Rapid In-Air Inactivation of Influenza A Virus Using an In-Duct Cold Atmospheric Plasma Panel

IF 2.7 2区 环境科学与生态学 Q1 CONSTRUCTION & BUILDING TECHNOLOGY
Indoor air Pub Date : 2026-10-17 DOI:10.1155/ina/7268405
Luutzen F. A. Wymenga, Suzanne M. A. Mijnhardt, Mohamad Ghaffarian Niasar, Willem D. van Driel, GuoQi Zhang, Pieter L. A. Fraaij, Ron A. M. Fouchier, Sander Herfst
{"title":"Rapid In-Air Inactivation of Influenza A Virus Using an In-Duct Cold Atmospheric Plasma Panel","authors":"Luutzen F. A. Wymenga,&nbsp;Suzanne M. A. Mijnhardt,&nbsp;Mohamad Ghaffarian Niasar,&nbsp;Willem D. van Driel,&nbsp;GuoQi Zhang,&nbsp;Pieter L. A. Fraaij,&nbsp;Ron A. M. Fouchier,&nbsp;Sander Herfst","doi":"10.1155/ina/7268405","DOIUrl":null,"url":null,"abstract":"<p>Respiratory virus infections pose a major public health burden and pandemic risk, especially when they are transmissible via the air. Consequently, there is an urgent need for effective control measures to mitigate airborne transmission. Cold atmospheric plasma (CAP) offers a promising solution for in-air virus inactivation by exposing viruses to a mixture of electrons, ions, photons, and reactive oxygen and nitrogen species (RONS). Here, a grating dielectric barrier discharge (DBD) panel consisting of 88 glass-covered electrodes was developed. Plasma formation using a high-voltage neon transformer was confirmed across all electrodes, with a power deposition of approximately 5 W. In an open acrylic tube, representative of an air duct, ozone levels increased to a maximum of 90 ppm and returned to zero within 30 s after the DBD panel was turned off. The obstructing area of the electrodes was 13%, resulting in a lower pressure drop than the current standard HEPA filters. The DBD panel was further tested in an aerosol chamber where the viability of artificially aerosolized influenza A virus (IAV) after a single passage through the DBD panel was assessed. Plaque assays showed that virus inactivation increased with exposure time, reaching 96.9% inactivation after 15 s of exposure and up to 99.9% inactivation when aerosolization followed prior RONS accumulation, whereas RNA levels and air temperature remained largely unaffected. These results demonstrate that in-duct DBD panels can effectively inactivate IAV in aerosols without leaving persistent toxic residues. This proof-of-concept study might give future directions for implementation of CAP technology in high-risk settings such as hospitals, livestock facilities, and transportation hubs to reduce the spread of infectious virus in the environment.</p>","PeriodicalId":13529,"journal":{"name":"Indoor air","volume":"2026 1","pages":""},"PeriodicalIF":2.7000,"publicationDate":"2026-10-17","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"https://onlinelibrary.wiley.com/doi/epdf/10.1155/ina/7268405","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Indoor air","FirstCategoryId":"93","ListUrlMain":"https://onlinelibrary.wiley.com/doi/10.1155/ina/7268405","RegionNum":2,"RegionCategory":"环境科学与生态学","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q1","JCRName":"CONSTRUCTION & BUILDING TECHNOLOGY","Score":null,"Total":0}
引用次数: 0

Abstract

Respiratory virus infections pose a major public health burden and pandemic risk, especially when they are transmissible via the air. Consequently, there is an urgent need for effective control measures to mitigate airborne transmission. Cold atmospheric plasma (CAP) offers a promising solution for in-air virus inactivation by exposing viruses to a mixture of electrons, ions, photons, and reactive oxygen and nitrogen species (RONS). Here, a grating dielectric barrier discharge (DBD) panel consisting of 88 glass-covered electrodes was developed. Plasma formation using a high-voltage neon transformer was confirmed across all electrodes, with a power deposition of approximately 5 W. In an open acrylic tube, representative of an air duct, ozone levels increased to a maximum of 90 ppm and returned to zero within 30 s after the DBD panel was turned off. The obstructing area of the electrodes was 13%, resulting in a lower pressure drop than the current standard HEPA filters. The DBD panel was further tested in an aerosol chamber where the viability of artificially aerosolized influenza A virus (IAV) after a single passage through the DBD panel was assessed. Plaque assays showed that virus inactivation increased with exposure time, reaching 96.9% inactivation after 15 s of exposure and up to 99.9% inactivation when aerosolization followed prior RONS accumulation, whereas RNA levels and air temperature remained largely unaffected. These results demonstrate that in-duct DBD panels can effectively inactivate IAV in aerosols without leaving persistent toxic residues. This proof-of-concept study might give future directions for implementation of CAP technology in high-risk settings such as hospitals, livestock facilities, and transportation hubs to reduce the spread of infectious virus in the environment.

利用管道内冷大气等离子体面板在空气中快速灭活甲型流感病毒
呼吸道病毒感染构成重大公共卫生负担和大流行风险,特别是当它们通过空气传播时。因此,迫切需要有效的控制措施来减轻空气传播。低温大气等离子体(CAP)通过将病毒暴露于电子、离子、光子以及活性氧和活性氮(RONS)的混合物中,为空气中病毒灭活提供了一种很有前途的解决方案。本文研制了一种由88个玻璃覆盖电极组成的光栅介质阻挡放电面板。使用高压霓虹灯变压器在所有电极上确认了等离子体的形成,功率沉积约为5w。在一个开放的丙烯酸管中,空气管道的代表,臭氧水平增加到90 ppm的最大值,并在DBD面板关闭后30秒内恢复为零。电极的阻挡面积为13%,因此比目前标准HEPA过滤器的压降更低。在气溶胶室中对DBD面板进行了进一步测试,评估人工雾化的甲型流感病毒(IAV)通过DBD面板后的生存能力。空斑分析显示,病毒失活随暴露时间增加而增加,暴露15 s后达到96.9%的失活,在先前的RONS积累后雾化时达到99.9%的失活,而RNA水平和空气温度基本未受影响。这些结果表明,导管内DBD面板可以有效地灭活气溶胶中的IAV,而不会留下持久的有毒残留物。这项概念验证研究可能为在医院、牲畜设施和交通枢纽等高风险环境中实施CAP技术提供未来方向,以减少传染性病毒在环境中的传播。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
Indoor air
Indoor air 环境科学-工程:环境
CiteScore
10.80
自引率
10.30%
发文量
175
审稿时长
3 months
期刊介绍: The quality of the environment within buildings is a topic of major importance for public health. Indoor Air provides a location for reporting original research results in the broad area defined by the indoor environment of non-industrial buildings. An international journal with multidisciplinary content, Indoor Air publishes papers reflecting the broad categories of interest in this field: health effects; thermal comfort; monitoring and modelling; source characterization; ventilation and other environmental control techniques. The research results present the basic information to allow designers, building owners, and operators to provide a healthy and comfortable environment for building occupants, as well as giving medical practitioners information on how to deal with illnesses related to the indoor environment.
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书