S. Parikh, Michael J. Sustarich, R. Hulett, Eric Reitler
{"title":"Considering process temperatures when designing electrical heat tracing for hazardous areas","authors":"S. Parikh, Michael J. Sustarich, R. Hulett, Eric Reitler","doi":"10.1109/PCICON.2011.6085878","DOIUrl":null,"url":null,"abstract":"Hazardous areas in many industrial process facilities often represent design challenges for high temperature electrical heat tracing (EHT) applications. When there is a relatively close proximity of the maintenance temperatures and Auto-ignition Temperature (AIT) or T-Rating, Controlled Designs per IEEE-515-2004 are utilized to achieve the desired maintain temperatures. Other common techniques of reducing heat tracing sheath temperatures include improving tracer contact with the process pipe, decreasing tracer output and / or increasing the number of heat tracing passes. This paper will present design methods to establish maximum heat tracing sheath temperatures in Class I Division 2 gaseous environments. Design tradeoffs and resolution approaches when the process temperature exceeds the AIT or T-rating are also presented.","PeriodicalId":67291,"journal":{"name":"中国石油和化工(企业版)","volume":"27 1","pages":"1-5"},"PeriodicalIF":0.0000,"publicationDate":"2011-11-28","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"中国石油和化工(企业版)","FirstCategoryId":"1087","ListUrlMain":"https://doi.org/10.1109/PCICON.2011.6085878","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1
Abstract
Hazardous areas in many industrial process facilities often represent design challenges for high temperature electrical heat tracing (EHT) applications. When there is a relatively close proximity of the maintenance temperatures and Auto-ignition Temperature (AIT) or T-Rating, Controlled Designs per IEEE-515-2004 are utilized to achieve the desired maintain temperatures. Other common techniques of reducing heat tracing sheath temperatures include improving tracer contact with the process pipe, decreasing tracer output and / or increasing the number of heat tracing passes. This paper will present design methods to establish maximum heat tracing sheath temperatures in Class I Division 2 gaseous environments. Design tradeoffs and resolution approaches when the process temperature exceeds the AIT or T-rating are also presented.