Evaluation of the efficiency of a low voltage autotransformer

Measurement: Energy Pub Date : 2026-03-01 Epub Date: 2025-11-26 DOI:10.1016/j.meaene.2025.100080
Edwin Garabitos-Lara , José Miguel Mateo-Beltré , Jesús Manuel Silva-García
{"title":"Evaluation of the efficiency of a low voltage autotransformer","authors":"Edwin Garabitos-Lara ,&nbsp;José Miguel Mateo-Beltré ,&nbsp;Jesús Manuel Silva-García","doi":"10.1016/j.meaene.2025.100080","DOIUrl":null,"url":null,"abstract":"<div><div>In many developing countries, low-voltage autotransformers are commonly used in residential settings to compensate for persistent voltage irregularities in the electrical distribution network. Despite their widespread use, few studies have systematically evaluated their performance and efficiency under typical operating conditions. This study presents the design, construction, and experimental evaluation of a low-voltage autotransformer rated at 1580 VA. The design equations were derived from Faraday's Law, and the equivalent circuit parameters were obtained through open-circuit and short-circuit tests. The efficiency was measured using a power network analyzer under resistive and non-resistive loads and compared with values calculated analytically from the equivalent circuit. The study also incorporated uncertainty analysis in both experimental and analytical procedures. Results showed that the autotransformer reached an efficiency of 98.0 % under nominal load and exceeded 90.0 % efficiency at just 10.7 % of the demand coefficient. Furthermore, the all-day efficiency remained stable between 96.5 % and 96.8 % across real residential demand profiles, confirming consistent energy performance under variable load conditions. The differences between measured and calculated efficiencies were below 1 percentage point in all cases, and validation was confirmed using uncertainty propagation, mean absolute error (MAE), and root mean square error (RMSE). These findings reinforce the reliability of the analytical model and highlight the high efficiency of these devices as voltage-regulating elements when properly designed.</div></div>","PeriodicalId":100897,"journal":{"name":"Measurement: Energy","volume":"9 ","pages":"Article 100080"},"PeriodicalIF":0.0000,"publicationDate":"2026-03-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Measurement: Energy","FirstCategoryId":"1085","ListUrlMain":"https://www.sciencedirect.com/science/article/pii/S2950345025000478","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"2025/11/26 0:00:00","PubModel":"Epub","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

In many developing countries, low-voltage autotransformers are commonly used in residential settings to compensate for persistent voltage irregularities in the electrical distribution network. Despite their widespread use, few studies have systematically evaluated their performance and efficiency under typical operating conditions. This study presents the design, construction, and experimental evaluation of a low-voltage autotransformer rated at 1580 VA. The design equations were derived from Faraday's Law, and the equivalent circuit parameters were obtained through open-circuit and short-circuit tests. The efficiency was measured using a power network analyzer under resistive and non-resistive loads and compared with values calculated analytically from the equivalent circuit. The study also incorporated uncertainty analysis in both experimental and analytical procedures. Results showed that the autotransformer reached an efficiency of 98.0 % under nominal load and exceeded 90.0 % efficiency at just 10.7 % of the demand coefficient. Furthermore, the all-day efficiency remained stable between 96.5 % and 96.8 % across real residential demand profiles, confirming consistent energy performance under variable load conditions. The differences between measured and calculated efficiencies were below 1 percentage point in all cases, and validation was confirmed using uncertainty propagation, mean absolute error (MAE), and root mean square error (RMSE). These findings reinforce the reliability of the analytical model and highlight the high efficiency of these devices as voltage-regulating elements when properly designed.
一种低压自耦变压器的效率评价
在许多发展中国家,低压自耦变压器通常用于住宅环境,以补偿配电网络中持续的电压不正常。尽管它们被广泛使用,但很少有研究系统地评估它们在典型操作条件下的性能和效率。本文介绍了一种额定电压为1580 VA的低压自耦变压器的设计、构造和实验评估,根据法拉第定律推导了设计方程,并通过开路和短路试验获得了等效电路参数。利用电网分析仪在电阻性和非电阻性负载下测量了效率,并与等效电路的解析计算值进行了比较。该研究还在实验和分析过程中纳入了不确定度分析。结果表明,自耦变压器在额定负载下效率达到98.0%,在需求系数仅为10.7%时效率超过90%。此外,在实际住宅需求曲线中,全天效率保持稳定在96.5%至96.8%之间,确认了在可变负载条件下的一致能源性能。在所有情况下,测量和计算效率之间的差异都低于1个百分点,并且使用不确定性传播、平均绝对误差(MAE)和均方根误差(RMSE)来确认有效性。这些发现加强了分析模型的可靠性,并突出了这些器件在适当设计时作为电压调节元件的高效率。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书