Monitoring and Control of Water Chemistry in the Power Unit Turbine Generator Water Cooling System

IF 1.3 Q4 ENERGY & FUELS
A. B. Larin, B. M. Larin, M. P. Savinov, E. G. Ukhalova
{"title":"Monitoring and Control of Water Chemistry in the Power Unit Turbine Generator Water Cooling System","authors":"A. B. Larin,&nbsp;B. M. Larin,&nbsp;M. P. Savinov,&nbsp;E. G. Ukhalova","doi":"10.1134/S0040601525700715","DOIUrl":null,"url":null,"abstract":"<p>Electrical conductivity, pH, and oxygen concentration, all continuously measured in circulation water, are the key water chemistry (WC) parameters monitored in a power unit turbine generator water cooling system. With a shift for the use of water cooling in the turbine generator systems at thermal power plants (TPP) and for designing of such systems for turbine generators of the T3V-1200-2AU3 series at NPPs, problems were encountered in meeting the circulation water quality standards and in WC control. The article presents a method for determining by calculation the standardized values of electrical conductivity and pH in metering NaOH in a circulating cooling system (CCS) depending on these indicators in makeup water (water medium with low buffering capacity). The turbine generator water cooling systems serve for intense heat removal from the stator (and rotor) windings and are widely used in the power units at TPPs and NPPs. The cooling (circulation) water quality is standardized with respect to several indicators, the main ones of which are electrical conductivity and pH. In view of quite stringent standards on electrical conductivity, especially for the turbine generator rotor cooling system (below 1.43 μS/cm), there is nothing to do but use deeply demineralized weakly acidic water (рН &lt; 7.0), and it is not permitted to use ammonia. For the acidity to be neutralized with NaOH solution, very precise controlled metering is required: with an insufficient quantity of NaOH, the рН will be below 6.5 (the lower limit), and with an excessive quantity of NaOH, the pH value will exceed 9.0, which is the upper permissible limit for the CCS. A mathematical model of ionic equilibria in the CCS circulation water is constructed and solved. With NaOH solution metered within the range of permissible values, the electrical conductivity and pH value adjustment boundaries are determined depending on the source and makeup water quality. An author’s certificate for a software product has been received. Given the existing makeup water quality and unchanged CCS process circuit arrangement, the performed study makes it possible to recommend installing an automated system for metering NaOH solution into circulation water based on the prescribed electrical conductivity value.</p>","PeriodicalId":799,"journal":{"name":"Thermal Engineering","volume":"73 1","pages":"62 - 70"},"PeriodicalIF":1.3000,"publicationDate":"2026-03-11","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Thermal Engineering","FirstCategoryId":"1085","ListUrlMain":"https://link.springer.com/article/10.1134/S0040601525700715","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q4","JCRName":"ENERGY & FUELS","Score":null,"Total":0}
引用次数: 0

Abstract

Electrical conductivity, pH, and oxygen concentration, all continuously measured in circulation water, are the key water chemistry (WC) parameters monitored in a power unit turbine generator water cooling system. With a shift for the use of water cooling in the turbine generator systems at thermal power plants (TPP) and for designing of such systems for turbine generators of the T3V-1200-2AU3 series at NPPs, problems were encountered in meeting the circulation water quality standards and in WC control. The article presents a method for determining by calculation the standardized values of electrical conductivity and pH in metering NaOH in a circulating cooling system (CCS) depending on these indicators in makeup water (water medium with low buffering capacity). The turbine generator water cooling systems serve for intense heat removal from the stator (and rotor) windings and are widely used in the power units at TPPs and NPPs. The cooling (circulation) water quality is standardized with respect to several indicators, the main ones of which are electrical conductivity and pH. In view of quite stringent standards on electrical conductivity, especially for the turbine generator rotor cooling system (below 1.43 μS/cm), there is nothing to do but use deeply demineralized weakly acidic water (рН < 7.0), and it is not permitted to use ammonia. For the acidity to be neutralized with NaOH solution, very precise controlled metering is required: with an insufficient quantity of NaOH, the рН will be below 6.5 (the lower limit), and with an excessive quantity of NaOH, the pH value will exceed 9.0, which is the upper permissible limit for the CCS. A mathematical model of ionic equilibria in the CCS circulation water is constructed and solved. With NaOH solution metered within the range of permissible values, the electrical conductivity and pH value adjustment boundaries are determined depending on the source and makeup water quality. An author’s certificate for a software product has been received. Given the existing makeup water quality and unchanged CCS process circuit arrangement, the performed study makes it possible to recommend installing an automated system for metering NaOH solution into circulation water based on the prescribed electrical conductivity value.

Abstract Image

发电机组汽轮发电机组水冷却系统水化学监测与控制
导电性、pH值和氧浓度是发电机组水冷却系统监测的关键水化学参数,它们都是在循环水中连续测量的。随着火电厂水冷发电机组系统(TPP)和核电站T3V-1200-2AU3系列水冷发电机组系统设计的转变,在满足循环水质量标准和WC控制方面遇到了问题。本文提出了一种通过计算确定循环冷却系统(CCS)中计量NaOH时电导率和pH的标准值的方法,该方法取决于补充水(具有低缓冲能力的水介质)中的这些指标。水轮发电机水冷却系统用于从定子(和转子)绕组中除去强烈的热量,并广泛应用于tpp和npp的动力装置中。冷却(循环)水质在几个指标上进行了标准化,主要是电导率和ph。鉴于电导率标准相当严格,特别是汽轮发电机转子冷却系统(低于1.43 μS/cm),只能使用深度去矿弱酸性水(рН < 7.0),不允许使用氨水。要用NaOH溶液中和酸度,需要非常精确的控制计量:NaOH用量不足时,рН会低于6.5(下限),NaOH用量过多时,pH值会超过9.0,这是CCS的允许上限。建立并求解了CCS循环水中离子平衡的数学模型。在允许的范围内测量NaOH溶液,电导率和pH值调整边界取决于水源和补给水质。已收到软件产品的作者证书。鉴于现有的补给水质和未改变的CCS工艺电路安排,本研究可以建议安装一个自动化系统,根据规定的电导率值对循环水中的NaOH溶液进行计量。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
CiteScore
1.30
自引率
20.00%
发文量
94
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书