{"title":"Harmonic Blocking Based Differential Relay Protection Considering Neutral Stray Currents from DC Metro Systems","authors":"Haoran Fan;Sheng Lin;Aimin Wang;Qi Zhou;Hongbo Cheng","doi":"10.35833/MPCE.2024.000440","DOIUrl":null,"url":null,"abstract":"Stray currents from DC metro systems intrude into the grounded neutrals of large power transformers, posing a major threat to the differential relay protection of transformer. In this paper, the performance of harmonic blocking based differential relay protection considering neutral stray currents (NSCs) from DC metro systems is thoroughly investigated. The findings reveal that relays may fail to clear internal faults in some scenarios because they are blocked due to NSC-induced harmonic currents. To improve the reliability of differential relay protection, a method for preventing incorrect operation is proposed using a skewness-based criterion to detect the presence of NSCs. Then, the relay is unblocked when an internal fault is simultaneously detected by the novel internal fault detection block. The proposed method is resistant to current transformer saturation and accounts for NSC fluctuations. Various time-domain simulations conducted in PSCAD/EMTDC verify the effectiveness of the proposed method.","PeriodicalId":51326,"journal":{"name":"Journal of Modern Power Systems and Clean Energy","volume":"13 5","pages":"1689-1700"},"PeriodicalIF":6.1000,"publicationDate":"2025-03-27","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"https://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=10944545","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Journal of Modern Power Systems and Clean Energy","FirstCategoryId":"5","ListUrlMain":"https://ieeexplore.ieee.org/document/10944545/","RegionNum":1,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q1","JCRName":"ENGINEERING, ELECTRICAL & ELECTRONIC","Score":null,"Total":0}
引用次数: 0
Abstract
Stray currents from DC metro systems intrude into the grounded neutrals of large power transformers, posing a major threat to the differential relay protection of transformer. In this paper, the performance of harmonic blocking based differential relay protection considering neutral stray currents (NSCs) from DC metro systems is thoroughly investigated. The findings reveal that relays may fail to clear internal faults in some scenarios because they are blocked due to NSC-induced harmonic currents. To improve the reliability of differential relay protection, a method for preventing incorrect operation is proposed using a skewness-based criterion to detect the presence of NSCs. Then, the relay is unblocked when an internal fault is simultaneously detected by the novel internal fault detection block. The proposed method is resistant to current transformer saturation and accounts for NSC fluctuations. Various time-domain simulations conducted in PSCAD/EMTDC verify the effectiveness of the proposed method.
期刊介绍:
Journal of Modern Power Systems and Clean Energy (MPCE), commencing from June, 2013, is a newly established, peer-reviewed and quarterly published journal in English. It is the first international power engineering journal originated in mainland China. MPCE publishes original papers, short letters and review articles in the field of modern power systems with focus on smart grid technology and renewable energy integration, etc.