The round cell: promises vs. results 30 years later

A. Cannone, W. Cantor, D. Feder, J.P. Stevens
{"title":"The round cell: promises vs. results 30 years later","authors":"A. Cannone, W. Cantor, D. Feder, J.P. Stevens","doi":"10.1109/INTLEC.2004.1401500","DOIUrl":null,"url":null,"abstract":"In the late 1960's Bell Laboratories developed a novel cylindrical design for a stationary reserve lead acid battery to provide back-up power in the Bell Telephone System's central offices. The extensive laboratory test and evaluation data suggested that this design should significantly extend the expected life and reduce maintenance in telephone float service vs. conventional designs available at that time. Limited commercial production of this design was initiated in 1972, with full-scale production at two manufacturers underway by 1974. To date more than 1.5 million cells have been made, installed and used by the divested telecom heirs to their Bell System forefathers, as well as nonBell companies. Actual discharge test, field inspection and overall performance evaluation results are presented on more than 14,000 individual round cells, ranging from less than one to more than 24 years in service. Round cell string capacity tests show a level trend with no string failures for the full 24-year period. Individual round cell tests of the 14,568 round cell population indicate a worst case failure rate of 19 round cells in the 14,568 cell population, or 0.1% failure. Eliminating cells of questionable suitability (not recharged, etc.) results in a failure rate of only 2 cells of the 14,551 remaining round cell population, or 0.01% failure. The 1970's accelerated tests had projected plate growth to reach only 2% in 70 years. Plate growth data from round cells removed from field service for 7, 15 and 23 years appear to confirm that projection. The data also indicates zero post seal or jar cover seal leakage in any of the more than 14,000 round cells tested, in stark contrast to the traditional field expectations of post seal and jar/cover seal leakage in either rectangular flooded or valve regulated lead acid (VRLA) cell designs. An actual post seal leakage rate of 4 to 10 percent was found on the more than 28,000 rectangular flooded cell population tested. Capacity test results on the >14,000 VRLA cell test population follow results of other recent publications. VRLA average string capacities trend linearly downward with age, reaching 80% in only 5 years. This study lends further credence to what appeared at the time to be exorbitant promises of the 1970's with regard to both reduced capacity aging and grid growth rates. This study also reports a zero rate of post seal and jar/cover seal leakage, unique in the industry.","PeriodicalId":192956,"journal":{"name":"INTELEC 2004. 26th Annual International Telecommunications Energy Conference","volume":"120 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2004-09-19","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"5","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"INTELEC 2004. 26th Annual International Telecommunications Energy Conference","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/INTLEC.2004.1401500","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 5

Abstract

In the late 1960's Bell Laboratories developed a novel cylindrical design for a stationary reserve lead acid battery to provide back-up power in the Bell Telephone System's central offices. The extensive laboratory test and evaluation data suggested that this design should significantly extend the expected life and reduce maintenance in telephone float service vs. conventional designs available at that time. Limited commercial production of this design was initiated in 1972, with full-scale production at two manufacturers underway by 1974. To date more than 1.5 million cells have been made, installed and used by the divested telecom heirs to their Bell System forefathers, as well as nonBell companies. Actual discharge test, field inspection and overall performance evaluation results are presented on more than 14,000 individual round cells, ranging from less than one to more than 24 years in service. Round cell string capacity tests show a level trend with no string failures for the full 24-year period. Individual round cell tests of the 14,568 round cell population indicate a worst case failure rate of 19 round cells in the 14,568 cell population, or 0.1% failure. Eliminating cells of questionable suitability (not recharged, etc.) results in a failure rate of only 2 cells of the 14,551 remaining round cell population, or 0.01% failure. The 1970's accelerated tests had projected plate growth to reach only 2% in 70 years. Plate growth data from round cells removed from field service for 7, 15 and 23 years appear to confirm that projection. The data also indicates zero post seal or jar cover seal leakage in any of the more than 14,000 round cells tested, in stark contrast to the traditional field expectations of post seal and jar/cover seal leakage in either rectangular flooded or valve regulated lead acid (VRLA) cell designs. An actual post seal leakage rate of 4 to 10 percent was found on the more than 28,000 rectangular flooded cell population tested. Capacity test results on the >14,000 VRLA cell test population follow results of other recent publications. VRLA average string capacities trend linearly downward with age, reaching 80% in only 5 years. This study lends further credence to what appeared at the time to be exorbitant promises of the 1970's with regard to both reduced capacity aging and grid growth rates. This study also reports a zero rate of post seal and jar/cover seal leakage, unique in the industry.
圆形细胞:承诺与30年后的结果
在20世纪60年代末,贝尔实验室开发了一种新颖的圆柱形设计,用于固定备用铅酸电池,为贝尔电话系统的中央办公室提供备用电源。大量的实验室测试和评估数据表明,与当时可用的传统设计相比,这种设计可以显着延长电话浮子服务的预期寿命并减少维护。这种设计的有限商业生产在1972年开始,到1974年在两家制造商进行全面生产。迄今为止,从贝尔系统前辈手中剥离出来的电信继承人以及非贝尔公司已经制造、安装和使用了150多万个基站。实际放电测试,现场检查和整体性能评估结果呈现在超过14000个单独的圆形电池,从不足1年到超过24年的服务。圆单元管柱容量测试显示,在整个24年期间,没有出现管柱故障。14,568个圆形细胞群的单个圆形细胞测试表明,14,568个圆形细胞群中最坏情况下的失败率为19个圆形细胞,即失败率为0.1%。排除适用性有问题的细胞(未充电等)导致14,551个剩余圆形细胞群中只有2个细胞的故障率,或0.01%的失败率。20世纪70年代的加速试验预测,在70年内,板块增长率仅为2%。7年、15年和23年从野外移除的圆形细胞的平板生长数据似乎证实了这一预测。数据还表明,在测试的14000多个圆形电池中,任何一个电池的后密封或罐盖密封都没有泄漏,这与传统的矩形淹水或阀控铅酸(VRLA)电池设计的后密封和罐盖密封泄漏形成鲜明对比。实际密封后泄漏率为4%至10%,在超过28,000个矩形淹水电池中进行了测试。对>14,000 VRLA细胞测试群体的容量测试结果遵循其他近期出版物的结果。VRLA平均管柱容量随年龄呈线性下降趋势,仅5年就达到80%。这项研究进一步证实了20世纪70年代关于降低容量老化和电网增长率的过高承诺。这项研究还报告了零后密封和罐/盖密封泄漏率,这在行业中是独一无二的。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书