失磁,它对发电机和电力系统都是有害的。应及时检测这种情况,并将发电机与系统隔离,以避免发电机损坏和电力系统不稳定。本文对两种传统的LOE保护方案——负偏置和正偏置mho元件在不同条件下进行了实验研究和比较。结果表明,两种方案在完全或部分LOE条件下都能检测到LOE故障,但在速度(故障检测时间)方面,正偏移方案在所有负载条件下都比负偏移方案快。此外,两种LOE保护方案都是可靠的,并且在任何类型的外部故障引起的功率摆动干扰下都不会运行。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Comparison study among the different existing loss of excitation protection schemes in synchronous generator
Synchronous generator is the most important element of a power system and its fast and reliable protection is crucial. One of the most abnormal conditions in a generator is loss of excitation (LOE) which is harmful to both the generator and the power system. This condition should be detected and the generator isolated from the system to avoid generator damage as well as power system instability. This work presents an experimental study and comparison of the two conventional LOE protection schemes, negative-offset and positive-offset mho element under different conditions. The results show that the two schemes can detect LOE fault under total or partial LOE conditions, however in terms of speed (fault detection time) the positive offset scheme is faster than the negative offset scheme under all loading conditions. Besides, the two LOE protection schemes are reliable and do not operate under power swing disturbances caused by any type of external faults.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信