Influence of grid-connected inverters on the power quality of the distribution grid

B. Verhelst, Jurgen Van Ryckeghem, J. Desmet
{"title":"Influence of grid-connected inverters on the power quality of the distribution grid","authors":"B. Verhelst, Jurgen Van Ryckeghem, J. Desmet","doi":"10.1109/SPEEDAM.2014.6872002","DOIUrl":null,"url":null,"abstract":"Many inverters are quoted as having a PF of better than 0.95 when in reality, the true power factor is between 0.5 and 0.75. This paper describes the influence of grid-connected inverters on the distribution grid. The impact of the voltage distortion from the inverter to the distribution grid is relative small without grid impedance. When the grid impedance is involved, the distortion will become higher and so, more harmonics will be injected into the grid. The impact of the current distortion is especially high at low power output, but decreases fast at moderate or high power. If the background distortion of the grid increases, there will be an increase of the voltage and current harmonics. The specific limits of the EN 50160 and IEC 61000-3-12 could be exceeded at such high pollution.","PeriodicalId":344918,"journal":{"name":"2014 International Symposium on Power Electronics, Electrical Drives, Automation and Motion","volume":"19 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2014-06-18","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2014 International Symposium on Power Electronics, Electrical Drives, Automation and Motion","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/SPEEDAM.2014.6872002","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

Many inverters are quoted as having a PF of better than 0.95 when in reality, the true power factor is between 0.5 and 0.75. This paper describes the influence of grid-connected inverters on the distribution grid. The impact of the voltage distortion from the inverter to the distribution grid is relative small without grid impedance. When the grid impedance is involved, the distortion will become higher and so, more harmonics will be injected into the grid. The impact of the current distortion is especially high at low power output, but decreases fast at moderate or high power. If the background distortion of the grid increases, there will be an increase of the voltage and current harmonics. The specific limits of the EN 50160 and IEC 61000-3-12 could be exceeded at such high pollution.
并网逆变器对配电网电能质量的影响
许多逆变器被引用为具有优于0.95的PF,而实际上,真正的功率因数在0.5和0.75之间。本文介绍了并网逆变器对配电网的影响。无电网阻抗时,逆变器电压畸变对配电网的影响相对较小。当涉及到电网阻抗时,失真会变大,从而会向电网注入更多的谐波。在低功率输出时,电流畸变的影响特别大,但在中等或高功率输出时减小得很快。如果电网的背景失真增大,电压和电流的谐波就会增大。在如此高的污染下,可能会超过EN 50160和IEC 61000-3-12的特定限值。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信