Experimental study on space heating performance of PVT-air dual heat source direct expansion heat pump system based on micro heat pipe arrays

IF 9.1 1区 工程技术 Q1 ENERGY & FUELS
Renewable Energy Pub Date : 2026-04-15 Epub Date: 2026-02-02 DOI:10.1016/j.renene.2026.125383
Ze Bai , Yaohua Zhao , Zhenhua Quan , Haibo Ren , Chenyang Du
{"title":"Experimental study on space heating performance of PVT-air dual heat source direct expansion heat pump system based on micro heat pipe arrays","authors":"Ze Bai ,&nbsp;Yaohua Zhao ,&nbsp;Zhenhua Quan ,&nbsp;Haibo Ren ,&nbsp;Chenyang Du","doi":"10.1016/j.renene.2026.125383","DOIUrl":null,"url":null,"abstract":"<div><div>To address the growing demand for efficient and renewable heating, a novel dual source direct expansion PVT-air heat pump system integrating a PVT-air evaporator based on micro heat pipe arrays is proposed. This design overcomes limitations of conventional flat-plate PVT evaporators, such as high-pressure loss, low solar energy utilization and unstable system energy supply. The system was experimentally evaluated under winter space heating conditions. Results showed a maximum thermal efficiency of 35%, power generation efficiency of 17%, <em>COP</em> of 3.52, and exergy efficiency of 21% under average solar irradiance of 654 W/m<sup>2</sup>, ambient temperature of 5.1 °C, and wind speed of 2.6 m/s. <em>COP</em> increased by up to 12.5% and exergy efficiency by 43.4% per 100 W/m<sup>2</sup> rise in solar irradiance, while a 5 K rise in load water temperature reduced <em>COP</em> by 8.4% and exergy efficiency by 4.7%. The system demonstrated stable switching between solar and air heat sources. Compared to the conventional tube-and-sheet PVT direct expansion heat pump, the proposed system achieved 4.5%, 33.5%, and 20% improvements in <em>COP</em>, power generation efficiency, and <em>COP</em><sub><em>PVT</em></sub>, respectively. The dimensionless pressure loss of the PVT-air evaporator based on micro heat pipe arrays was also 87% lower than that of the fin-tube heat exchanger. These results confirm the system's excellent performance, reliability, and potential for practical heating applications.</div></div>","PeriodicalId":419,"journal":{"name":"Renewable Energy","volume":"262 ","pages":"Article 125383"},"PeriodicalIF":9.1000,"publicationDate":"2026-04-15","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Renewable Energy","FirstCategoryId":"5","ListUrlMain":"https://www.sciencedirect.com/science/article/pii/S0960148126002089","RegionNum":1,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"2026/2/2 0:00:00","PubModel":"Epub","JCR":"Q1","JCRName":"ENERGY & FUELS","Score":null,"Total":0}
引用次数: 0

Abstract

To address the growing demand for efficient and renewable heating, a novel dual source direct expansion PVT-air heat pump system integrating a PVT-air evaporator based on micro heat pipe arrays is proposed. This design overcomes limitations of conventional flat-plate PVT evaporators, such as high-pressure loss, low solar energy utilization and unstable system energy supply. The system was experimentally evaluated under winter space heating conditions. Results showed a maximum thermal efficiency of 35%, power generation efficiency of 17%, COP of 3.52, and exergy efficiency of 21% under average solar irradiance of 654 W/m2, ambient temperature of 5.1 °C, and wind speed of 2.6 m/s. COP increased by up to 12.5% and exergy efficiency by 43.4% per 100 W/m2 rise in solar irradiance, while a 5 K rise in load water temperature reduced COP by 8.4% and exergy efficiency by 4.7%. The system demonstrated stable switching between solar and air heat sources. Compared to the conventional tube-and-sheet PVT direct expansion heat pump, the proposed system achieved 4.5%, 33.5%, and 20% improvements in COP, power generation efficiency, and COPPVT, respectively. The dimensionless pressure loss of the PVT-air evaporator based on micro heat pipe arrays was also 87% lower than that of the fin-tube heat exchanger. These results confirm the system's excellent performance, reliability, and potential for practical heating applications.
基于微热管阵列的pvt -空气双热源直扩热泵系统空间采暖性能实验研究
为了满足日益增长的高效可再生供暖需求,提出了一种新型的双源直接膨胀式pvt -空气热泵系统,该系统集成了基于微热管阵列的pvt -空气蒸发器。本设计克服了传统平板PVT蒸发器高压损耗、太阳能利用率低、系统供能不稳定等缺点。在冬季空间采暖条件下对该系统进行了实验评估。结果表明,在平均太阳辐照度为654 W/m2、环境温度为5.1℃、风速为2.6 m/s的条件下,该电站最大热效率为35%,发电效率为17%,COP为3.52,火用效率为21%。太阳辐照度每增加100 W/m2, COP提高12.5%,火用效率提高43.4%,而负荷水温每增加5 K, COP降低8.4%,火用效率降低4.7%。该系统在太阳能和空气热源之间进行了稳定的切换。与传统管板式PVT直接膨胀热泵相比,该系统的COP、发电效率和COPPVT分别提高了4.5%、33.5%和20%。基于微热管阵列的pvt -空气蒸发器的无因次压力损失也比翅片管换热器低87%。这些结果证实了该系统的优异性能、可靠性和实际加热应用的潜力。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
Renewable Energy
Renewable Energy 工程技术-能源与燃料
CiteScore
18.40
自引率
9.20%
发文量
1955
审稿时长
6.6 months
期刊介绍: Renewable Energy journal is dedicated to advancing knowledge and disseminating insights on various topics and technologies within renewable energy systems and components. Our mission is to support researchers, engineers, economists, manufacturers, NGOs, associations, and societies in staying updated on new developments in their respective fields and applying alternative energy solutions to current practices. As an international, multidisciplinary journal in renewable energy engineering and research, we strive to be a premier peer-reviewed platform and a trusted source of original research and reviews in the field of renewable energy. Join us in our endeavor to drive innovation and progress in sustainable energy solutions.
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书