Delays in Protection Devices and Their Effects on Selectivity: The Reaction Time Gap

IF 4.8 Q1 ENGINEERING, ELECTRICAL & ELECTRONIC
IEEE open journal of power electronics Pub Date : 2026-01-01 Epub Date: 2026-03-19 DOI:10.1109/OJPEL.2026.3675767
Johannes Gehring;Raffael Schwanninger;Kilian Drexler;Bernd Wunder;Vincent Lorentz;Martin März
{"title":"Delays in Protection Devices and Their Effects on Selectivity: The Reaction Time Gap","authors":"Johannes Gehring;Raffael Schwanninger;Kilian Drexler;Bernd Wunder;Vincent Lorentz;Martin März","doi":"10.1109/OJPEL.2026.3675767","DOIUrl":null,"url":null,"abstract":"This Paper investigates how the internal delays of circuit breakers until the limitation of the fault current affect the selectivity of a low-voltage direct current (LVDC)-grid under short-circuit conditions. For conventional mechanical circuit breakers and future hybrid or solid-state devices, selectivity is, in line with AC practice, typically achieved by coordination based on their time-current trip characteristics. However, experimental short-circuit tests show that in DC-grids non-selective behavior can occur with high current slopes. To explain this effect, the delays until the fault current is effectively limited are analyzed. Based on this analysis, a critical time interval is identified and introduced as the reaction time gap. It describes the delay between the time when the circuit breaker should ideally trip immediately after detecting the fault and the time when it actually limits the current. To represent this behavior within conventional time–current characteristic curves, a measurement method for determining the relevant time intervals is proposed. A measurement-based study on several commercially available mechanical circuit breakers reveals the characteristics of short-circuit detection and current limitation, thereby confirming the existence of the reaction time gap and the resulting constraint on achievable selectivity. Possible countermeasures to overcome this reaction time gap relating to the behavior of the grid and the circuit breaker are outlined. Finally, the results and their implications for the design and protection coordination of DC-grids are discussed.","PeriodicalId":93182,"journal":{"name":"IEEE open journal of power electronics","volume":"7 ","pages":"1059-1074"},"PeriodicalIF":4.8000,"publicationDate":"2026-01-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"https://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=11447418","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"IEEE open journal of power electronics","FirstCategoryId":"1085","ListUrlMain":"https://ieeexplore.ieee.org/document/11447418/","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"2026/3/19 0:00:00","PubModel":"Epub","JCR":"Q1","JCRName":"ENGINEERING, ELECTRICAL & ELECTRONIC","Score":null,"Total":0}
引用次数: 0

Abstract

This Paper investigates how the internal delays of circuit breakers until the limitation of the fault current affect the selectivity of a low-voltage direct current (LVDC)-grid under short-circuit conditions. For conventional mechanical circuit breakers and future hybrid or solid-state devices, selectivity is, in line with AC practice, typically achieved by coordination based on their time-current trip characteristics. However, experimental short-circuit tests show that in DC-grids non-selective behavior can occur with high current slopes. To explain this effect, the delays until the fault current is effectively limited are analyzed. Based on this analysis, a critical time interval is identified and introduced as the reaction time gap. It describes the delay between the time when the circuit breaker should ideally trip immediately after detecting the fault and the time when it actually limits the current. To represent this behavior within conventional time–current characteristic curves, a measurement method for determining the relevant time intervals is proposed. A measurement-based study on several commercially available mechanical circuit breakers reveals the characteristics of short-circuit detection and current limitation, thereby confirming the existence of the reaction time gap and the resulting constraint on achievable selectivity. Possible countermeasures to overcome this reaction time gap relating to the behavior of the grid and the circuit breaker are outlined. Finally, the results and their implications for the design and protection coordination of DC-grids are discussed.
保护装置的延迟及其对选择性的影响:反应时间间隙
本文研究了短路条件下断路器在故障电流限制前的内部延迟对低压直流电网选择性的影响。对于传统的机械断路器和未来的混合或固态设备,选择性符合交流实践,通常通过基于其时间电流脱扣特性的协调来实现。然而,实验短路试验表明,在直流电网中,当电流斜率较大时,会出现非选择性行为。为了解释这种影响,分析了故障电流有效限制之前的延迟。在此基础上,确定了一个临界时间间隔,并将其作为反应时间间隙。它描述了断路器在检测到故障后理想情况下应该立即跳闸的时间与实际限制电流的时间之间的延迟。为了在传统的时间-电流特性曲线中表示这种行为,提出了一种确定相关时间间隔的测量方法。对几种市售机械断路器的基于测量的研究揭示了短路检测和电流限制的特性,从而证实了反应时间间隙的存在以及由此产生的对可实现选择性的约束。概述了克服与电网和断路器的行为有关的反应时间差距的可能对策。最后,讨论了研究结果及其对直流电网设计和保护协调的启示。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
CiteScore
8.60
自引率
0.00%
发文量
0
审稿时长
8 weeks
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书