Improving electrical saftey in an electrolytic cell line

A. Long, Brad Boyd, J. Phillips, Ray Machado, E. Kelly, Marcelle Tremblay, Edward J Cialkowski
{"title":"Improving electrical saftey in an electrolytic cell line","authors":"A. Long, Brad Boyd, J. Phillips, Ray Machado, E. Kelly, Marcelle Tremblay, Edward J Cialkowski","doi":"10.1109/PCIC.2010.5666817","DOIUrl":null,"url":null,"abstract":"Due to the design and layout of the electrolytic cell production plant, electrical safety is challenging. The cells, which are connected in a series circuit creating a large layout, are powered by a 200–500 volt DC source, which is intentionally ungrounded to provide personnel and equipment protection. Detection of the first ground connection of the electrolytic cell line is critical to ensure safety to personnel. Traditional methods of ground connection monitoring of a cell line, such as midpoint zero-volt detection, require constant analysis of data to determine if the first ground exists. This method can easily lead to human error, since the zero-volt location changes when cells are removed or added to the cell line. Also, the midpoint zero-volt method only functions when the cell line is energized, which makes troubleshooting not only a safety concern but also difficult. Moreover, if the ground connection occurs at the zero-volt location, there is no indication of the increased electrical hazard. Protection from electrical shocks and electrocution is safety critical and requires an instrument that continuously monitors the dynamic insulation resistance-to-ground of the entire cell line. The instrument must perform this vital safety function whether the cell line is energized or de-energized, so that finding the first ground quickly is easy and can be achieved without applying power to the cell line. Existing DC ground fault detection equipment, or insulation monitoring device, used in the mass transit and other industries has been adapted to accomplish this necessary ground fault detection in the electrolytic cell line; thereby, improving electrical safety in an electrolytic cell line.","PeriodicalId":67291,"journal":{"name":"中国石油和化工(企业版)","volume":"37 1","pages":"1-13"},"PeriodicalIF":0.0000,"publicationDate":"2010-12-13","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"中国石油和化工(企业版)","FirstCategoryId":"1087","ListUrlMain":"https://doi.org/10.1109/PCIC.2010.5666817","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

Due to the design and layout of the electrolytic cell production plant, electrical safety is challenging. The cells, which are connected in a series circuit creating a large layout, are powered by a 200–500 volt DC source, which is intentionally ungrounded to provide personnel and equipment protection. Detection of the first ground connection of the electrolytic cell line is critical to ensure safety to personnel. Traditional methods of ground connection monitoring of a cell line, such as midpoint zero-volt detection, require constant analysis of data to determine if the first ground exists. This method can easily lead to human error, since the zero-volt location changes when cells are removed or added to the cell line. Also, the midpoint zero-volt method only functions when the cell line is energized, which makes troubleshooting not only a safety concern but also difficult. Moreover, if the ground connection occurs at the zero-volt location, there is no indication of the increased electrical hazard. Protection from electrical shocks and electrocution is safety critical and requires an instrument that continuously monitors the dynamic insulation resistance-to-ground of the entire cell line. The instrument must perform this vital safety function whether the cell line is energized or de-energized, so that finding the first ground quickly is easy and can be achieved without applying power to the cell line. Existing DC ground fault detection equipment, or insulation monitoring device, used in the mass transit and other industries has been adapted to accomplish this necessary ground fault detection in the electrolytic cell line; thereby, improving electrical safety in an electrolytic cell line.
提高电解槽生产线的电气安全性
由于电解槽生产工厂的设计和布局,电气安全具有挑战性。这些单元以串联电路连接,形成一个大的布局,由200-500伏直流电源供电,该电源故意不接地,以提供人员和设备保护。检测电解槽线的第一次接地连接对确保人员安全至关重要。对细胞系进行接地监测的传统方法,如中点零伏检测,需要不断分析数据以确定是否存在第一个接地。这种方法很容易导致人为错误,因为当细胞被移除或添加到细胞系时,零伏位置会发生变化。此外,中点零伏特方法仅在细胞系通电时起作用,这使得故障排除不仅是一个安全问题,而且很困难。此外,如果接地发生在零伏位置,没有迹象表明电气危险增加。防止触电和触电对安全至关重要,需要一种仪器连续监测整个细胞系的动态绝缘对地电阻。无论细胞系通电还是断电,仪器都必须执行这一重要的安全功能,以便快速找到第一接地,并且可以在不向细胞系通电的情况下实现。现有的直流接地故障检测设备,或绝缘监测装置,应用于轨道交通等行业,已适应在电解槽线路中完成这种必要的接地故障检测;从而提高电解槽系的电气安全性。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
346
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书