{"title":"On-line monitoring of winding deformation of power transformer","authors":"D.K. Xu, J. Huang, Y.M. Li","doi":"10.1109/ISEIM.2001.973812","DOIUrl":null,"url":null,"abstract":"The feasibility of estimating transformer winding deformation by measuring short-circuit reactance is expounded. Based on the theoretical research, the on-line measurement system for short-circuit reactance of a transformer is proposed. The study on a power transformer in actual operating condition shows that the on-line method is satisfactory for detecting short-circuit reactance variations with high degree of accuracy and good stability, and can be used for detecting deformation in the transformer windings.","PeriodicalId":71964,"journal":{"name":"装备机械","volume":"2 1","pages":"853-856"},"PeriodicalIF":0.0000,"publicationDate":"2001-11-19","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"27","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"装备机械","FirstCategoryId":"1087","ListUrlMain":"https://doi.org/10.1109/ISEIM.2001.973812","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 27
Abstract
The feasibility of estimating transformer winding deformation by measuring short-circuit reactance is expounded. Based on the theoretical research, the on-line measurement system for short-circuit reactance of a transformer is proposed. The study on a power transformer in actual operating condition shows that the on-line method is satisfactory for detecting short-circuit reactance variations with high degree of accuracy and good stability, and can be used for detecting deformation in the transformer windings.