Transient stability of power systems with different configurations for wind power integration

H. Abdelhalim, A. Farid, A. Adegbege, K. Youcef-Toumi
{"title":"Transient stability of power systems with different configurations for wind power integration","authors":"H. Abdelhalim, A. Farid, A. Adegbege, K. Youcef-Toumi","doi":"10.1109/ISGT.2013.6497903","DOIUrl":null,"url":null,"abstract":"Previous transient stability studies investigating the effects of wind power integration into a conventional power system assume the insertion point of the wind-generating units to be at the same bus and interconnection voltage as the synchronous generators they are substituting or complementing. While these assumptions offer some insights into the effects of the wind on the existing system, important points about the physical distance and interconnection voltage of wind farms with respect to the conventional power system are neglected. This paper analyzes the effects of integrating doubly-fed induction wind turbine generators through different transmission line configurations and at different buses. The IEEE 14-bus test system is used in order to compare results with previous works. Results show that connecting wind generators through transmission lines and to different buses introducesdelays in the speed dynamic responses of existing synchronous generators. These delays in turn affect the bus voltage oscillations. Results also show that there is no significant effect on the base cases when using different interconnection voltages to connect the wind. The results of this study can be used by power system operators when deciding how to connect wind farms to an existing power network when optimizing for stability response to a large fault. Overall, wind farms should be connected through additional transmission lines to buses near where synchronous generators are located and further away from loads and higher risk fault areas.","PeriodicalId":268687,"journal":{"name":"2013 IEEE PES Innovative Smart Grid Technologies Conference (ISGT)","volume":"77 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2013-04-15","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"7","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2013 IEEE PES Innovative Smart Grid Technologies Conference (ISGT)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ISGT.2013.6497903","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 7

Abstract

Previous transient stability studies investigating the effects of wind power integration into a conventional power system assume the insertion point of the wind-generating units to be at the same bus and interconnection voltage as the synchronous generators they are substituting or complementing. While these assumptions offer some insights into the effects of the wind on the existing system, important points about the physical distance and interconnection voltage of wind farms with respect to the conventional power system are neglected. This paper analyzes the effects of integrating doubly-fed induction wind turbine generators through different transmission line configurations and at different buses. The IEEE 14-bus test system is used in order to compare results with previous works. Results show that connecting wind generators through transmission lines and to different buses introducesdelays in the speed dynamic responses of existing synchronous generators. These delays in turn affect the bus voltage oscillations. Results also show that there is no significant effect on the base cases when using different interconnection voltages to connect the wind. The results of this study can be used by power system operators when deciding how to connect wind farms to an existing power network when optimizing for stability response to a large fault. Overall, wind farms should be connected through additional transmission lines to buses near where synchronous generators are located and further away from loads and higher risk fault areas.
风电一体化中不同配置电力系统的暂态稳定性
以往研究风力发电并入传统电力系统的暂态稳定性研究,都假定风力发电机组的插入点与它们所替代或补充的同步发电机处于相同的母线和互联电压。虽然这些假设对风力对现有系统的影响提供了一些见解,但关于风力发电场相对于传统电力系统的物理距离和互连电压的关键点却被忽视了。分析了不同传输线配置和不同母线对双馈感应风力发电机组集成的影响。采用IEEE 14总线测试系统,与以往的工作结果进行比较。结果表明,将风力发电机通过传输线连接到不同的母线上,会给现有同步发电机的速度动态响应带来延迟。这些延迟反过来影响母线电压振荡。结果还表明,采用不同的接风电压对基本工况没有显著影响。这项研究的结果可以为电力系统运营商在决定如何将风电场连接到现有电网时使用,同时优化对大故障的稳定性响应。总的来说,风力发电场应该通过额外的传输线连接到靠近同步发电机位置的公共汽车上,远离负载和高风险的故障区域。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信