Study on combustion characteristics of cables with spacing arrangement under different external radiation conditions

IF 3.4 Q1 PUBLIC, ENVIRONMENTAL & OCCUPATIONAL HEALTH
安全科学与韧性(英文) Pub Date : 2026-06-01 Epub Date: 2025-09-06 DOI:10.1016/j.jnlssr.2025.100255
Tong Xu , Xiaole Dai , Kai Wang , Fazheng Chong , Fengju Shang , Chang Liu
{"title":"Study on combustion characteristics of cables with spacing arrangement under different external radiation conditions","authors":"Tong Xu ,&nbsp;Xiaole Dai ,&nbsp;Kai Wang ,&nbsp;Fazheng Chong ,&nbsp;Fengju Shang ,&nbsp;Chang Liu","doi":"10.1016/j.jnlssr.2025.100255","DOIUrl":null,"url":null,"abstract":"<div><div>A series of experiments was conducted to explore the influence of cable spacing on combustion characteristics in real cable installation, considering various external radiation intensities (30, 50 kW/m<sup>2</sup>) and cable spacings (0, 2.5, 5 cm). A comparative analysis of the combustion characteristics (such as heat release rate (HRR), combustion gas, and mass loss) was conducted, and the HRR calculation for cables that were not fully filled in the sample tray was revised as well. It could be found that with the increasing radiation intensities, the peak concentrations of CO and CO₂ increased (O₂ concentration decreased), and the interval between the two peaks shortened. The HRR curves of cables with different spacings all presented two peaks under two radiation intensities. The max-peak HRR occurs at <em>D<sub>d</sub></em> = 2.5 cm, and the double max-peak HRRs are 582 kW/m<sup>2</sup> and 407 kW/m<sup>2</sup> under radiation intensities of 50 kW/m<sup>2</sup> and 35 kW/m<sup>2</sup>, respectively. This is because when <em>D<sub>d</sub></em> = 0 cm, the thermal feedback effect between cables is relatively enhanced, while the air entrainment between the cables is weakened. When <em>D<sub>d</sub></em> = 5 cm, the thermal feedback effect is weakened. When <em>D<sub>d</sub></em> = 2.5 cm, both the air entrainment and the thermal feedback are strengthened, and the peak HRR occurs. The above results could provide data to support fire safety design and the emergency response to cable laying.</div></div>","PeriodicalId":62710,"journal":{"name":"安全科学与韧性(英文)","volume":"7 2","pages":"Article 100255"},"PeriodicalIF":3.4000,"publicationDate":"2026-06-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"安全科学与韧性(英文)","FirstCategoryId":"1087","ListUrlMain":"https://www.sciencedirect.com/science/article/pii/S2666449625000891","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"2025/9/6 0:00:00","PubModel":"Epub","JCR":"Q1","JCRName":"PUBLIC, ENVIRONMENTAL & OCCUPATIONAL HEALTH","Score":null,"Total":0}
引用次数: 0

Abstract

A series of experiments was conducted to explore the influence of cable spacing on combustion characteristics in real cable installation, considering various external radiation intensities (30, 50 kW/m2) and cable spacings (0, 2.5, 5 cm). A comparative analysis of the combustion characteristics (such as heat release rate (HRR), combustion gas, and mass loss) was conducted, and the HRR calculation for cables that were not fully filled in the sample tray was revised as well. It could be found that with the increasing radiation intensities, the peak concentrations of CO and CO₂ increased (O₂ concentration decreased), and the interval between the two peaks shortened. The HRR curves of cables with different spacings all presented two peaks under two radiation intensities. The max-peak HRR occurs at Dd = 2.5 cm, and the double max-peak HRRs are 582 kW/m2 and 407 kW/m2 under radiation intensities of 50 kW/m2 and 35 kW/m2, respectively. This is because when Dd = 0 cm, the thermal feedback effect between cables is relatively enhanced, while the air entrainment between the cables is weakened. When Dd = 5 cm, the thermal feedback effect is weakened. When Dd = 2.5 cm, both the air entrainment and the thermal feedback are strengthened, and the peak HRR occurs. The above results could provide data to support fire safety design and the emergency response to cable laying.
不同外辐射条件下布置间距电缆燃烧特性研究
在实际电缆安装中,考虑不同的外辐射强度(30、50 kW/m2)和电缆间距(0、2.5、5 cm),进行了一系列实验,探讨了电缆间距对燃烧特性的影响。对比分析了燃烧特性(热释放率(HRR)、燃烧气体、质量损失等),并修正了样品盘内未完全填充电缆的HRR计算。可以发现,随着辐射强度的增加,CO和CO₂的峰值浓度增加(O₂浓度降低),两峰之间的间隔缩短。不同间距电缆的HRR曲线在两种辐射强度下均呈现两个峰值。辐射强度为50 kW/m2和35 kW/m2时,双峰HRR分别为582 kW/m2和407 kW/m2。这是因为当Dd = 0 cm时,电缆间的热反馈效应相对增强,而电缆间的夹带气流减弱。当Dd = 5 cm时,热反馈效应减弱。当Dd = 2.5 cm时,夹带空气和热反馈都增强,HRR出现峰值。上述结果可为电缆敷设的消防安全设计和应急响应提供数据支持。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
安全科学与韧性(英文)
安全科学与韧性(英文) Management Science and Operations Research, Safety, Risk, Reliability and Quality, Safety Research
CiteScore
8.70
自引率
0.00%
发文量
0
审稿时长
72 days
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书