{"title":"地磁扰动下负序电流同步发电机的不对称过载","authors":"V. Vakhnina, A. Kuvshinov, A. Chernenko, D. Kretov","doi":"10.1109/ICOECS50468.2020.9278505","DOIUrl":null,"url":null,"abstract":"It is demonstrated that at the occurrence of geomagnetic disturbances the value of quasi-direct current acting on a generator step-up transformer depends on the type and number of blocks \"synchronous generator – generator step-up transformer\" as parts of a power plant, phase wire parameters, geographic direction of overhead power lines extending away from high voltage collecting buses. It is established that, other things being equal, the generator step-up transformers of simple and enlarged power plant blocks are subject to a more intensive action of quasi-direct currents. The saturation of the magnet system of a generator step-up transformer under the action of quasi-direct currents causes simultaneous occurrence of symmetric overload at a synchronous generator with a stator reactive current induced by the increase in the magnetization capacity and non-symmetric rotor overload induced by the higher harmonics of positive and negative sequence magnetization current. The authors define a harmonic composition of the current of the synchronous generator stator at a unilateral saturation of the generator step-up transformer magnetic system. It is shown that the second current harmonic of the stator is the most significant one, as its current can reach 50% of the rated stator current. The authors obtain the ranges of a permitted duration of the asymmetric mode for all types of considered synchronous generators beyond which the rotor is damaged because of inadmissible thermal action.","PeriodicalId":363631,"journal":{"name":"2020 International Conference on Electrotechnical Complexes and Systems (ICOECS)","volume":"45 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2020-10-27","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Asymmetric Overload of Synchronous Generators with Negative Sequence Currents at Geomagnetic Disturbances\",\"authors\":\"V. Vakhnina, A. Kuvshinov, A. Chernenko, D. Kretov\",\"doi\":\"10.1109/ICOECS50468.2020.9278505\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"It is demonstrated that at the occurrence of geomagnetic disturbances the value of quasi-direct current acting on a generator step-up transformer depends on the type and number of blocks \\\"synchronous generator – generator step-up transformer\\\" as parts of a power plant, phase wire parameters, geographic direction of overhead power lines extending away from high voltage collecting buses. It is established that, other things being equal, the generator step-up transformers of simple and enlarged power plant blocks are subject to a more intensive action of quasi-direct currents. The saturation of the magnet system of a generator step-up transformer under the action of quasi-direct currents causes simultaneous occurrence of symmetric overload at a synchronous generator with a stator reactive current induced by the increase in the magnetization capacity and non-symmetric rotor overload induced by the higher harmonics of positive and negative sequence magnetization current. The authors define a harmonic composition of the current of the synchronous generator stator at a unilateral saturation of the generator step-up transformer magnetic system. It is shown that the second current harmonic of the stator is the most significant one, as its current can reach 50% of the rated stator current. The authors obtain the ranges of a permitted duration of the asymmetric mode for all types of considered synchronous generators beyond which the rotor is damaged because of inadmissible thermal action.\",\"PeriodicalId\":363631,\"journal\":{\"name\":\"2020 International Conference on Electrotechnical Complexes and Systems (ICOECS)\",\"volume\":\"45 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2020-10-27\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2020 International Conference on Electrotechnical Complexes and Systems (ICOECS)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ICOECS50468.2020.9278505\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2020 International Conference on Electrotechnical Complexes and Systems (ICOECS)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICOECS50468.2020.9278505","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

结果表明,在发生地磁扰动时,作用在发电机升压变压器上的准直流电数值取决于作为发电厂组成部分的“同步发电机-发电机升压变压器”的模块类型和数量、相线参数、从高压集流母线伸出的架空电力线的地理方向。结果表明,在其他条件相同的情况下,小型和大型电站机组的发电机升压变压器受准直流电的作用更大。发电机升压变压器磁铁系统在准直流电流下饱和,导致同步发电机定子无功电流因磁化能力增加而对称过载,正负序磁化电流高次谐波引起转子非对称过载同时发生。定义了发电机升压变压器磁系统单边饱和时同步发电机定子电流的谐波组成。结果表明,定子电流二次谐波最为显著,其电流可达定子额定电流的50%。作者得到了所考虑的所有类型的同步发电机的不对称模态的允许持续时间范围,超过该范围转子将因不可接受的热作用而损坏。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Asymmetric Overload of Synchronous Generators with Negative Sequence Currents at Geomagnetic Disturbances
It is demonstrated that at the occurrence of geomagnetic disturbances the value of quasi-direct current acting on a generator step-up transformer depends on the type and number of blocks "synchronous generator – generator step-up transformer" as parts of a power plant, phase wire parameters, geographic direction of overhead power lines extending away from high voltage collecting buses. It is established that, other things being equal, the generator step-up transformers of simple and enlarged power plant blocks are subject to a more intensive action of quasi-direct currents. The saturation of the magnet system of a generator step-up transformer under the action of quasi-direct currents causes simultaneous occurrence of symmetric overload at a synchronous generator with a stator reactive current induced by the increase in the magnetization capacity and non-symmetric rotor overload induced by the higher harmonics of positive and negative sequence magnetization current. The authors define a harmonic composition of the current of the synchronous generator stator at a unilateral saturation of the generator step-up transformer magnetic system. It is shown that the second current harmonic of the stator is the most significant one, as its current can reach 50% of the rated stator current. The authors obtain the ranges of a permitted duration of the asymmetric mode for all types of considered synchronous generators beyond which the rotor is damaged because of inadmissible thermal action.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信