{"title":"Effect of ageing on the impulse breakdown strength of oil-impregnated pressboard used in power transformers","authors":"H. Ding, Z. Wang, P. Jarman","doi":"10.1109/CEIDP.2006.311978","DOIUrl":null,"url":null,"abstract":"This paper presents the lightning impulse voltage test results of service-aged pressboards taken from a failed power transformer after 29 years' service. Impulse voltage tests have revealed that there is a significant reduction of breakdown voltages, most probably due to the degradation of mechanical strength. The minimum impulse electric strength may reduce approximately by 30% after 29 years' service. Test results on the service-aged pressboard also indicate that when the moisture content in pressboard is less than 4%, there is no significant correlation between the reductions of the impulse electric strength with increasing moisture content.","PeriodicalId":219099,"journal":{"name":"2006 IEEE Conference on Electrical Insulation and Dielectric Phenomena","volume":"8 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2006-10-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"13","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2006 IEEE Conference on Electrical Insulation and Dielectric Phenomena","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CEIDP.2006.311978","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 13
Abstract
This paper presents the lightning impulse voltage test results of service-aged pressboards taken from a failed power transformer after 29 years' service. Impulse voltage tests have revealed that there is a significant reduction of breakdown voltages, most probably due to the degradation of mechanical strength. The minimum impulse electric strength may reduce approximately by 30% after 29 years' service. Test results on the service-aged pressboard also indicate that when the moisture content in pressboard is less than 4%, there is no significant correlation between the reductions of the impulse electric strength with increasing moisture content.