{"title":"Estimation of Pressure Drop in the Refrigeration System of a Commercial Potato Cold Storage","authors":"Rubia Khatun, Manoj Kumar Chourasia","doi":"10.1111/jfpe.70108","DOIUrl":null,"url":null,"abstract":"<div>\n \n <p>This study is aimed at the estimation of pressure drop in the vapor compression refrigeration system of a commercial cold storage having a storage capacity of 6000 metric tons of potato. A generalized methodology is adopted for calculating the pressure drop by using the Darcy-Weibach and Chawla's correlations for single- and two-phase flows, respectively. The pressure drop was estimated between the two consecutive components for each section of the refrigeration system. The total estimated pressure drop was found to be equivalent to a temperature change of 2.7°C at −10°C evaporation temperature and 3.3°C at 35°C condensation temperature for the low-pressure and high-pressure sides, respectively. The pressure drop only in the suction line was calculated as 143 Pa per meter length, which was well below the recommended maximum limit of 678 Pa per meter of length. The estimated pressure drops were compared with the measured values by using the pressure gauge readings mounted at various sections and found to be in good agreement with a maximum deviation of 13.1% and 7.4% for higher and lower pressure sides, respectively.</p>\n </div>","PeriodicalId":15932,"journal":{"name":"Journal of Food Process Engineering","volume":"48 4","pages":""},"PeriodicalIF":2.7000,"publicationDate":"2025-04-22","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Journal of Food Process Engineering","FirstCategoryId":"97","ListUrlMain":"https://onlinelibrary.wiley.com/doi/10.1111/jfpe.70108","RegionNum":3,"RegionCategory":"农林科学","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"ENGINEERING, CHEMICAL","Score":null,"Total":0}
引用次数: 0
Abstract
This study is aimed at the estimation of pressure drop in the vapor compression refrigeration system of a commercial cold storage having a storage capacity of 6000 metric tons of potato. A generalized methodology is adopted for calculating the pressure drop by using the Darcy-Weibach and Chawla's correlations for single- and two-phase flows, respectively. The pressure drop was estimated between the two consecutive components for each section of the refrigeration system. The total estimated pressure drop was found to be equivalent to a temperature change of 2.7°C at −10°C evaporation temperature and 3.3°C at 35°C condensation temperature for the low-pressure and high-pressure sides, respectively. The pressure drop only in the suction line was calculated as 143 Pa per meter length, which was well below the recommended maximum limit of 678 Pa per meter of length. The estimated pressure drops were compared with the measured values by using the pressure gauge readings mounted at various sections and found to be in good agreement with a maximum deviation of 13.1% and 7.4% for higher and lower pressure sides, respectively.
期刊介绍:
This international research journal focuses on the engineering aspects of post-production handling, storage, processing, packaging, and distribution of food. Read by researchers, food and chemical engineers, and industry experts, this is the only international journal specifically devoted to the engineering aspects of food processing. Co-Editors M. Elena Castell-Perez and Rosana Moreira, both of Texas A&M University, welcome papers covering the best original research on applications of engineering principles and concepts to food and food processes.