Cheng-Min Yang , M. Muneeshwaran , Yifeng Hu , Gustavo Pottker , Samuel F. Yana Motta
{"title":"Pool boiling heat transfer evaluation of next-generation dielectric fluid: Opteon™ 2P50","authors":"Cheng-Min Yang , M. Muneeshwaran , Yifeng Hu , Gustavo Pottker , Samuel F. Yana Motta","doi":"10.1016/j.ijft.2025.101379","DOIUrl":null,"url":null,"abstract":"<div><div>The growing use of artificial intelligence has led to heavy thermal loads and high heat dissipation rates in data centers. Conventional air-cooled technologies are not able to fulfill these requirements. To overcome these challenges, two-phase immersion cooling (2PIC) has emerged as one of the leading technologies for high power-density chips. 2PIC increases the heat dissipation rate and efficiency of the system while reducing the footprint of the cooling equipment. A fluid with adequate dielectric properties, a suitable normal boiling temperature to maintain chip temperatures, and good material compatibility, is desired for 2PIC system. In this study, the pool boiling heat transfer of a new developmental dielectric fluid, Opteon™ 2P50, was experimentally investigated. The heat transfer coefficients at various heat fluxes (20–150 kW/m<sup>2</sup>) and the critical heat flux were measured using a smooth aluminum surface. Compared with HFE-7100, Opteon™ 2P50 shows higher heat transfer coefficient (up to 59% higher) and a slightly lower value of critical heat flux (around 5.9% lower). The modified Cooper correlation with the optimized leading constant resulted in reliable prediction accuracy with a 5.3% mean absolute error percentage. Overall, these results indicate that the new dielectric fluid provides similar thermal performance to some legacy fluids.</div></div>","PeriodicalId":36341,"journal":{"name":"International Journal of Thermofluids","volume":"29 ","pages":"Article 101379"},"PeriodicalIF":0.0000,"publicationDate":"2025-08-15","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"International Journal of Thermofluids","FirstCategoryId":"1085","ListUrlMain":"https://www.sciencedirect.com/science/article/pii/S2666202725003258","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q1","JCRName":"Chemical Engineering","Score":null,"Total":0}
引用次数: 0
Abstract
The growing use of artificial intelligence has led to heavy thermal loads and high heat dissipation rates in data centers. Conventional air-cooled technologies are not able to fulfill these requirements. To overcome these challenges, two-phase immersion cooling (2PIC) has emerged as one of the leading technologies for high power-density chips. 2PIC increases the heat dissipation rate and efficiency of the system while reducing the footprint of the cooling equipment. A fluid with adequate dielectric properties, a suitable normal boiling temperature to maintain chip temperatures, and good material compatibility, is desired for 2PIC system. In this study, the pool boiling heat transfer of a new developmental dielectric fluid, Opteon™ 2P50, was experimentally investigated. The heat transfer coefficients at various heat fluxes (20–150 kW/m2) and the critical heat flux were measured using a smooth aluminum surface. Compared with HFE-7100, Opteon™ 2P50 shows higher heat transfer coefficient (up to 59% higher) and a slightly lower value of critical heat flux (around 5.9% lower). The modified Cooper correlation with the optimized leading constant resulted in reliable prediction accuracy with a 5.3% mean absolute error percentage. Overall, these results indicate that the new dielectric fluid provides similar thermal performance to some legacy fluids.