Selection of transformers for commercial buildings

R. Dwyer, D. Mueller
{"title":"Selection of transformers for commercial buildings","authors":"R. Dwyer, D. Mueller","doi":"10.1109/IAS.1992.244263","DOIUrl":null,"url":null,"abstract":"Standards dealing with the application of transformers subjected to harmonic load currents are clarified, and application guidelines are provided. The impact of harmonic currents in commercial building systems needs to be considered, due to the increased use of electrical equipment that draw nonsinusoidal current from the AC line. A transformer subjected to harmonic load currents should have a K-factor rating higher than that of the load it supplies. It is preferable to use a K-factor-rated transformer, rather than derating a general-purpose transformer. If the transformer is not K-factor rated, its maximum load kVA should be limited in accordance with ANSI/IEEE Standard C57.110, which applies to general-purpose transformers that are subjected to a load current with total harmonic distortion greater than 5%. Most applications for K-factor-rated transformers require either K=4 or K=13. Higher K-factor specifications should be examined for erroneous assumptions regarding load characteristics. The ANSI/IEEE Std. C57.110 derating calculation is very sensitive to errors in the input data; typical values and rules of thumb should be avoided.<<ETX>>","PeriodicalId":110710,"journal":{"name":"Conference Record of the 1992 IEEE Industry Applications Society Annual Meeting","volume":"79 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1992-10-04","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"6","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Conference Record of the 1992 IEEE Industry Applications Society Annual Meeting","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/IAS.1992.244263","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 6

Abstract

Standards dealing with the application of transformers subjected to harmonic load currents are clarified, and application guidelines are provided. The impact of harmonic currents in commercial building systems needs to be considered, due to the increased use of electrical equipment that draw nonsinusoidal current from the AC line. A transformer subjected to harmonic load currents should have a K-factor rating higher than that of the load it supplies. It is preferable to use a K-factor-rated transformer, rather than derating a general-purpose transformer. If the transformer is not K-factor rated, its maximum load kVA should be limited in accordance with ANSI/IEEE Standard C57.110, which applies to general-purpose transformers that are subjected to a load current with total harmonic distortion greater than 5%. Most applications for K-factor-rated transformers require either K=4 or K=13. Higher K-factor specifications should be examined for erroneous assumptions regarding load characteristics. The ANSI/IEEE Std. C57.110 derating calculation is very sensitive to errors in the input data; typical values and rules of thumb should be avoided.<>
商业建筑变压器的选择
澄清了变压器在谐波负载电流下的应用标准,并提供了应用指南。由于越来越多地使用从交流线路中吸取非正弦电流的电气设备,因此需要考虑商业建筑系统中谐波电流的影响。受谐波负载电流作用的变压器,其k因子额定值应高于其所供电负载的k因子额定值。最好使用k因子额定变压器,而不是通用变压器降额。如果变压器不是k因子额定的,则其最大负载kVA应按照ANSI/IEEE标准C57.110进行限制,该标准适用于负载电流总谐波失真大于5%的通用变压器。大多数K因子额定变压器的应用要求K=4或K=13。应检查较高的k因子规格是否存在有关负载特性的错误假设。ANSI/IEEE Std. C57.110降额计算对输入数据中的误差非常敏感;应该避免典型的价值观和经验法则。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信