失配并联变压器母线稳压及OLTC性能分析

Ls Madzonga, J. Munda, A. Jimoh
{"title":"失配并联变压器母线稳压及OLTC性能分析","authors":"Ls Madzonga, J. Munda, A. Jimoh","doi":"10.1109/AFRCON.2009.5308082","DOIUrl":null,"url":null,"abstract":"This paper analyzes the regulation of bus voltage when master-follower or master-slave tap change control method is used when two mismatched-transformers are operated in parallel. Bus voltage regulation at a distribution substation relies on the use of the AVR relay that controls the OLTC. The circulating current method yields expected performance regarding bus voltage regulation when mismatched transformers are operated in parallel. When the master-follower/slave method is used, the standard voltage set-point of 103% results in low voltages being experienced by the customer at the end of the feeder. The simulations done on the network suggests that the voltage set point of each AVR relay be determined with the consideration of the upstream and downstream AVR relay settings.","PeriodicalId":122830,"journal":{"name":"AFRICON 2009","volume":"27 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2009-11-03","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"7","resultStr":"{\"title\":\"Analysis of bus voltage regulation and OLTC performance on mismatched parallel-connected transformers\",\"authors\":\"Ls Madzonga, J. Munda, A. Jimoh\",\"doi\":\"10.1109/AFRCON.2009.5308082\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"This paper analyzes the regulation of bus voltage when master-follower or master-slave tap change control method is used when two mismatched-transformers are operated in parallel. Bus voltage regulation at a distribution substation relies on the use of the AVR relay that controls the OLTC. The circulating current method yields expected performance regarding bus voltage regulation when mismatched transformers are operated in parallel. When the master-follower/slave method is used, the standard voltage set-point of 103% results in low voltages being experienced by the customer at the end of the feeder. The simulations done on the network suggests that the voltage set point of each AVR relay be determined with the consideration of the upstream and downstream AVR relay settings.\",\"PeriodicalId\":122830,\"journal\":{\"name\":\"AFRICON 2009\",\"volume\":\"27 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2009-11-03\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"7\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"AFRICON 2009\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/AFRCON.2009.5308082\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"AFRICON 2009","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/AFRCON.2009.5308082","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 7

摘要

分析了双失配变压器并联运行时采用主从动器或主从抽头变换控制方式时母线电压的变化规律。配电变电站的母线电压调节依赖于控制OLTC的AVR继电器的使用。当失配变压器并联运行时,循环电流法在母线电压调节方面取得了预期的效果。当使用主-从动/从动方法时,103%的标准电压设定点导致馈线末端的客户体验到低电压。网络仿真表明,各AVR继电器的电压设定点应综合考虑AVR继电器上下游的整定值。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Analysis of bus voltage regulation and OLTC performance on mismatched parallel-connected transformers
This paper analyzes the regulation of bus voltage when master-follower or master-slave tap change control method is used when two mismatched-transformers are operated in parallel. Bus voltage regulation at a distribution substation relies on the use of the AVR relay that controls the OLTC. The circulating current method yields expected performance regarding bus voltage regulation when mismatched transformers are operated in parallel. When the master-follower/slave method is used, the standard voltage set-point of 103% results in low voltages being experienced by the customer at the end of the feeder. The simulations done on the network suggests that the voltage set point of each AVR relay be determined with the consideration of the upstream and downstream AVR relay settings.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信