A Validation Method for UHF Partial Discharge Localization in Power Transformers Based on Pulse Injection

IF 3.3 3区 工程技术 Q2 ENGINEERING, ELECTRICAL & ELECTRONIC
Zirui Wu;Cheng Pan;Zijun Pan;Qingdong Zhu;Hui Wang;Ju Tang
{"title":"A Validation Method for UHF Partial Discharge Localization in Power Transformers Based on Pulse Injection","authors":"Zirui Wu;Cheng Pan;Zijun Pan;Qingdong Zhu;Hui Wang;Ju Tang","doi":"10.1109/TDEI.2026.3656146","DOIUrl":null,"url":null,"abstract":"Accurate localization of partial discharge (PD) in power transformers is critical for condition monitoring and fault prevention. However, localization algorithms are primarily validated through laboratory experiments or offline tests, making it difficult to assess their performance accurately in operational transformers. In this article, a method is proposed to evaluate the positioning accuracy of PD localization algorithms by injecting pulse current into an ultrahigh-frequency (UHF) sensor to simulate a PD source. The proposed method is first validated on an in-service 220-kV transformer equipped with six built-in UHF sensors. The results show that this method is safe, controllable, and capable of flexibly changing the location of PD. Furthermore, extensive experiments are conducted on another 220-kV transformer equipped with 18 built-in UHF sensors to systematically analyze the impact of sensor number and placement on the localization error of time difference of arrival (TDOA). It is found that increasing the number of sensors can reduce the likelihood of large positioning errors to some extent. However, for highly accurate positioning, the best result is achieved when using five or six sensors. In terms of sensor placement, TDOA-based localization is less robust when sensors are placed on the same side or in adjacent areas. Uniform placement on all sides of the transformer can improve robustness, but it is difficult to achieve a high accuracy of the positioning error within 0.5 m.","PeriodicalId":13247,"journal":{"name":"IEEE Transactions on Dielectrics and Electrical Insulation","volume":"33 5","pages":"3705-3712"},"PeriodicalIF":3.3000,"publicationDate":"2026-10-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"IEEE Transactions on Dielectrics and Electrical Insulation","FirstCategoryId":"5","ListUrlMain":"https://ieeexplore.ieee.org/document/11358980/","RegionNum":3,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"2026/1/19 0:00:00","PubModel":"Epub","JCR":"Q2","JCRName":"ENGINEERING, ELECTRICAL & ELECTRONIC","Score":null,"Total":0}
引用次数: 0

Abstract

Accurate localization of partial discharge (PD) in power transformers is critical for condition monitoring and fault prevention. However, localization algorithms are primarily validated through laboratory experiments or offline tests, making it difficult to assess their performance accurately in operational transformers. In this article, a method is proposed to evaluate the positioning accuracy of PD localization algorithms by injecting pulse current into an ultrahigh-frequency (UHF) sensor to simulate a PD source. The proposed method is first validated on an in-service 220-kV transformer equipped with six built-in UHF sensors. The results show that this method is safe, controllable, and capable of flexibly changing the location of PD. Furthermore, extensive experiments are conducted on another 220-kV transformer equipped with 18 built-in UHF sensors to systematically analyze the impact of sensor number and placement on the localization error of time difference of arrival (TDOA). It is found that increasing the number of sensors can reduce the likelihood of large positioning errors to some extent. However, for highly accurate positioning, the best result is achieved when using five or six sensors. In terms of sensor placement, TDOA-based localization is less robust when sensors are placed on the same side or in adjacent areas. Uniform placement on all sides of the transformer can improve robustness, but it is difficult to achieve a high accuracy of the positioning error within 0.5 m.
基于脉冲注入的电力变压器超高频局部放电定位验证方法
电力变压器局部放电的准确定位对状态监测和故障预防至关重要。然而,定位算法主要通过实验室实验或离线测试进行验证,这使得难以准确评估其在运行变压器中的性能。本文提出了一种通过向超高频(UHF)传感器注入脉冲电流来模拟PD源的方法来评估PD定位算法的定位精度。该方法首先在一台内置6个超高频传感器的220千伏在役变压器上进行了验证。结果表明,该方法安全、可控,能够灵活改变PD位置。在另一台内置18个UHF传感器的220 kv变压器上进行了大量实验,系统分析了传感器数量和放置位置对到达时差(TDOA)定位误差的影响。研究发现,增加传感器的数量可以在一定程度上降低出现较大定位误差的可能性。然而,对于高度精确的定位,使用五到六个传感器才能达到最佳效果。在传感器放置方面,当传感器放置在同一侧或相邻区域时,基于tdoa的定位鲁棒性较差。变压器四面均匀放置可提高稳健性,但定位误差难以在0.5 m以内实现高精度。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
IEEE Transactions on Dielectrics and Electrical Insulation
IEEE Transactions on Dielectrics and Electrical Insulation 工程技术-工程:电子与电气
CiteScore
6.00
自引率
22.60%
发文量
309
审稿时长
5.2 months
期刊介绍: Topics that are concerned with dielectric phenomena and measurements, with development and characterization of gaseous, vacuum, liquid and solid electrical insulating materials and systems; and with utilization of these materials in circuits and systems under condition of use.
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书