An Improved Communication-Free Dual Characteristic Over Current-Based Protection Scheme for AC Microgrids

IF 1.9 4区 工程技术 Q3 ENGINEERING, ELECTRICAL & ELECTRONIC
Hossein Mohammadi Panah, Behrooz Zaker, Haidar Samet
{"title":"An Improved Communication-Free Dual Characteristic Over Current-Based Protection Scheme for AC Microgrids","authors":"Hossein Mohammadi Panah,&nbsp;Behrooz Zaker,&nbsp;Haidar Samet","doi":"10.1155/etep/5975734","DOIUrl":null,"url":null,"abstract":"<div>\n <p>The entry of distributed generation causes the network to become complicated, and as a result, the protection coordination between the network equipment is lost. In previous studies, three decision variables were considered for each directional overcurrent relay: time dial setting in the main mode, time dial setting in the backup mode, and pickup current (<i>I</i><sub><i>p</i></sub>). However, the minimum coordination time interval between the main and backup relay was lost. In this paper, communication-free dual characteristics directional overcurrent relays are used, considering six decision variables: <i>I</i><sub><i>p</i></sub>, time dial setting of the relays in the main and backup mode, breakpoint current, and the type of curves in main and backup operations. The proposed scheme maintains the minimum time interval between the main and backup relays, which reduces the operation time of the relays compared to previous studies. The proposed scheme is implemented on the modified IEEE 30-bus network distribution section. DIGSILENT software is used for simulation, and load currents and fault currents of protection relays in grid-connected and islanded conditions are extracted based on load flow and short circuit studies. Then, the optimization problem is solved using the genetic algorithm in MATLAB software, and optimal settings are obtained to minimize the operation time of the relays. The simulation results of the proposed method shows that the operation time of the relays can be improved by 17% compared with the previous existing method.</p>\n </div>","PeriodicalId":51293,"journal":{"name":"International Transactions on Electrical Energy Systems","volume":"2025 1","pages":""},"PeriodicalIF":1.9000,"publicationDate":"2025-07-10","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"https://onlinelibrary.wiley.com/doi/epdf/10.1155/etep/5975734","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"International Transactions on Electrical Energy Systems","FirstCategoryId":"5","ListUrlMain":"https://onlinelibrary.wiley.com/doi/10.1155/etep/5975734","RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"ENGINEERING, ELECTRICAL & ELECTRONIC","Score":null,"Total":0}
引用次数: 0

Abstract

The entry of distributed generation causes the network to become complicated, and as a result, the protection coordination between the network equipment is lost. In previous studies, three decision variables were considered for each directional overcurrent relay: time dial setting in the main mode, time dial setting in the backup mode, and pickup current (Ip). However, the minimum coordination time interval between the main and backup relay was lost. In this paper, communication-free dual characteristics directional overcurrent relays are used, considering six decision variables: Ip, time dial setting of the relays in the main and backup mode, breakpoint current, and the type of curves in main and backup operations. The proposed scheme maintains the minimum time interval between the main and backup relays, which reduces the operation time of the relays compared to previous studies. The proposed scheme is implemented on the modified IEEE 30-bus network distribution section. DIGSILENT software is used for simulation, and load currents and fault currents of protection relays in grid-connected and islanded conditions are extracted based on load flow and short circuit studies. Then, the optimization problem is solved using the genetic algorithm in MATLAB software, and optimal settings are obtained to minimize the operation time of the relays. The simulation results of the proposed method shows that the operation time of the relays can be improved by 17% compared with the previous existing method.

Abstract Image

一种改进的交流微电网无通信双特性过电流保护方案
分布式发电的进入使网络变得复杂,从而失去了网络设备之间的保护协调。在以往的研究中,每个方向过流继电器都考虑了三个决策变量:主模式时的时间拨号设置、备用模式时的时间拨号设置和拾取电流(Ip)。但是,丢失了主备中继之间的最小协调时间间隔。本文采用无通信双特性定向过流继电器,考虑了6个决策变量:Ip、继电器在主备模式时的时间拨盘整定值、断点电流和主备运行时的曲线类型。该方案保持了主备继电器之间最小的时间间隔,与以往的研究相比,减少了继电器的运行时间。该方案在改进的IEEE 30总线网络配电段上实现。利用DIGSILENT软件进行仿真,在负荷潮流和短路研究的基础上,提取并网状态和孤岛状态下保护继电器的负荷电流和故障电流。然后,利用MATLAB软件中的遗传算法对优化问题进行求解,得到继电器运行时间最小的最优整定值。仿真结果表明,与现有方法相比,该方法可使继电器的运行时间提高17%。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
International Transactions on Electrical Energy Systems
International Transactions on Electrical Energy Systems ENGINEERING, ELECTRICAL & ELECTRONIC-
CiteScore
6.70
自引率
8.70%
发文量
342
期刊介绍: International Transactions on Electrical Energy Systems publishes original research results on key advances in the generation, transmission, and distribution of electrical energy systems. Of particular interest are submissions concerning the modeling, analysis, optimization and control of advanced electric power systems. Manuscripts on topics of economics, finance, policies, insulation materials, low-voltage power electronics, plasmas, and magnetics will generally not be considered for review.
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信