{"title":"STUDI SISTEM PENTANAHAN SALURAN UDARA TEGANGAN TINGGI(SUTT) PENGHANTAR 150 KV LUBUK LINGGAU - PEKALONGAN PT. PLN (PERSERO) UNIT PEMBANGKIT DAN TRAMSISI (UPT) BENGKULU","authors":"Dian Eka Putra, Fitra Angga","doi":"10.32502/JSE.V3I1.1253","DOIUrl":null,"url":null,"abstract":"High-voltage 150 kV air ducts that use open wire are very likely to cause interference, both external and internal interference. And one of the most common disorders is due to lightning strikes. To optimize the distribution of electrical energy in the high voltage air duct, an earth system is installed at the foot of the tower. This study was conducted to calculate the value of foot tower resistance installed on 150 kV high voltage air line  Lubuk Linggau - Pekalongan. Here it will also be discussed to minimize the resistance in earth that exceeds the set standard. Based on measurements using earth tester obtained several towers have a resistance value exceeding the standard on Tower T.20 of 14.5 ohms, Tower T.53 of 12.43 Ohm and Tower T.151 10.33 ohms. After adding the electrode rod obtained by T.20 to 8.056 ohm, T.53 became 8.055 ohms, T.151 8.51 ohms. Of the total 150 kV high voltage  air ducts in Lubuk Linggau - Pekalongan, the grounding system is still good and capable of flowing the fault current to the ground","PeriodicalId":307311,"journal":{"name":"JURNAL SURYA ENERGY","volume":"77 ","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2018-09-15","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"JURNAL SURYA ENERGY","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.32502/JSE.V3I1.1253","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

使用开线的高压150kv风管非常容易产生干扰,既有外部干扰,也有内部干扰。最常见的疾病之一是由雷击引起的。为了优化高压风道中的电能分配,在塔的底部安装了接地系统。本文对鲁巴克灵高至北卡隆岸150kv高压线路上安装的脚塔电阻值进行了计算。这里还将讨论如何尽量减少超过设定标准的接地电阻。根据接地测试仪的测量结果,有几个塔的电阻值超标,其中塔T.20为14.5欧姆,塔T.53为12.43欧姆,塔T.151为10.33欧姆。将T.20得到的电极棒加到8.056欧姆后,T.53变成8.055欧姆,T.151变成8.51欧姆。鲁巴克岭高-北卡隆岸共150千伏高压风管中,接地系统仍然良好,能够将故障电流输送到地面
本文章由计算机程序翻译,如有差异,请以英文原文为准。
STUDI SISTEM PENTANAHAN SALURAN UDARA TEGANGAN TINGGI(SUTT) PENGHANTAR 150 KV LUBUK LINGGAU - PEKALONGAN PT. PLN (PERSERO) UNIT PEMBANGKIT DAN TRAMSISI (UPT) BENGKULU
High-voltage 150 kV air ducts that use open wire are very likely to cause interference, both external and internal interference. And one of the most common disorders is due to lightning strikes. To optimize the distribution of electrical energy in the high voltage air duct, an earth system is installed at the foot of the tower. This study was conducted to calculate the value of foot tower resistance installed on 150 kV high voltage air line  Lubuk Linggau - Pekalongan. Here it will also be discussed to minimize the resistance in earth that exceeds the set standard. Based on measurements using earth tester obtained several towers have a resistance value exceeding the standard on Tower T.20 of 14.5 ohms, Tower T.53 of 12.43 Ohm and Tower T.151 10.33 ohms. After adding the electrode rod obtained by T.20 to 8.056 ohm, T.53 became 8.055 ohms, T.151 8.51 ohms. Of the total 150 kV high voltage  air ducts in Lubuk Linggau - Pekalongan, the grounding system is still good and capable of flowing the fault current to the ground
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信