Experimental Analysis of Server Fan Control Strategies for Improved Data Center Air-based Thermal Management*

J. Sarkinen, Rickard Brännvall, Jonas Gustafsson, J. Summers
{"title":"Experimental Analysis of Server Fan Control Strategies for Improved Data Center Air-based Thermal Management*","authors":"J. Sarkinen, Rickard Brännvall, Jonas Gustafsson, J. Summers","doi":"10.1109/ITherm45881.2020.9190337","DOIUrl":null,"url":null,"abstract":"This paper analyzes the prospects of a holistic air-cooling strategy that enables synchronisation of data center facility fans and server fans to minimize data center energy use. Each server is equipped with a custom circuit board which controls the fans using a proportional, integral and derivative (PID) controller running on the servers operating system to maintain constant operating temperatures, irrespective of environmental conditions or workload. Experiments are carried out in a server wind tunnel which is controlled to mimic data center environmental conditions. The wind tunnel fan, humidifier and heater are controlled via separate PID controllers to maintain a prescribed pressure drop across the server with air entering at a defined temperature and humidity. The experiments demonstrate server operating temperatures which optimally trade off power losses versus server fan power, while examining the effect on the temperature difference, ∆T. Furthermore the results are theoretically applied to a direct fresh air cooled data center to obtain holistic sweet spots for the servers, revealing that the minimum energy use is already attained by factory control. Power consumption and Power Usage Effectiveness (PUE) are also compared, confirming that decreasing the PUE can increase the overall data center power consumption. Lastly the effect of decreased server inlet temperatures is examined showing that lower inlet temperatures can reduce both energy consumption and PUE.","PeriodicalId":193052,"journal":{"name":"2020 19th IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm)","volume":"20 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2020-07-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"10","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2020 19th IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ITherm45881.2020.9190337","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 10

Abstract

This paper analyzes the prospects of a holistic air-cooling strategy that enables synchronisation of data center facility fans and server fans to minimize data center energy use. Each server is equipped with a custom circuit board which controls the fans using a proportional, integral and derivative (PID) controller running on the servers operating system to maintain constant operating temperatures, irrespective of environmental conditions or workload. Experiments are carried out in a server wind tunnel which is controlled to mimic data center environmental conditions. The wind tunnel fan, humidifier and heater are controlled via separate PID controllers to maintain a prescribed pressure drop across the server with air entering at a defined temperature and humidity. The experiments demonstrate server operating temperatures which optimally trade off power losses versus server fan power, while examining the effect on the temperature difference, ∆T. Furthermore the results are theoretically applied to a direct fresh air cooled data center to obtain holistic sweet spots for the servers, revealing that the minimum energy use is already attained by factory control. Power consumption and Power Usage Effectiveness (PUE) are also compared, confirming that decreasing the PUE can increase the overall data center power consumption. Lastly the effect of decreased server inlet temperatures is examined showing that lower inlet temperatures can reduce both energy consumption and PUE.
改进数据中心空气热管理的服务器风扇控制策略实验分析*
本文分析了整体空气冷却策略的前景,该策略使数据中心设施风扇和服务器风扇能够同步,以最大限度地减少数据中心的能源使用。每台服务器都配备了一个定制的电路板,使用在服务器操作系统上运行的比例,积分和导数(PID)控制器来控制风扇,以保持恒定的工作温度,无论环境条件或工作量如何。实验在模拟数据中心环境条件的服务器风洞中进行。风洞风扇、加湿器和加热器通过单独的PID控制器控制,以保持服务器上规定的压降,并使空气在规定的温度和湿度下进入。实验证明了服务器的工作温度最优地平衡了功率损耗与服务器风扇功率,同时检查了对温差∆T的影响。此外,理论结果应用于直接新鲜空气冷却的数据中心,以获得服务器的整体最佳点,表明工厂控制已经达到了最小的能源使用。还比较了功耗和电源使用效率(PUE),确认降低PUE会增加数据中心的整体功耗。最后,研究了降低服务器入口温度的影响,表明降低入口温度可以降低能耗和PUE。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信