{"title":"Research on PI automatic tracking and arc elimination method based on phase deviation‐fault residual voltage control","authors":"Hongwen Liu, Xiangjun Zeng, Qing Yang, Chenchao Chai","doi":"10.1002/cta.4202","DOIUrl":null,"url":null,"abstract":"Aiming at the problem that the current arc suppression method of coil cannot achieve full compensation. First, the calculation model of the full compensation parameters of the controllable voltage source is established by analyzing the grounding fault arc suppression principle of the independent controllable voltage source and the parallel arc suppression coil. Second, by analyzing the arc suppression characteristics of controllable voltage source, a PI automatic regulation method based on phase deviation‐fault residual voltage control is proposed. The method uses fault residual voltage and the change of output voltage amplitude of controllable voltage source to control the adjustment direction and fault residual voltage to control the output voltage amplitude of controllable voltage source. The simulation results show that when the capacitive current of the distribution network is 24.47 A, the fault residual voltage is 2.5 V and the residual current is 446 mA after compensation by the independent controllable voltage source. When the capacitive current is 40.8 A and the deharmonic degree of arc suppression coil is −9%, the fault residual voltage and residual current are 2.2 V and 60 mA after compensated by the parallel arc suppression coil of the controlled voltage source. The proposed PI control method exhibits good stability, resulting in low fault residual voltage, and outperforms traditional control methods, enhancing the arc extinction effect of ground faults.","PeriodicalId":13874,"journal":{"name":"International Journal of Circuit Theory and Applications","volume":"155 1","pages":""},"PeriodicalIF":1.8000,"publicationDate":"2024-08-13","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"International Journal of Circuit Theory and Applications","FirstCategoryId":"5","ListUrlMain":"https://doi.org/10.1002/cta.4202","RegionNum":3,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"ENGINEERING, ELECTRICAL & ELECTRONIC","Score":null,"Total":0}
引用次数: 0
Abstract
Aiming at the problem that the current arc suppression method of coil cannot achieve full compensation. First, the calculation model of the full compensation parameters of the controllable voltage source is established by analyzing the grounding fault arc suppression principle of the independent controllable voltage source and the parallel arc suppression coil. Second, by analyzing the arc suppression characteristics of controllable voltage source, a PI automatic regulation method based on phase deviation‐fault residual voltage control is proposed. The method uses fault residual voltage and the change of output voltage amplitude of controllable voltage source to control the adjustment direction and fault residual voltage to control the output voltage amplitude of controllable voltage source. The simulation results show that when the capacitive current of the distribution network is 24.47 A, the fault residual voltage is 2.5 V and the residual current is 446 mA after compensation by the independent controllable voltage source. When the capacitive current is 40.8 A and the deharmonic degree of arc suppression coil is −9%, the fault residual voltage and residual current are 2.2 V and 60 mA after compensated by the parallel arc suppression coil of the controlled voltage source. The proposed PI control method exhibits good stability, resulting in low fault residual voltage, and outperforms traditional control methods, enhancing the arc extinction effect of ground faults.
针对线圈电流消弧方式无法实现全补偿的问题。首先,通过分析独立可控电压源和并联消弧线圈的接地故障消弧原理,建立了可控电压源全补偿参数的计算模型。其次,通过分析可控电压源的消弧特性,提出了一种基于相位偏差-故障残压控制的 PI 自动调节方法。该方法利用故障残压和可控电压源输出电压幅值的变化来控制调节方向,利用故障残压来控制可控电压源的输出电压幅值。仿真结果表明,当配电网电容电流为 24.47 A 时,经独立可控电压源补偿后,故障残压为 2.5 V,残流为 446 mA。当电容电流为 40.8 A,消弧线圈的失谐度为-9%时,通过可控电压源的并联消弧线圈补偿后,故障残压和残流分别为 2.2 V 和 60 mA。所提出的 PI 控制方法稳定性好,故障残压低,优于传统控制方法,增强了接地故障的消弧效果。
期刊介绍:
The scope of the Journal comprises all aspects of the theory and design of analog and digital circuits together with the application of the ideas and techniques of circuit theory in other fields of science and engineering. Examples of the areas covered include: Fundamental Circuit Theory together with its mathematical and computational aspects; Circuit modeling of devices; Synthesis and design of filters and active circuits; Neural networks; Nonlinear and chaotic circuits; Signal processing and VLSI; Distributed, switched and digital circuits; Power electronics; Solid state devices. Contributions to CAD and simulation are welcome.