{"title":"A Self-Tuning Fuzzy Logic Controller for Superheat of Evaporator by Using Electronic Expansion Valve","authors":"H. Tian, Jiangang Lu, Qinmin Yang","doi":"10.1109/ISCID.2013.76","DOIUrl":null,"url":null,"abstract":"In this paper, a self-tuning fuzzy logic controller (STFLC) is proposed to maintain the evaporator superheat via an electronic expansion valve (EEV) in a vapor compression chiller system. The output scaling factor (SF) of the STFLC is tuned in an on-line manner by fuzzy rules according to the current condition of the process. To verify the performance of the proposed control scheme, real-time experiments have been conducted on a pilot vapor compression chiller system. The results demonstrate that the controller design outperforms its conventional counterpart in keeping the evaporator superheat at a desired value even when the refrigeration load is changed over a wide range.","PeriodicalId":297027,"journal":{"name":"2013 Sixth International Symposium on Computational Intelligence and Design","volume":"5 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2013-10-28","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2013 Sixth International Symposium on Computational Intelligence and Design","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ISCID.2013.76","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1
Abstract
In this paper, a self-tuning fuzzy logic controller (STFLC) is proposed to maintain the evaporator superheat via an electronic expansion valve (EEV) in a vapor compression chiller system. The output scaling factor (SF) of the STFLC is tuned in an on-line manner by fuzzy rules according to the current condition of the process. To verify the performance of the proposed control scheme, real-time experiments have been conducted on a pilot vapor compression chiller system. The results demonstrate that the controller design outperforms its conventional counterpart in keeping the evaporator superheat at a desired value even when the refrigeration load is changed over a wide range.