Thermo-economic analysis of a wire-mesh integrated photovoltaic thermal collector

IF 7.5 2区 工程技术 Q2 ENERGY & FUELS
Applied Thermal Engineering Pub Date : 2026-10-01 Epub Date: 2026-09-29 DOI:10.1016/j.applthermaleng.2026.133467
Nitesh Singh, Prabhakar Jha
{"title":"Thermo-economic analysis of a wire-mesh integrated photovoltaic thermal collector","authors":"Nitesh Singh,&nbsp;Prabhakar Jha","doi":"10.1016/j.applthermaleng.2026.133467","DOIUrl":null,"url":null,"abstract":"<div><div>This study experimentally compared a flat-plate photovoltaic-thermal air collector with and without a double-crimped galvanized iron wire mesh. Both units were tested together for eight days under identical outdoor conditions in Noida, India at an optimized airflow rate of 0.0165 kg/s. The hourly and daily means, along with standard deviations and 95% confidence intervals, were calculated; statistical significance tests were carried out; and a sensitivity analysis was performed to confirm the robustness of the mesh-integrated PVT system over the conventional PVT system. The mesh-integrated system maintained a 2.5 °C lower mean PV module temperature and a 2.1 °C higher mean outlet air temperature than the conventional unit. On an annual basis, the mesh-integrated system generated 43.2% higher mean thermal energy, 74.2% higher mean thermal exergy, and 1.9% higher mean net electrical energy than the conventional unit. Overall annual energy and exergy outputs rose by 19.25% and 3.15%, respectively. Despite a 2.5% increase in embodied energy, the mesh-integrated system required 14.18% and 0.58% less time on an overall energy and exergy basis to recover the invested energy. Over a 25-year lifespan, it mitigated 19.21% more CO₂ on an overall energy basis and 3.16% more on an overall exergy basis, yielding higher carbon-credit potential. Therefore, with better energy- and enviro-economic parameters, the mesh-integrated system has enhanced techno-economic and environmental viability over the conventional unit.</div></div>","PeriodicalId":8201,"journal":{"name":"Applied Thermal Engineering","volume":"307 ","pages":"Article 133467"},"PeriodicalIF":7.5000,"publicationDate":"2026-10-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Applied Thermal Engineering","FirstCategoryId":"5","ListUrlMain":"https://www.sciencedirect.com/science/article/pii/S1359431126037750","RegionNum":2,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"2026/9/29 0:00:00","PubModel":"Epub","JCR":"Q2","JCRName":"ENERGY & FUELS","Score":null,"Total":0}
引用次数: 0

Abstract

This study experimentally compared a flat-plate photovoltaic-thermal air collector with and without a double-crimped galvanized iron wire mesh. Both units were tested together for eight days under identical outdoor conditions in Noida, India at an optimized airflow rate of 0.0165 kg/s. The hourly and daily means, along with standard deviations and 95% confidence intervals, were calculated; statistical significance tests were carried out; and a sensitivity analysis was performed to confirm the robustness of the mesh-integrated PVT system over the conventional PVT system. The mesh-integrated system maintained a 2.5 °C lower mean PV module temperature and a 2.1 °C higher mean outlet air temperature than the conventional unit. On an annual basis, the mesh-integrated system generated 43.2% higher mean thermal energy, 74.2% higher mean thermal exergy, and 1.9% higher mean net electrical energy than the conventional unit. Overall annual energy and exergy outputs rose by 19.25% and 3.15%, respectively. Despite a 2.5% increase in embodied energy, the mesh-integrated system required 14.18% and 0.58% less time on an overall energy and exergy basis to recover the invested energy. Over a 25-year lifespan, it mitigated 19.21% more CO₂ on an overall energy basis and 3.16% more on an overall exergy basis, yielding higher carbon-credit potential. Therefore, with better energy- and enviro-economic parameters, the mesh-integrated system has enhanced techno-economic and environmental viability over the conventional unit.
一种线网集成光伏集热器的热经济分析
本研究通过实验比较了带和不带双卷曲镀锌铁丝网的平板光伏热风集热器。在印度诺伊达,两种装置在相同的室外条件下进行了8天的测试,优化气流速率为0.0165 kg/s。计算每小时和每天的平均值,以及标准差和95%置信区间;进行统计学显著性检验;通过灵敏度分析,验证了网格一体化PVT系统相对于传统PVT系统的鲁棒性。与传统装置相比,网格集成系统的光伏组件平均温度降低了2.5℃,平均出风口温度提高了2.1℃。与常规机组相比,网格一体化系统年平均发电量高43.2%,年平均热用能高74.2%,年平均净电能高1.9%。全年能源和火用总量分别增长19.25%和3.15%。尽管蕴藏能量增加了2.5%,但mesh-integrated系统需要更少的时间14.18%和0.58%在整体能源和(火用)的基础上恢复能源投资。在25年的使用寿命中,它在总体能源基础上减少了19.21%的二氧化碳,在总体能源基础上减少了3.16%的二氧化碳,产生了更高的碳信用潜力。因此,由于具有更好的能源和环境经济参数,网格集成系统比常规装置具有更高的技术经济和环境可行性。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
Applied Thermal Engineering
Applied Thermal Engineering 工程技术-工程:机械
CiteScore
11.30
自引率
15.60%
发文量
1474
审稿时长
57 days
期刊介绍: Applied Thermal Engineering disseminates novel research related to the design, development and demonstration of components, devices, equipment, technologies and systems involving thermal processes for the production, storage, utilization and conservation of energy, with a focus on engineering application. The journal publishes high-quality and high-impact Original Research Articles, Review Articles, Short Communications and Letters to the Editor on cutting-edge innovations in research, and recent advances or issues of interest to the thermal engineering community.
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书