在“危险区域”操作:接触器脱落vs保险丝清除时间

J. Webb, Andrea Delpozzo, Ilaria Dognini, C. Reuber
{"title":"在“危险区域”操作:接触器脱落vs保险丝清除时间","authors":"J. Webb, Andrea Delpozzo, Ilaria Dognini, C. Reuber","doi":"10.1109/PCIC42668.2022.10181277","DOIUrl":null,"url":null,"abstract":"The most common and economical arrangement for medium voltage motor controllers is to self-supply from the primary motor circuit. In this arrangement a short-circuit collapses the line voltage, causing the contactor to ’dropout’. For low-level faults which nevertheless exceed the interrupting rating of the contactor it is common for the dropout time to be faster than the clearing time for the fuse. Although this fault current is extremely unlikely to occur, no provisions exist in current standards to permit application of contactors in this manner. To prevent the contactor from attempting to clear a fault current above its rating, less than optimal fuses must be selected or complex and expensive supplemental power supply circuits are added to ensure the holding coil remains energized until the fuse clears the fault. The trade-offs of short-circuit clearing time versus rated current to achieve a take-over point below the interrupting rating of a contactor are illustrated. In response to a customer request, an alternative test procedure to demonstrate capability where contactor dropout precedes fuse clearing was performed; actual results of such tests are included.","PeriodicalId":301848,"journal":{"name":"2022 IEEE IAS Petroleum and Chemical Industry Technical Conference (PCIC)","volume":"204 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2022-09-26","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"Operating in the ‘Danger Zone’: Contactor Dropout vs. Fuse Clearing Time\",\"authors\":\"J. Webb, Andrea Delpozzo, Ilaria Dognini, C. Reuber\",\"doi\":\"10.1109/PCIC42668.2022.10181277\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The most common and economical arrangement for medium voltage motor controllers is to self-supply from the primary motor circuit. In this arrangement a short-circuit collapses the line voltage, causing the contactor to ’dropout’. For low-level faults which nevertheless exceed the interrupting rating of the contactor it is common for the dropout time to be faster than the clearing time for the fuse. Although this fault current is extremely unlikely to occur, no provisions exist in current standards to permit application of contactors in this manner. To prevent the contactor from attempting to clear a fault current above its rating, less than optimal fuses must be selected or complex and expensive supplemental power supply circuits are added to ensure the holding coil remains energized until the fuse clears the fault. The trade-offs of short-circuit clearing time versus rated current to achieve a take-over point below the interrupting rating of a contactor are illustrated. In response to a customer request, an alternative test procedure to demonstrate capability where contactor dropout precedes fuse clearing was performed; actual results of such tests are included.\",\"PeriodicalId\":301848,\"journal\":{\"name\":\"2022 IEEE IAS Petroleum and Chemical Industry Technical Conference (PCIC)\",\"volume\":\"204 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2022-09-26\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2022 IEEE IAS Petroleum and Chemical Industry Technical Conference (PCIC)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/PCIC42668.2022.10181277\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2022 IEEE IAS Petroleum and Chemical Industry Technical Conference (PCIC)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/PCIC42668.2022.10181277","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

摘要

中压电机控制器最常见和最经济的安排是从一次电机电路自供电。在这种安排中,短路使线路电压崩溃,导致接触器“脱落”。对于低电平故障,尽管超过了接触器的中断额定值,但通常情况下,断开时间比熔断器的清除时间快。虽然这种故障电流极不可能发生,但现行标准中没有规定允许以这种方式应用接触器。为了防止接触器试图清除高于其额定值的故障电流,必须选择不理想的熔断器或添加复杂而昂贵的补充电源电路,以确保保持线圈保持通电,直到熔断器清除故障。为了达到低于接触器的中断额定值的接管点,短路清除时间与额定电流之间的权衡是图示的。应客户要求,在熔断器熔断之前进行了接触器脱落测试,以验证其性能。这些测试的实际结果也包括在内。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Operating in the ‘Danger Zone’: Contactor Dropout vs. Fuse Clearing Time
The most common and economical arrangement for medium voltage motor controllers is to self-supply from the primary motor circuit. In this arrangement a short-circuit collapses the line voltage, causing the contactor to ’dropout’. For low-level faults which nevertheless exceed the interrupting rating of the contactor it is common for the dropout time to be faster than the clearing time for the fuse. Although this fault current is extremely unlikely to occur, no provisions exist in current standards to permit application of contactors in this manner. To prevent the contactor from attempting to clear a fault current above its rating, less than optimal fuses must be selected or complex and expensive supplemental power supply circuits are added to ensure the holding coil remains energized until the fuse clears the fault. The trade-offs of short-circuit clearing time versus rated current to achieve a take-over point below the interrupting rating of a contactor are illustrated. In response to a customer request, an alternative test procedure to demonstrate capability where contactor dropout precedes fuse clearing was performed; actual results of such tests are included.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信