{"title":"Study on method of single-phase-to-earth fault section location in neutral point resonant grounded system","authors":"Qi Zheng, Zheng Zhao, Y. Yihan","doi":"10.1109/CRIS.2010.5617537","DOIUrl":null,"url":null,"abstract":"Due to the large amount of branches and high grounding resistance of the distribution network, the earth fault location has not been solved effectively. A live location method is proposed for the single-phase-to-earth fault section in the neutral point resonant grounded system. By this method, the compensation current of arc-suppression coil is adjusted after the metallic earth fault occurs. And the fault section can be confirmed by the variation of zero-sequence current measured by FTU equipped in the lines, for the zero-sequence current in the non-fault path is proportional to the zero-sequence voltage. When the single-phase-to-earth fault via resistance occurs, zero-sequence voltage changes after the arc-suppression coil is adjusted. The method is also effective as long as the zero-sequence current is converted by zero-sequence voltage. The site experiments have been carried out to prove that the method is feasible.","PeriodicalId":206094,"journal":{"name":"2010 5th International Conference on Critical Infrastructure (CRIS)","volume":"49 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2010-11-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2010 5th International Conference on Critical Infrastructure (CRIS)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CRIS.2010.5617537","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 2
Abstract
Due to the large amount of branches and high grounding resistance of the distribution network, the earth fault location has not been solved effectively. A live location method is proposed for the single-phase-to-earth fault section in the neutral point resonant grounded system. By this method, the compensation current of arc-suppression coil is adjusted after the metallic earth fault occurs. And the fault section can be confirmed by the variation of zero-sequence current measured by FTU equipped in the lines, for the zero-sequence current in the non-fault path is proportional to the zero-sequence voltage. When the single-phase-to-earth fault via resistance occurs, zero-sequence voltage changes after the arc-suppression coil is adjusted. The method is also effective as long as the zero-sequence current is converted by zero-sequence voltage. The site experiments have been carried out to prove that the method is feasible.