Spatial distribution and influencing factors of data center water usage effectiveness in China

IF 10.7 1区 环境科学与生态学 Q1 ENGINEERING, ENVIRONMENTAL
Journal of Cleaner Production Pub Date : 2026-10-08 Epub Date: 2026-09-28 DOI:10.1016/j.jclepro.2026.149559
Yongzhen Wang, Jia Kang, Shengyi Li, Kai Han, Jiaxi Fan, Dongdong Zhou, Mingming Li
{"title":"Spatial distribution and influencing factors of data center water usage effectiveness in China","authors":"Yongzhen Wang,&nbsp;Jia Kang,&nbsp;Shengyi Li,&nbsp;Kai Han,&nbsp;Jiaxi Fan,&nbsp;Dongdong Zhou,&nbsp;Mingming Li","doi":"10.1016/j.jclepro.2026.149559","DOIUrl":null,"url":null,"abstract":"<div><div>This study evaluates the direct water consumption of data centers using water-side cooling systems in China. A WUE calculation framework is developed by coupling cooling-tower water loss with cooling-system COP. Long-term meteorological data are used to extract representative typical days, which are then used to simulate annual and seasonal WUE patterns across major Chinese cities. The results show a clear spatial pattern: WUE is generally lower in northern and western China and higher in southern and eastern China. For closed-circuit cooling towers, WUE is mostly below 1.0 L/kWh in Northeast China, Northwest China, and the Qinghai–Xizang Plateau, but approaches or exceeds 2.0 L/kWh in hot and humid cities in South China. Among the eight national data center hub regions, the wet-cooling operation ratio is 27.3% in Inner Mongolia, 36.6% in Ningxia, and 52.4% in Gansu, while it reaches 100% in the Pearl River Delta. The results indicate that climate conditions and cooling-control strategies strongly affect water use. In the model, a 7 °C wet-bulb threshold is used for closed-tower dry-wet switching and for identifying open-tower natural-cooling availability, while open-tower air-to-water-ratio modes are classified using seasonal mean dry-bulb temperature.</div></div>","PeriodicalId":349,"journal":{"name":"Journal of Cleaner Production","volume":"578 ","pages":"Article 149559"},"PeriodicalIF":10.7000,"publicationDate":"2026-10-08","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Journal of Cleaner Production","FirstCategoryId":"93","ListUrlMain":"https://www.sciencedirect.com/science/article/pii/S0959652626021001","RegionNum":1,"RegionCategory":"环境科学与生态学","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"2026/9/28 0:00:00","PubModel":"Epub","JCR":"Q1","JCRName":"ENGINEERING, ENVIRONMENTAL","Score":null,"Total":0}
引用次数: 0

Abstract

This study evaluates the direct water consumption of data centers using water-side cooling systems in China. A WUE calculation framework is developed by coupling cooling-tower water loss with cooling-system COP. Long-term meteorological data are used to extract representative typical days, which are then used to simulate annual and seasonal WUE patterns across major Chinese cities. The results show a clear spatial pattern: WUE is generally lower in northern and western China and higher in southern and eastern China. For closed-circuit cooling towers, WUE is mostly below 1.0 L/kWh in Northeast China, Northwest China, and the Qinghai–Xizang Plateau, but approaches or exceeds 2.0 L/kWh in hot and humid cities in South China. Among the eight national data center hub regions, the wet-cooling operation ratio is 27.3% in Inner Mongolia, 36.6% in Ningxia, and 52.4% in Gansu, while it reaches 100% in the Pearl River Delta. The results indicate that climate conditions and cooling-control strategies strongly affect water use. In the model, a 7 °C wet-bulb threshold is used for closed-tower dry-wet switching and for identifying open-tower natural-cooling availability, while open-tower air-to-water-ratio modes are classified using seasonal mean dry-bulb temperature.
中国数据中心用水效率空间分布及影响因素
本研究评估了中国使用水边冷却系统的数据中心的直接用水量。建立了将冷却塔失水与冷却系统COP耦合的WUE计算框架。利用长期气象数据提取具有代表性的典型日,然后利用这些典型日模拟中国主要城市的年和季节WUE模式。研究结果显示出明显的空间格局:水分利用效率总体上表现为北部和西部较低,南部和东部较高。闭式冷却塔WUE在东北、西北、青藏高原地区多在1.0 L/kWh以下,在华南湿热城市接近或超过2.0 L/kWh。在8个国家级数据中心枢纽区域中,内蒙古、宁夏和甘肃的湿冷运行比例分别为27.3%、36.6%和52.4%,而珠三角的湿冷运行比例达到100%。结果表明,气候条件和冷却控制策略对水分利用有重要影响。在模型中,7 °C湿球阈值用于闭塔干湿切换和确定开塔自然冷却可用性,而开塔空气-水比模式使用季节平均干球温度进行分类。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
Journal of Cleaner Production
Journal of Cleaner Production 环境科学-工程:环境
CiteScore
20.40
自引率
9.00%
发文量
4720
审稿时长
111 days
期刊介绍: The Journal of Cleaner Production is an international, transdisciplinary journal that addresses and discusses theoretical and practical Cleaner Production, Environmental, and Sustainability issues. It aims to help societies become more sustainable by focusing on the concept of 'Cleaner Production', which aims at preventing waste production and increasing efficiencies in energy, water, resources, and human capital use. The journal serves as a platform for corporations, governments, education institutions, regions, and societies to engage in discussions and research related to Cleaner Production, environmental, and sustainability practices.
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书