Xiangyu Han, Fei Yang, Yili Chen, Yunqi Wang, Chenle Zhai, Xuliang Zhao, Zhaowei Diao, Yi Wu, Mingzhe Rong
{"title":"Post-Arc Transient Dielectric Recovery Characteristics of Vacuum Interrupter in the Large-Capacity Generator Circuit Breaker","authors":"Xiangyu Han, Fei Yang, Yili Chen, Yunqi Wang, Chenle Zhai, Xuliang Zhao, Zhaowei Diao, Yi Wu, Mingzhe Rong","doi":"10.1049/hve2.70153","DOIUrl":null,"url":null,"abstract":"<p>Large-capacity generator circuit breaker (GCB) based on vacuum interrupter technology is the key power equipment to ensure the safe operation of the power system. When the short-circuit current was forced to cross zero, the large-capacity GCB was difficult to generate a zero-voltage environment through freewheeling, the vacuum interrupter (VI) would immediately withstand the transient recovery voltage (TRV), and there was a lack of research on the post-arc transient dielectric recovery characteristics. First, an experimental platform for transient dielectric recovery characteristics was built, which was capable of generating TRV quickly after current-zero with the voltage rise rate (d<i>u</i>/d<i>t</i>) of about 20 kV/μs. The large current post-arc dielectric recovery tolerance experiments with the peak current of 100 kA were carried out, and the post-arc tolerance process was divided into three modes according to the TRV waveform. The influence of arcing time, residual current and current change rate (d<i>i</i>/d<i>t</i>) on the transient dielectric recovery characteristics was investigated. Next, we found that the transient dielectric recovery of VI under the same conditions was characterised by dispersion. The influence mechanisms of ‘active regulation of the vacuum arc’ and ‘consistency of the arcing process’ on the dispersion of the transient dielectric recovery were studied in detail. The ‘safety boundary’ consisting of the minimum of dielectric recovery strength was analysed, and the optimal arcing control strategy was proposed. The design basis of the circuit breaker was obtained. Finally, a prototype GCB based on vacuum six-breakers in parallel and current transfer was developed, and the large short-circuit current had been successfully broken, which verified the post-arc transient breaking reliability of the VI. The conclusions will lay the foundation for the engineering application of high-capacity GCB.</p>","PeriodicalId":48649,"journal":{"name":"High Voltage","volume":"11 4","pages":"999-1010"},"PeriodicalIF":5.7000,"publicationDate":"2026-08-31","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"https://onlinelibrary.wiley.com/doi/epdf/10.1049/hve2.70153","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"High Voltage","FirstCategoryId":"5","ListUrlMain":"https://onlinelibrary.wiley.com/doi/10.1049/hve2.70153","RegionNum":2,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"2026/2/11 0:00:00","PubModel":"Epub","JCR":"Q1","JCRName":"ENGINEERING, ELECTRICAL & ELECTRONIC","Score":null,"Total":0}
引用次数: 0
Abstract
Large-capacity generator circuit breaker (GCB) based on vacuum interrupter technology is the key power equipment to ensure the safe operation of the power system. When the short-circuit current was forced to cross zero, the large-capacity GCB was difficult to generate a zero-voltage environment through freewheeling, the vacuum interrupter (VI) would immediately withstand the transient recovery voltage (TRV), and there was a lack of research on the post-arc transient dielectric recovery characteristics. First, an experimental platform for transient dielectric recovery characteristics was built, which was capable of generating TRV quickly after current-zero with the voltage rise rate (du/dt) of about 20 kV/μs. The large current post-arc dielectric recovery tolerance experiments with the peak current of 100 kA were carried out, and the post-arc tolerance process was divided into three modes according to the TRV waveform. The influence of arcing time, residual current and current change rate (di/dt) on the transient dielectric recovery characteristics was investigated. Next, we found that the transient dielectric recovery of VI under the same conditions was characterised by dispersion. The influence mechanisms of ‘active regulation of the vacuum arc’ and ‘consistency of the arcing process’ on the dispersion of the transient dielectric recovery were studied in detail. The ‘safety boundary’ consisting of the minimum of dielectric recovery strength was analysed, and the optimal arcing control strategy was proposed. The design basis of the circuit breaker was obtained. Finally, a prototype GCB based on vacuum six-breakers in parallel and current transfer was developed, and the large short-circuit current had been successfully broken, which verified the post-arc transient breaking reliability of the VI. The conclusions will lay the foundation for the engineering application of high-capacity GCB.
High VoltageEnergy-Energy Engineering and Power Technology
CiteScore
9.60
自引率
27.30%
发文量
97
审稿时长
21 weeks
期刊介绍:
High Voltage aims to attract original research papers and review articles. The scope covers high-voltage power engineering and high voltage applications, including experimental, computational (including simulation and modelling) and theoretical studies, which include:
Electrical Insulation
● Outdoor, indoor, solid, liquid and gas insulation
● Transient voltages and overvoltage protection
● Nano-dielectrics and new insulation materials
● Condition monitoring and maintenance
Discharge and plasmas, pulsed power
● Electrical discharge, plasma generation and applications
● Interactions of plasma with surfaces
● Pulsed power science and technology
High-field effects
● Computation, measurements of Intensive Electromagnetic Field
● Electromagnetic compatibility
● Biomedical effects
● Environmental effects and protection
High Voltage Engineering
● Design problems, testing and measuring techniques
● Equipment development and asset management
● Smart Grid, live line working
● AC/DC power electronics
● UHV power transmission
Special Issues. Call for papers:
Interface Charging Phenomena for Dielectric Materials - https://digital-library.theiet.org/files/HVE_CFP_ICP.pdf
Emerging Materials For High Voltage Applications - https://digital-library.theiet.org/files/HVE_CFP_EMHVA.pdf