Johannes Gehring;Raffael Schwanninger;Alexander Nowak;Bernd Wunder;Vincent Lorentz;Martin März
{"title":"Method for Detection and Limitation of Short-Circuit Currents for Semiconductor Circuit Breakers in LVDC Grids Using a Pre-Saturated Inductor","authors":"Johannes Gehring;Raffael Schwanninger;Alexander Nowak;Bernd Wunder;Vincent Lorentz;Martin März","doi":"10.1109/OJPEL.2025.3555797","DOIUrl":null,"url":null,"abstract":"This paper introduces an innovative non-destructive device designed to detect and limit short-circuit currents in LVDC grids. The proposed solution utilizes a transformer fully saturated by a permanent magnet during normal operation. When a short-circuit condition occurs, the transformer desaturates, reducing the rise in current and triggering the detection and protection mechanism. The structure and functionality of the device, along with the design criteria, are discussed. Additionally, optimization measures are presented, examined, and validated. Experimental results from the advanced device prototype demonstrate its effectiveness in detecting and limiting overcurrents. The device features a stable tripping threshold and can safely and reliably interrupt even low time constant capacitive short-circuits. This hardware-based detection solution is ideally suited for installation in a semiconductor circuit breaker.","PeriodicalId":93182,"journal":{"name":"IEEE open journal of power electronics","volume":"6 ","pages":"524-536"},"PeriodicalIF":5.0000,"publicationDate":"2025-03-31","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"https://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=10945435","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"IEEE open journal of power electronics","FirstCategoryId":"1085","ListUrlMain":"https://ieeexplore.ieee.org/document/10945435/","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q1","JCRName":"ENGINEERING, ELECTRICAL & ELECTRONIC","Score":null,"Total":0}
引用次数: 0
Abstract
This paper introduces an innovative non-destructive device designed to detect and limit short-circuit currents in LVDC grids. The proposed solution utilizes a transformer fully saturated by a permanent magnet during normal operation. When a short-circuit condition occurs, the transformer desaturates, reducing the rise in current and triggering the detection and protection mechanism. The structure and functionality of the device, along with the design criteria, are discussed. Additionally, optimization measures are presented, examined, and validated. Experimental results from the advanced device prototype demonstrate its effectiveness in detecting and limiting overcurrents. The device features a stable tripping threshold and can safely and reliably interrupt even low time constant capacitive short-circuits. This hardware-based detection solution is ideally suited for installation in a semiconductor circuit breaker.