{"title":"Arc flash mitigation in a chemical and refining facility using IEC 61850","authors":"F. Dixon, M. Yunas, V. Wedelich, J. Howard, H. E. Brown, S. Sauer, Y. Xu, T. Markello, W. Sheikh","doi":"10.1109/PCICON.2012.6549669","DOIUrl":null,"url":null,"abstract":"This paper describes the design, testing, and commissioning of modified low voltage switchgear located in a major chemical and refining complex. The intent of the redesign was to significantly reduce the incident energy at the line and bus side of the low voltage lineups. The company mandated that the incident energy should be reduced to Category 3 (25 cal/cm2 or less) at the low voltage line side of the main breakers and to Category 2 (8 cal/cm2 or less) at the bus or load side of the low voltage main breakers. To achieve the reduction of incident energy, new relaying schemes used arc flash sensors and high speed Ethernet networks with GOOSE messaging to send protection and metering information to upstream relays. This paper describes the efforts to modify the equipment, the demonstration tests to show that the protection scheme worked as expected, and the system commissioning.","PeriodicalId":133636,"journal":{"name":"2012 Petroleum and Chemical Industry Conference (PCIC)","volume":"153 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2012-09-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2012 Petroleum and Chemical Industry Conference (PCIC)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/PCICON.2012.6549669","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1
Abstract
This paper describes the design, testing, and commissioning of modified low voltage switchgear located in a major chemical and refining complex. The intent of the redesign was to significantly reduce the incident energy at the line and bus side of the low voltage lineups. The company mandated that the incident energy should be reduced to Category 3 (25 cal/cm2 or less) at the low voltage line side of the main breakers and to Category 2 (8 cal/cm2 or less) at the bus or load side of the low voltage main breakers. To achieve the reduction of incident energy, new relaying schemes used arc flash sensors and high speed Ethernet networks with GOOSE messaging to send protection and metering information to upstream relays. This paper describes the efforts to modify the equipment, the demonstration tests to show that the protection scheme worked as expected, and the system commissioning.