Subsequent commutation failure suppression strategy of hybrid cascaded HVDC system based on coordinated control of CEC and VDCOL

IF 1.6 Q4 ENERGY & FUELS
He Wang, Daqian Zhang, Jing Bian, Jiazhi Guo, Shiqiang Li
{"title":"Subsequent commutation failure suppression strategy of hybrid cascaded HVDC system based on coordinated control of CEC and VDCOL","authors":"He Wang,&nbsp;Daqian Zhang,&nbsp;Jing Bian,&nbsp;Jiazhi Guo,&nbsp;Shiqiang Li","doi":"10.1049/esi2.12180","DOIUrl":null,"url":null,"abstract":"<p>The inverter side of hybrid cascaded HVDC adopts the structure of Modular Multilevel Converter (MMC) in series with Line Commutated Converter (LCC). The complete system amalgamates the advantages of LCC with MMC, but it also makes the interaction process of multi-controller more complicated during the failure of the system. Therefore, through the analysis of the controller interaction process during the system fault, this paper proposes a multi-controller coordinated control strategy based on the inverter side of the hybrid cascaded HVDC system, which can suppress the subsequent commutation failure of the system and take into account the recovery characteristics of the system during the fault, which has certain practical application value. Initially, the operational properties of current error control (CEC) and voltage-dependent current limit control (VDCOL) are examined, and a coordinated control technique for subsequent commutation failure suppression and rapid power recovery during fault is proposed. Secondly, aiming at the problem of power return between MMC after VDCOL regulation, the new VDCOL control curve is coordinated to improve the MMC control strategy to ensure stable recovery during system failure. Finally, the simulation model is built in PSCAD/EMTDC simulation environment. The simulation results indicate that the proposed control technique can successfully achieve the synchronisation of commutation failure suppression and rapid, stable power restoration, thereby enhancing the operational performance of hybrid cascaded HVDC.</p>","PeriodicalId":33288,"journal":{"name":"IET Energy Systems Integration","volume":"6 S1","pages":"932-945"},"PeriodicalIF":1.6000,"publicationDate":"2024-12-19","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"https://onlinelibrary.wiley.com/doi/epdf/10.1049/esi2.12180","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"IET Energy Systems Integration","FirstCategoryId":"1085","ListUrlMain":"https://onlinelibrary.wiley.com/doi/10.1049/esi2.12180","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q4","JCRName":"ENERGY & FUELS","Score":null,"Total":0}
引用次数: 0

Abstract

The inverter side of hybrid cascaded HVDC adopts the structure of Modular Multilevel Converter (MMC) in series with Line Commutated Converter (LCC). The complete system amalgamates the advantages of LCC with MMC, but it also makes the interaction process of multi-controller more complicated during the failure of the system. Therefore, through the analysis of the controller interaction process during the system fault, this paper proposes a multi-controller coordinated control strategy based on the inverter side of the hybrid cascaded HVDC system, which can suppress the subsequent commutation failure of the system and take into account the recovery characteristics of the system during the fault, which has certain practical application value. Initially, the operational properties of current error control (CEC) and voltage-dependent current limit control (VDCOL) are examined, and a coordinated control technique for subsequent commutation failure suppression and rapid power recovery during fault is proposed. Secondly, aiming at the problem of power return between MMC after VDCOL regulation, the new VDCOL control curve is coordinated to improve the MMC control strategy to ensure stable recovery during system failure. Finally, the simulation model is built in PSCAD/EMTDC simulation environment. The simulation results indicate that the proposed control technique can successfully achieve the synchronisation of commutation failure suppression and rapid, stable power restoration, thereby enhancing the operational performance of hybrid cascaded HVDC.

Abstract Image

求助全文
约1分钟内获得全文 求助全文
来源期刊
IET Energy Systems Integration
IET Energy Systems Integration Engineering-Engineering (miscellaneous)
CiteScore
5.90
自引率
8.30%
发文量
29
审稿时长
11 weeks
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信