Influence of cooling surface area on indoor air and surface heat transfer characteristics of a thermally activated building system in warm and humid zones: An Experimental study

IF 1.8 4区 工程技术 Q3 CONSTRUCTION & BUILDING TECHNOLOGY
T. Vivek, K. Balaji
{"title":"Influence of cooling surface area on indoor air and surface heat transfer characteristics of a thermally activated building system in warm and humid zones: An Experimental study","authors":"T. Vivek, K. Balaji","doi":"10.1177/17442591231177428","DOIUrl":null,"url":null,"abstract":"Several alternatives have been introduced in recent years to enhance the thermal comfort levels within buildings. Thermally Activated Building Systems (TABS), one of the above alternatives, have gained interest because of the huge benefits this technology offers the building sector. This type of system consists of encapsulated pipes within the building structure to control the surface temperature. This study explores the thermal behavior of the cooling surface and fluctuations in indoor air temperature (IAT) of TABS under various cooling scenarios. Only limited number of investigations has been carried out to study the heat transfer behavior of TABS. Hence, the building indoor thermal properties such as air temperature, surface temperature and rate of heat transfer between the indoor air and inner surface of the TABS has been evaluated experimentally by enhancing the cooling surface area. Moreover the results were compared with the conventional building (no cooling provides). The thermal energy stored in the TABS is significantly removed by the increase in cooling surface area, resulting in a 2°C decrease in the average indoor air temperature. The average heat gain of all wall surfaces in the case of no cooling (WOC) ranges from −3 to 13 W/m2. The amount of heat gain on the walls was not significantly affected by only roof and floor cooling (R+F) activities. Moreover, it ranged from −2 to 24 W/m2 in all surface cooling (ASC) scenarios. As a result, there was additional surface cooling, which increased surface heat gain and indoor cooling capacity.","PeriodicalId":50249,"journal":{"name":"Journal of Building Physics","volume":"9 1","pages":"204 - 229"},"PeriodicalIF":1.8000,"publicationDate":"2023-06-29","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Journal of Building Physics","FirstCategoryId":"5","ListUrlMain":"https://doi.org/10.1177/17442591231177428","RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"CONSTRUCTION & BUILDING TECHNOLOGY","Score":null,"Total":0}
引用次数: 1

Abstract

Several alternatives have been introduced in recent years to enhance the thermal comfort levels within buildings. Thermally Activated Building Systems (TABS), one of the above alternatives, have gained interest because of the huge benefits this technology offers the building sector. This type of system consists of encapsulated pipes within the building structure to control the surface temperature. This study explores the thermal behavior of the cooling surface and fluctuations in indoor air temperature (IAT) of TABS under various cooling scenarios. Only limited number of investigations has been carried out to study the heat transfer behavior of TABS. Hence, the building indoor thermal properties such as air temperature, surface temperature and rate of heat transfer between the indoor air and inner surface of the TABS has been evaluated experimentally by enhancing the cooling surface area. Moreover the results were compared with the conventional building (no cooling provides). The thermal energy stored in the TABS is significantly removed by the increase in cooling surface area, resulting in a 2°C decrease in the average indoor air temperature. The average heat gain of all wall surfaces in the case of no cooling (WOC) ranges from −3 to 13 W/m2. The amount of heat gain on the walls was not significantly affected by only roof and floor cooling (R+F) activities. Moreover, it ranged from −2 to 24 W/m2 in all surface cooling (ASC) scenarios. As a result, there was additional surface cooling, which increased surface heat gain and indoor cooling capacity.
温湿地区热激活建筑系统冷却面积对室内空气和表面传热特性影响的实验研究
近年来已经引入了几种替代方案来提高建筑物内的热舒适水平。热激活建筑系统(TABS)是上述替代方案之一,由于该技术为建筑行业提供了巨大的好处,因此引起了人们的兴趣。这种类型的系统由建筑结构内的密封管道组成,以控制表面温度。本研究探讨了不同冷却方案下,tab冷却表面的热行为和室内空气温度的波动。只有有限的研究进行了传热行为的tab。因此,建筑室内热性能,如空气温度,表面温度和传热率之间的室内空气和tab的内表面之间的实验评估通过增加冷却面积。并与传统建筑(不提供冷却)进行了比较。由于冷却表面积的增加,储存在tab中的热能被显著去除,导致室内平均空气温度降低2°C。在无冷却(WOC)情况下,所有壁面的平均热增益范围为−3 ~ 13w /m2。仅屋顶和地板冷却(R+F)活动对墙壁上的热增益没有显著影响。此外,在所有表面冷却(ASC)方案中,其范围为−2至24 W/m2。因此,有额外的表面冷却,这增加了表面的热量增益和室内的冷却能力。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
Journal of Building Physics
Journal of Building Physics 工程技术-结构与建筑技术
CiteScore
5.10
自引率
15.00%
发文量
10
审稿时长
5.3 months
期刊介绍: Journal of Building Physics (J. Bldg. Phys) is an international, peer-reviewed journal that publishes a high quality research and state of the art “integrated” papers to promote scientifically thorough advancement of all the areas of non-structural performance of a building and particularly in heat, air, moisture transfer.
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信