{"title":"Stability Analysis of Grid-Strengthening Geared Direct Grid-Connected Dual-Speed Slip-Synchronous Wind Turbines","authors":"Ryno Gerber;Maarten Jan Kamper","doi":"10.1109/OJIA.2025.3636406","DOIUrl":null,"url":null,"abstract":"With the recent proliferation in penetration levels of converter-based grid-connected wind turbine systems, a decrease in grid strength has been observed. In pursuit of improving grid strength and power quality, the newly proposed slip-synchronous wind turbine system (SS-WTS) is employed, whereby a synchronous generator (SG) is directly connected to the grid and damping is provided through the use of a slip permanent magnet coupling (S-PMC). However, the proper operation of the turbine drivetrain has yet to be fully investigated under transient loading conditions. This article examines various drivetrain topologies to ensure the optimal placement of the S-PMC for stability and load mitigation. From the stability analysis, various S-PMC slip ranges, SG synchronous reactance values and inertia ratios between the turbine hub and SG rotor were evaluated. This led to more thorough design criteria being established to ensure the proper stability of the SS-WTS under transient conditions, with specific regard to low-voltage ride-throughs (LVRTs). This article found that, although connecting the SS-WTS to the grid is a feasible solution to improve grid strength, instability is observed under certain transient conditions, such as LVRTs. It was noted that direct-drive SS-WTSs are less susceptible to transient instability, as they possess a far larger inertia ratio between the wind turbine and the SG rotor. This article found the optimal slip and synchronous reactance for all SS-WTS variants, where stability under all transient conditions is dependent on the turbine’s rated torque, the turbine’s inertia and the SG inertia. This made it possible to formulate adequate design criteria based on the application and capability needs of the SS-WTS.","PeriodicalId":100629,"journal":{"name":"IEEE Open Journal of Industry Applications","volume":"7 ","pages":"3-23"},"PeriodicalIF":3.8000,"publicationDate":"2025-11-24","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"https://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=11264835","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"IEEE Open Journal of Industry Applications","FirstCategoryId":"1085","ListUrlMain":"https://ieeexplore.ieee.org/document/11264835/","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q1","JCRName":"ENGINEERING, ELECTRICAL & ELECTRONIC","Score":null,"Total":0}
引用次数: 0

Abstract

With the recent proliferation in penetration levels of converter-based grid-connected wind turbine systems, a decrease in grid strength has been observed. In pursuit of improving grid strength and power quality, the newly proposed slip-synchronous wind turbine system (SS-WTS) is employed, whereby a synchronous generator (SG) is directly connected to the grid and damping is provided through the use of a slip permanent magnet coupling (S-PMC). However, the proper operation of the turbine drivetrain has yet to be fully investigated under transient loading conditions. This article examines various drivetrain topologies to ensure the optimal placement of the S-PMC for stability and load mitigation. From the stability analysis, various S-PMC slip ranges, SG synchronous reactance values and inertia ratios between the turbine hub and SG rotor were evaluated. This led to more thorough design criteria being established to ensure the proper stability of the SS-WTS under transient conditions, with specific regard to low-voltage ride-throughs (LVRTs). This article found that, although connecting the SS-WTS to the grid is a feasible solution to improve grid strength, instability is observed under certain transient conditions, such as LVRTs. It was noted that direct-drive SS-WTSs are less susceptible to transient instability, as they possess a far larger inertia ratio between the wind turbine and the SG rotor. This article found the optimal slip and synchronous reactance for all SS-WTS variants, where stability under all transient conditions is dependent on the turbine’s rated torque, the turbine’s inertia and the SG inertia. This made it possible to formulate adequate design criteria based on the application and capability needs of the SS-WTS.
并网加固齿轮直连双速滑移同步风力发电机组稳定性分析
随着最近以变流器为基础的并网风力发电系统的渗透水平的激增,电网强度已经下降。为了提高电网的强度和电能质量,采用了新提出的滑移同步风力发电系统(SS-WTS),其中同步发电机(SG)直接连接到电网,并通过使用滑移永磁耦合(S-PMC)提供阻尼。然而,涡轮传动系统在瞬态负载条件下的正常运行尚未得到充分的研究。本文研究了各种动力传动系统拓扑结构,以确保S-PMC的最佳位置,以实现稳定性和减轻负载。从稳定性分析出发,对S-PMC的滑移范围、SG同步电抗值以及轮毂与SG转子间的惯量比进行了评估。这导致了更彻底的设计标准的建立,以确保SS-WTS在瞬态条件下的适当稳定性,特别是在低压穿越(lvrt)方面。本文发现,虽然将SS-WTS接入电网是提高电网强度的可行方案,但在某些暂态条件下,如lvrt,会出现不稳定现象。值得注意的是,直接驱动的ss - wts不太容易受到瞬态不稳定的影响,因为它们在风力涡轮机和SG转子之间具有更大的惯性比。本文找到了所有SS-WTS变体的最佳滑移和同步电抗,其中所有瞬态条件下的稳定性取决于涡轮机的额定扭矩,涡轮机的惯性和SG惯性。这使得根据SS-WTS的应用和能力需求制定适当的设计标准成为可能。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
CiteScore
13.50
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书