{"title":"电力设备在畸变激励电压下的介电损耗系数测量","authors":"Pratic A Muntakim, Jun-yan Zhang, Shubin Zhang, B. Phung","doi":"10.1109/ICSGTEIS53426.2021.9650374","DOIUrl":null,"url":null,"abstract":"The dielectric dissipation factor (DDF) is a useful parameter for the diagnosis of high voltage equipment insulation condition. Traditionally, the AC power grid voltage was considered pure sinusoidal. Due to the increasing presence of non-linear loads in the power system, the grid voltage nowadays gets distorted with high frequency harmonics. This paper investigates the impact of distorted voltage on the DDF measurement. Based on a circuit model with the polarization loss, a mathematical formula is derived which shows that, given the same RMS applied voltage, the DDF value will decrease with increasing harmonic distortion level. The theoretical formulation is implemented in computer simulation using MATLAB Simulink to validate the results. Laboratory experiments were carried out on a 33kV dry-type current transformer which confirmed the monotonically decreasing pattern, but the trend is more complex.","PeriodicalId":345626,"journal":{"name":"2021 International Conference on Smart-Green Technology in Electrical and Information Systems (ICSGTEIS)","volume":"2 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2021-10-28","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"Dielectric Dissipation Factor Measurement of Power Equipment under Distorted Excitation Voltage\",\"authors\":\"Pratic A Muntakim, Jun-yan Zhang, Shubin Zhang, B. Phung\",\"doi\":\"10.1109/ICSGTEIS53426.2021.9650374\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The dielectric dissipation factor (DDF) is a useful parameter for the diagnosis of high voltage equipment insulation condition. Traditionally, the AC power grid voltage was considered pure sinusoidal. Due to the increasing presence of non-linear loads in the power system, the grid voltage nowadays gets distorted with high frequency harmonics. This paper investigates the impact of distorted voltage on the DDF measurement. Based on a circuit model with the polarization loss, a mathematical formula is derived which shows that, given the same RMS applied voltage, the DDF value will decrease with increasing harmonic distortion level. The theoretical formulation is implemented in computer simulation using MATLAB Simulink to validate the results. Laboratory experiments were carried out on a 33kV dry-type current transformer which confirmed the monotonically decreasing pattern, but the trend is more complex.\",\"PeriodicalId\":345626,\"journal\":{\"name\":\"2021 International Conference on Smart-Green Technology in Electrical and Information Systems (ICSGTEIS)\",\"volume\":\"2 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2021-10-28\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2021 International Conference on Smart-Green Technology in Electrical and Information Systems (ICSGTEIS)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ICSGTEIS53426.2021.9650374\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2021 International Conference on Smart-Green Technology in Electrical and Information Systems (ICSGTEIS)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICSGTEIS53426.2021.9650374","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

摘要

介质耗散系数(DDF)是诊断高压设备绝缘状态的一个有用参数。传统上,交流电网电压被认为是纯正弦的。由于电力系统中非线性负荷的增加,电网电压受到高频谐波的畸变。本文研究了失真电压对DDF测量的影响。在考虑极化损耗的电路模型的基础上,推导出了当有效值电压相同时,DDF值随谐波失真程度的增加而减小的数学公式。利用MATLAB Simulink对理论公式进行了计算机仿真验证。在33kV干式电流互感器上进行了室内实验,证实了其单调递减规律,但其变化趋势较为复杂。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Dielectric Dissipation Factor Measurement of Power Equipment under Distorted Excitation Voltage
The dielectric dissipation factor (DDF) is a useful parameter for the diagnosis of high voltage equipment insulation condition. Traditionally, the AC power grid voltage was considered pure sinusoidal. Due to the increasing presence of non-linear loads in the power system, the grid voltage nowadays gets distorted with high frequency harmonics. This paper investigates the impact of distorted voltage on the DDF measurement. Based on a circuit model with the polarization loss, a mathematical formula is derived which shows that, given the same RMS applied voltage, the DDF value will decrease with increasing harmonic distortion level. The theoretical formulation is implemented in computer simulation using MATLAB Simulink to validate the results. Laboratory experiments were carried out on a 33kV dry-type current transformer which confirmed the monotonically decreasing pattern, but the trend is more complex.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信