RESEARCH OF ELECTRIC POWER QUALITY OF TRACTION SUBSTATIONS OF A HIGH MOUNTAIN MINER

IF 0.1 Q4 GEOSCIENCES, MULTIDISCIPLINARY
R. Klyuev, O. Fomenko, I. Bosikov, O. Gavrina
{"title":"RESEARCH OF ELECTRIC POWER QUALITY OF TRACTION SUBSTATIONS OF A HIGH MOUNTAIN MINER","authors":"R. Klyuev, O. Fomenko, I. Bosikov, O. Gavrina","doi":"10.46689/2218-5194-2021-4-1-399-415","DOIUrl":null,"url":null,"abstract":"The paper presents a methodology for researching the levels of higher harmonic in networks with a voltage of 6 kV and developed measures to eliminate harmonics of the non-canonical series. According to the results of the research, it was found that the sources of high-er harmonic ones are the ATP-500 traction substations, connected to the 6 kV network in groups and alone. In the 6 kV network, the 3rd, 5th, 7th and 11th harmonics of the canonical series, as well as the 3rd, 4th, 6th and 8th harmonics of the non-canonical series, are distin-guished, the levels of which significantly exceed the permissible levels according to GOST. The presence of non-canonical harmonics is caused by the asymmetry of the bridge circuit (current asymmetry relative to the abscissa axis). An instruction has been developed for the pre-start check of the bridge circuit gates to eliminate asymmetry. The prevalence of 5 and 7 higher harmonics in the 6 kV network was established and it was recommended to take into account the possibility of resonance phenomena in the pulse-phase control circuits of electric drives connected to the 6 kV network of the mine and open pit. The implementation of the recommen-dations set forth in the work increases the reliability of the bridge circuits of traction substa-tions and eliminates the possibility of the appearance of non-canonical harmonics, which im-proves the voltage quality in accordance with the requirements of GOST.","PeriodicalId":41869,"journal":{"name":"Proceedings of the Tula States University-Sciences of Earth","volume":"1 1","pages":""},"PeriodicalIF":0.1000,"publicationDate":"2021-01-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Proceedings of the Tula States University-Sciences of Earth","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.46689/2218-5194-2021-4-1-399-415","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q4","JCRName":"GEOSCIENCES, MULTIDISCIPLINARY","Score":null,"Total":0}
引用次数: 1

Abstract

The paper presents a methodology for researching the levels of higher harmonic in networks with a voltage of 6 kV and developed measures to eliminate harmonics of the non-canonical series. According to the results of the research, it was found that the sources of high-er harmonic ones are the ATP-500 traction substations, connected to the 6 kV network in groups and alone. In the 6 kV network, the 3rd, 5th, 7th and 11th harmonics of the canonical series, as well as the 3rd, 4th, 6th and 8th harmonics of the non-canonical series, are distin-guished, the levels of which significantly exceed the permissible levels according to GOST. The presence of non-canonical harmonics is caused by the asymmetry of the bridge circuit (current asymmetry relative to the abscissa axis). An instruction has been developed for the pre-start check of the bridge circuit gates to eliminate asymmetry. The prevalence of 5 and 7 higher harmonics in the 6 kV network was established and it was recommended to take into account the possibility of resonance phenomena in the pulse-phase control circuits of electric drives connected to the 6 kV network of the mine and open pit. The implementation of the recommen-dations set forth in the work increases the reliability of the bridge circuits of traction substa-tions and eliminates the possibility of the appearance of non-canonical harmonics, which im-proves the voltage quality in accordance with the requirements of GOST.
某高山煤矿牵引变电所电能质量研究
本文提出了一种研究电压为6kv的电网中高次谐波水平的方法,并提出了消除非正则串联谐波的措施。研究结果表明,高次谐波源为ATP-500牵引变电所,该变电所成组或单独接入6kv电网。在6kv电网中,规范串联的第3、第5、第7、第11次谐波和非规范串联的第3、第4、第6、第8次谐波被区分出来,其电平明显超过GOST的允许电平。非规范谐波的存在是由桥电路的不对称引起的(相对于横轴的电流不对称)。提出了一种桥式电路门的预启动检查指令,以消除不对称。建立了6kv网络中5次和7次高次谐波的流行率,并建议考虑与矿山和露天矿6kv网络连接的电传动脉冲相位控制电路中谐振现象的可能性。工作中提出的建议的实施,提高了牵引变电站桥式电路的可靠性,消除了出现非正则谐波的可能性,提高了符合GOST要求的电压质量。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信