Enhancing signal integrity and reactor power measurement in BTRR using line driver

Measurement: Energy Pub Date : 2026-03-01 Epub Date: 2026-03-04 DOI:10.1016/j.meaene.2026.100092
Md. Sayed Hossain
{"title":"Enhancing signal integrity and reactor power measurement in BTRR using line driver","authors":"Md. Sayed Hossain","doi":"10.1016/j.meaene.2026.100092","DOIUrl":null,"url":null,"abstract":"<div><div>The performance of the Bangladesh Atomic Energy Commission (BAEC) TRIGA Research Reactor (BTRR) was significantly improved by addressing signal integrity issues related to the NLW-1000 logarithmic power channel. The PA-1000 signal, which suffered from strength loss due to the unavoidable transmission line distance, was restored by installing a line driver between the PA-1000 and NLW-1000. Therefore, reactor power and period are visualized in the console in logarithmic scale from the well-acquisition of both pulse count and current signals. By addressing another wiring anomaly, the in activeness of the optocouplers in the FC-ISO-D and FC-ISO-C was resolved, a prestart checklist was performed, and it was found that the apparent “count rate low” failure arose from a mis-specified HMI message condition while the core logic correctly passed the test so further corrective action is needed for the HMI message. Presently, the BTRR functions up to 3MW<sub>th</sub> and the power is displayed in the CSC monitor. According to the user demand, the signal integrity is sufficiently enhanced and there is no error within the DACS &amp; CSC. Intermediate circuitry between the PA-1000 and logarithmic module can be omitted in the upcoming advanced logarithmic power monitoring channel to get better performance. The present study underscores the efficacy of signal enhancement methodologies in elevating reactor functionality and delineates a trajectory for sustained progress in nuclear research infrastructure.</div></div>","PeriodicalId":100897,"journal":{"name":"Measurement: Energy","volume":"9 ","pages":"Article 100092"},"PeriodicalIF":0.0000,"publicationDate":"2026-03-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Measurement: Energy","FirstCategoryId":"1085","ListUrlMain":"https://www.sciencedirect.com/science/article/pii/S2950345026000084","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"2026/3/4 0:00:00","PubModel":"Epub","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

The performance of the Bangladesh Atomic Energy Commission (BAEC) TRIGA Research Reactor (BTRR) was significantly improved by addressing signal integrity issues related to the NLW-1000 logarithmic power channel. The PA-1000 signal, which suffered from strength loss due to the unavoidable transmission line distance, was restored by installing a line driver between the PA-1000 and NLW-1000. Therefore, reactor power and period are visualized in the console in logarithmic scale from the well-acquisition of both pulse count and current signals. By addressing another wiring anomaly, the in activeness of the optocouplers in the FC-ISO-D and FC-ISO-C was resolved, a prestart checklist was performed, and it was found that the apparent “count rate low” failure arose from a mis-specified HMI message condition while the core logic correctly passed the test so further corrective action is needed for the HMI message. Presently, the BTRR functions up to 3MWth and the power is displayed in the CSC monitor. According to the user demand, the signal integrity is sufficiently enhanced and there is no error within the DACS & CSC. Intermediate circuitry between the PA-1000 and logarithmic module can be omitted in the upcoming advanced logarithmic power monitoring channel to get better performance. The present study underscores the efficacy of signal enhancement methodologies in elevating reactor functionality and delineates a trajectory for sustained progress in nuclear research infrastructure.
利用线路驱动器增强BTRR信号完整性和电抗器功率测量
孟加拉国原子能委员会(BAEC) TRIGA研究堆(BTRR)的性能通过解决与NLW-1000对数功率通道相关的信号完整性问题得到了显著改善。由于不可避免的传输线距离,PA-1000信号受到了强度损失,通过在PA-1000和NLW-1000之间安装线路驱动器,恢复了信号。因此,从脉冲计数和电流信号的良好采集中,电抗器功率和周期在控制台中以对数尺度显示。通过解决另一个布线异常,FC-ISO-D和FC-ISO-C中的光耦合器的活跃度得到了解决,执行了一个预启动检查表,发现明显的“计数率低”故障是由错误指定的HMI消息条件引起的,而核心逻辑正确地通过了测试,因此需要对HMI消息采取进一步的纠正措施。目前,BTRR的工作功率高达3mw,功率显示在CSC监视器上。根据用户需求,充分提高了信号的完整性,使DACS CSC内无误差。在即将推出的高级对数功率监测信道中,可以省去PA-1000与对数模块之间的中间电路,以获得更好的性能。本研究强调了信号增强方法在提高反应堆功能方面的有效性,并描绘了核研究基础设施持续进步的轨迹。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书