{"title":"HVDC system performance with a neutral conductor","authors":"V. Jankov, Mark Stobart","doi":"10.1109/ICHVE.2010.5640834","DOIUrl":null,"url":null,"abstract":"The poles of bipolar HVDC transmission systems are often required to be capable of independent operation. In order to maintain the independence of the poles a return path for the current is needed. If a ground return cannot be used a neutral conductor must be installed, either on the same structures as the pole conductors or on separate structures. A fault on one pole of such a system may cause a fault on the neutral and a fault on the other pole; therefore, a fault must be efficiently cleared. This paper examines the effect a neutral conductor has on HVDC system reliability and the effectiveness of fault clearing devices such as arcing horns and neutral grounding breakers.","PeriodicalId":287425,"journal":{"name":"2010 International Conference on High Voltage Engineering and Application","volume":"33 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2010-11-18","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"8","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2010 International Conference on High Voltage Engineering and Application","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICHVE.2010.5640834","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 8
Abstract
The poles of bipolar HVDC transmission systems are often required to be capable of independent operation. In order to maintain the independence of the poles a return path for the current is needed. If a ground return cannot be used a neutral conductor must be installed, either on the same structures as the pole conductors or on separate structures. A fault on one pole of such a system may cause a fault on the neutral and a fault on the other pole; therefore, a fault must be efficiently cleared. This paper examines the effect a neutral conductor has on HVDC system reliability and the effectiveness of fault clearing devices such as arcing horns and neutral grounding breakers.